Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 20:38

Tabular Output Report in Format: HTML

Building: Hospital

Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745

Simulation Timestamp: 2020-06-03 20:39:13


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2020-06-03 20:39:13

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 25732.73 1146.93 1146.93
Net Site Energy 25732.73 1146.93 1146.93
Total Source Energy 71807.21 3200.51 3200.51
Net Source Energy 71807.21 3200.51 3200.51


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 22436.18
Net Conditioned Building Area 22436.18
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 150.39 793.75 0.00 0.00 0.00 0.00
Cooling 2978.09 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3278.44 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 155.12 0.00 0.00 0.00 0.00 0.00
Interior Equipment 6892.71 2791.97 0.00 0.00 0.00 0.00
Exterior Equipment 2578.09 0.00 0.00 0.00 0.00 0.00
Fans 2979.62 0.00 0.00 0.00 0.00 0.00
Pumps 427.85 0.00 0.00 0.00 0.00 0.00
Heat Rejection 206.59 0.00 0.00 0.00 0.00 14850.97
Humidification 1116.11 0.00 0.00 0.00 0.00 415.19
Heat Recovery 173.77 0.00 0.00 0.00 0.00 0.00
Water Systems 26.40 1065.43 0.00 0.00 0.00 4534.60
Refrigeration 118.40 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 21081.58 4651.15 0.00 0.00 0.00 19800.76
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Boiler 0.00 793.75 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
  Other 150.39 0.00 0.00 0.00 0.00 0.00
Cooling General 2978.09 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 3278.44 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 155.12 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5464.40 0.00 0.00 0.00 0.00 0.00
  Cooking 1395.99 2791.97 0.00 0.00 0.00 0.00
  ReachInFreezer 17.50 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 14.82 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 70.73 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 2499.45 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 7.91 0.00 0.00 0.00 0.00 0.00
Fans General 2979.62 0.00 0.00 0.00 0.00 0.00
Pumps General 427.85 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 206.59 0.00 0.00 0.00 0.00 0.00
  Other 0.00 0.00 0.00 0.00 0.00 14850.97
Humidification General 1116.11 0.00 0.00 0.00 0.00 415.19
Heat Recovery General 173.77 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 26.40 1065.43 0.00 0.00 0.00 1898.78
  WaterUse 0.00 0.00 0.00 0.00 0.00 2635.82
Refrigeration General 19.94 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 37.86 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 60.59 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 153.04 0.00 0.00 0.00 0.00 0.00
HVAC 351.44 82.87 0.00 0.00 0.00 0.88
Other 435.14 124.44 0.00 0.00 0.00 0.00
Total 939.62 207.31 0.00 0.00 0.00 0.88


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 153.04 0.00 0.00 0.00 0.00 0.00
HVAC 351.44 82.87 0.00 0.00 0.00 0.88
Other 435.14 124.44 0.00 0.00 0.00 0.00
Total 939.62 207.31 0.00 0.00 0.00 0.88


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 21081.578 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 21081.578 100.00
     
Total On-Site and Utility Electric Sources 21081.578 100.00
Total Electricity End Uses 21081.578 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 2368.93 74.06
Air to Air Heat Recovery for Cooling 749.65 23.44
Air to Air Heat Recovery for Heating 80.06 2.50
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 3198.64 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 19800.76 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 19800.76 100.00
Total Water End Uses 19800.76 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 728.67
Time Not Comfortable Based on Simple ASHRAE 55-2004 4224.83


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Meter |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Meter |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

| Meter |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Meter |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOSPITAL

| Meter |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Meter |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Meter |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B

| Meter |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON

| Meter |

ZoneCoolingSummaryMonthly

| BASEMENT | ER_EXAM1_MULT4_FLR_1 | ER_TRAUMA1_FLR_1 | ER_EXAM3_MULT4_FLR_1 | ER_TRAUMA2_FLR_1 | ER_TRIAGE_MULT4_FLR_1 | OFFICE1_MULT4_FLR_1 | LOBBY_RECORDS_FLR_1 | CORRIDOR_FLR_1 | ER_NURSESTN_LOBBY_FLR_1 | OR1_FLR_2 | OR2_MULT5_FLR_2 | OR3_FLR_2 | OR4_FLR_2 | IC_PATROOM1_MULT5_FLR_2 | IC_PATROOM2_FLR_2 | IC_PATROOM3_MULT6_FLR_2 | ICU_FLR_2 | ICU_NURSESTN_LOBBY_FLR_2 | CORRIDOR_FLR_2 | OR_NURSESTN_LOBBY_FLR_2 | PATROOM1_MULT10_FLR_3 | PATROOM2_FLR_3 | PATROOM3_MULT10_FLR_3 | PATROOM4_FLR_3 | PATROOM5_MULT10_FLR_3 | PHYSTHERAPY_FLR_3 | PATROOM6_FLR_3 | PATROOM7_MULT10_FLR_3 | PATROOM8_FLR_3 | NURSESTN_LOBBY_FLR_3 | LAB_FLR_3 | CORRIDOR_SE_FLR_3 | CORRIDOR_NW_FLR_3 | PATROOM1_MULT10_FLR_4 | PATROOM2_FLR_4 | PATROOM3_MULT10_FLR_4 | PATROOM4_FLR_4 | PATROOM5_MULT10_FLR_4 | RADIOLOGY_FLR_4 | PATROOM6_FLR_4 | PATROOM7_MULT10_FLR_4 | PATROOM8_FLR_4 | NURSESTN_LOBBY_FLR_4 | LAB_FLR_4 | CORRIDOR_SE_FLR_4 | CORRIDOR_NW_FLR_4 | DINING_FLR_5 | NURSESTN_LOBBY_FLR_5 | KITCHEN_FLR_5 | OFFICE1_FLR_5 | OFFICE2_MULT5_FLR_5 | OFFICE3_FLR_5 | OFFICE4_MULT6_FLR_5 | CORRIDOR_FLR_5 |

ZoneHeatingSummaryMonthly

| BASEMENT | ER_EXAM1_MULT4_FLR_1 | ER_TRAUMA1_FLR_1 | ER_EXAM3_MULT4_FLR_1 | ER_TRAUMA2_FLR_1 | ER_TRIAGE_MULT4_FLR_1 | OFFICE1_MULT4_FLR_1 | LOBBY_RECORDS_FLR_1 | CORRIDOR_FLR_1 | ER_NURSESTN_LOBBY_FLR_1 | OR1_FLR_2 | OR2_MULT5_FLR_2 | OR3_FLR_2 | OR4_FLR_2 | IC_PATROOM1_MULT5_FLR_2 | IC_PATROOM2_FLR_2 | IC_PATROOM3_MULT6_FLR_2 | ICU_FLR_2 | ICU_NURSESTN_LOBBY_FLR_2 | CORRIDOR_FLR_2 | OR_NURSESTN_LOBBY_FLR_2 | PATROOM1_MULT10_FLR_3 | PATROOM2_FLR_3 | PATROOM3_MULT10_FLR_3 | PATROOM4_FLR_3 | PATROOM5_MULT10_FLR_3 | PHYSTHERAPY_FLR_3 | PATROOM6_FLR_3 | PATROOM7_MULT10_FLR_3 | PATROOM8_FLR_3 | NURSESTN_LOBBY_FLR_3 | LAB_FLR_3 | CORRIDOR_SE_FLR_3 | CORRIDOR_NW_FLR_3 | PATROOM1_MULT10_FLR_4 | PATROOM2_FLR_4 | PATROOM3_MULT10_FLR_4 | PATROOM4_FLR_4 | PATROOM5_MULT10_FLR_4 | RADIOLOGY_FLR_4 | PATROOM6_FLR_4 | PATROOM7_MULT10_FLR_4 | PATROOM8_FLR_4 | NURSESTN_LOBBY_FLR_4 | LAB_FLR_4 | CORRIDOR_SE_FLR_4 | CORRIDOR_NW_FLR_4 | DINING_FLR_5 | NURSESTN_LOBBY_FLR_5 | KITCHEN_FLR_5 | OFFICE1_FLR_5 | OFFICE2_MULT5_FLR_5 | OFFICE3_FLR_5 | OFFICE4_MULT6_FLR_5 | CORRIDOR_FLR_5 |

ZoneElectricSummaryMonthly

| BASEMENT | ER_EXAM1_MULT4_FLR_1 | ER_TRAUMA1_FLR_1 | ER_EXAM3_MULT4_FLR_1 | ER_TRAUMA2_FLR_1 | ER_TRIAGE_MULT4_FLR_1 | OFFICE1_MULT4_FLR_1 | LOBBY_RECORDS_FLR_1 | CORRIDOR_FLR_1 | ER_NURSESTN_LOBBY_FLR_1 | OR1_FLR_2 | OR2_MULT5_FLR_2 | OR3_FLR_2 | OR4_FLR_2 | IC_PATROOM1_MULT5_FLR_2 | IC_PATROOM2_FLR_2 | IC_PATROOM3_MULT6_FLR_2 | ICU_FLR_2 | ICU_NURSESTN_LOBBY_FLR_2 | CORRIDOR_FLR_2 | OR_NURSESTN_LOBBY_FLR_2 | PATROOM1_MULT10_FLR_3 | PATROOM2_FLR_3 | PATROOM3_MULT10_FLR_3 | PATROOM4_FLR_3 | PATROOM5_MULT10_FLR_3 | PHYSTHERAPY_FLR_3 | PATROOM6_FLR_3 | PATROOM7_MULT10_FLR_3 | PATROOM8_FLR_3 | NURSESTN_LOBBY_FLR_3 | LAB_FLR_3 | CORRIDOR_SE_FLR_3 | CORRIDOR_NW_FLR_3 | PATROOM1_MULT10_FLR_4 | PATROOM2_FLR_4 | PATROOM3_MULT10_FLR_4 | PATROOM4_FLR_4 | PATROOM5_MULT10_FLR_4 | RADIOLOGY_FLR_4 | PATROOM6_FLR_4 | PATROOM7_MULT10_FLR_4 | PATROOM8_FLR_4 | NURSESTN_LOBBY_FLR_4 | LAB_FLR_4 | CORRIDOR_SE_FLR_4 | CORRIDOR_NW_FLR_4 | DINING_FLR_5 | NURSESTN_LOBBY_FLR_5 | KITCHEN_FLR_5 | OFFICE1_FLR_5 | OFFICE2_MULT5_FLR_5 | OFFICE3_FLR_5 | OFFICE4_MULT6_FLR_5 | CORRIDOR_FLR_5 |

SpaceGainsMonthly

| BASEMENT | ER_EXAM1_MULT4_FLR_1 | ER_TRAUMA1_FLR_1 | ER_EXAM3_MULT4_FLR_1 | ER_TRAUMA2_FLR_1 | ER_TRIAGE_MULT4_FLR_1 | OFFICE1_MULT4_FLR_1 | LOBBY_RECORDS_FLR_1 | CORRIDOR_FLR_1 | ER_NURSESTN_LOBBY_FLR_1 | OR1_FLR_2 | OR2_MULT5_FLR_2 | OR3_FLR_2 | OR4_FLR_2 | IC_PATROOM1_MULT5_FLR_2 | IC_PATROOM2_FLR_2 | IC_PATROOM3_MULT6_FLR_2 | ICU_FLR_2 | ICU_NURSESTN_LOBBY_FLR_2 | CORRIDOR_FLR_2 | OR_NURSESTN_LOBBY_FLR_2 | PATROOM1_MULT10_FLR_3 | PATROOM2_FLR_3 | PATROOM3_MULT10_FLR_3 | PATROOM4_FLR_3 | PATROOM5_MULT10_FLR_3 | PHYSTHERAPY_FLR_3 | PATROOM6_FLR_3 | PATROOM7_MULT10_FLR_3 | PATROOM8_FLR_3 | NURSESTN_LOBBY_FLR_3 | LAB_FLR_3 | CORRIDOR_SE_FLR_3 | CORRIDOR_NW_FLR_3 | PATROOM1_MULT10_FLR_4 | PATROOM2_FLR_4 | PATROOM3_MULT10_FLR_4 | PATROOM4_FLR_4 | PATROOM5_MULT10_FLR_4 | RADIOLOGY_FLR_4 | PATROOM6_FLR_4 | PATROOM7_MULT10_FLR_4 | PATROOM8_FLR_4 | NURSESTN_LOBBY_FLR_4 | LAB_FLR_4 | CORRIDOR_SE_FLR_4 | CORRIDOR_NW_FLR_4 | DINING_FLR_5 | NURSESTN_LOBBY_FLR_5 | KITCHEN_FLR_5 | OFFICE1_FLR_5 | OFFICE2_MULT5_FLR_5 | OFFICE3_FLR_5 | OFFICE4_MULT6_FLR_5 | CORRIDOR_FLR_5 |

PeakSpaceGainsMonthly

| BASEMENT | ER_EXAM1_MULT4_FLR_1 | ER_TRAUMA1_FLR_1 | ER_EXAM3_MULT4_FLR_1 | ER_TRAUMA2_FLR_1 | ER_TRIAGE_MULT4_FLR_1 | OFFICE1_MULT4_FLR_1 | LOBBY_RECORDS_FLR_1 | CORRIDOR_FLR_1 | ER_NURSESTN_LOBBY_FLR_1 | OR1_FLR_2 | OR2_MULT5_FLR_2 | OR3_FLR_2 | OR4_FLR_2 | IC_PATROOM1_MULT5_FLR_2 | IC_PATROOM2_FLR_2 | IC_PATROOM3_MULT6_FLR_2 | ICU_FLR_2 | ICU_NURSESTN_LOBBY_FLR_2 | CORRIDOR_FLR_2 | OR_NURSESTN_LOBBY_FLR_2 | PATROOM1_MULT10_FLR_3 | PATROOM2_FLR_3 | PATROOM3_MULT10_FLR_3 | PATROOM4_FLR_3 | PATROOM5_MULT10_FLR_3 | PHYSTHERAPY_FLR_3 | PATROOM6_FLR_3 | PATROOM7_MULT10_FLR_3 | PATROOM8_FLR_3 | NURSESTN_LOBBY_FLR_3 | LAB_FLR_3 | CORRIDOR_SE_FLR_3 | CORRIDOR_NW_FLR_3 | PATROOM1_MULT10_FLR_4 | PATROOM2_FLR_4 | PATROOM3_MULT10_FLR_4 | PATROOM4_FLR_4 | PATROOM5_MULT10_FLR_4 | RADIOLOGY_FLR_4 | PATROOM6_FLR_4 | PATROOM7_MULT10_FLR_4 | PATROOM8_FLR_4 | NURSESTN_LOBBY_FLR_4 | LAB_FLR_4 | CORRIDOR_SE_FLR_4 | CORRIDOR_NW_FLR_4 | DINING_FLR_5 | NURSESTN_LOBBY_FLR_5 | KITCHEN_FLR_5 | OFFICE1_FLR_5 | OFFICE2_MULT5_FLR_5 | OFFICE3_FLR_5 | OFFICE4_MULT6_FLR_5 | CORRIDOR_FLR_5 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | ER_EXAM1_MULT4_FLR_1 | ER_TRAUMA1_FLR_1 | ER_EXAM3_MULT4_FLR_1 | ER_TRAUMA2_FLR_1 | ER_TRIAGE_MULT4_FLR_1 | OFFICE1_MULT4_FLR_1 | LOBBY_RECORDS_FLR_1 | CORRIDOR_FLR_1 | ER_NURSESTN_LOBBY_FLR_1 | OR1_FLR_2 | OR2_MULT5_FLR_2 | OR3_FLR_2 | OR4_FLR_2 | IC_PATROOM1_MULT5_FLR_2 | IC_PATROOM2_FLR_2 | IC_PATROOM3_MULT6_FLR_2 | ICU_FLR_2 | ICU_NURSESTN_LOBBY_FLR_2 | CORRIDOR_FLR_2 | OR_NURSESTN_LOBBY_FLR_2 | PATROOM1_MULT10_FLR_3 | PATROOM2_FLR_3 | PATROOM3_MULT10_FLR_3 | PATROOM4_FLR_3 | PATROOM5_MULT10_FLR_3 | PHYSTHERAPY_FLR_3 | PATROOM6_FLR_3 | PATROOM7_MULT10_FLR_3 | PATROOM8_FLR_3 | NURSESTN_LOBBY_FLR_3 | LAB_FLR_3 | CORRIDOR_SE_FLR_3 | CORRIDOR_NW_FLR_3 | PATROOM1_MULT10_FLR_4 | PATROOM2_FLR_4 | PATROOM3_MULT10_FLR_4 | PATROOM4_FLR_4 | PATROOM5_MULT10_FLR_4 | RADIOLOGY_FLR_4 | PATROOM6_FLR_4 | PATROOM7_MULT10_FLR_4 | PATROOM8_FLR_4 | NURSESTN_LOBBY_FLR_4 | LAB_FLR_4 | CORRIDOR_SE_FLR_4 | CORRIDOR_NW_FLR_4 | DINING_FLR_5 | NURSESTN_LOBBY_FLR_5 | KITCHEN_FLR_5 | OFFICE1_FLR_5 | OFFICE2_MULT5_FLR_5 | OFFICE3_FLR_5 | OFFICE4_MULT6_FLR_5 | CORRIDOR_FLR_5 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | ER_EXAM1_MULT4_FLR_1 | ER_TRAUMA1_FLR_1 | ER_EXAM3_MULT4_FLR_1 | ER_TRAUMA2_FLR_1 | ER_TRIAGE_MULT4_FLR_1 | OFFICE1_MULT4_FLR_1 | LOBBY_RECORDS_FLR_1 | CORRIDOR_FLR_1 | ER_NURSESTN_LOBBY_FLR_1 | OR1_FLR_2 | OR2_MULT5_FLR_2 | OR3_FLR_2 | OR4_FLR_2 | IC_PATROOM1_MULT5_FLR_2 | IC_PATROOM2_FLR_2 | IC_PATROOM3_MULT6_FLR_2 | ICU_FLR_2 | ICU_NURSESTN_LOBBY_FLR_2 | CORRIDOR_FLR_2 | OR_NURSESTN_LOBBY_FLR_2 | PATROOM1_MULT10_FLR_3 | PATROOM2_FLR_3 | PATROOM3_MULT10_FLR_3 | PATROOM4_FLR_3 | PATROOM5_MULT10_FLR_3 | PHYSTHERAPY_FLR_3 | PATROOM6_FLR_3 | PATROOM7_MULT10_FLR_3 | PATROOM8_FLR_3 | NURSESTN_LOBBY_FLR_3 | LAB_FLR_3 | CORRIDOR_SE_FLR_3 | CORRIDOR_NW_FLR_3 | PATROOM1_MULT10_FLR_4 | PATROOM2_FLR_4 | PATROOM3_MULT10_FLR_4 | PATROOM4_FLR_4 | PATROOM5_MULT10_FLR_4 | RADIOLOGY_FLR_4 | PATROOM6_FLR_4 | PATROOM7_MULT10_FLR_4 | PATROOM8_FLR_4 | NURSESTN_LOBBY_FLR_4 | LAB_FLR_4 | CORRIDOR_SE_FLR_4 | CORRIDOR_NW_FLR_4 | DINING_FLR_5 | NURSESTN_LOBBY_FLR_5 | KITCHEN_FLR_5 | OFFICE1_FLR_5 | OFFICE2_MULT5_FLR_5 | OFFICE3_FLR_5 | OFFICE4_MULT6_FLR_5 | CORRIDOR_FLR_5 |

ComfortReportSimple55Monthly

| BASEMENT | ER_EXAM1_MULT4_FLR_1 | ER_TRAUMA1_FLR_1 | ER_EXAM3_MULT4_FLR_1 | ER_TRAUMA2_FLR_1 | ER_TRIAGE_MULT4_FLR_1 | OFFICE1_MULT4_FLR_1 | LOBBY_RECORDS_FLR_1 | CORRIDOR_FLR_1 | ER_NURSESTN_LOBBY_FLR_1 | OR1_FLR_2 | OR2_MULT5_FLR_2 | OR3_FLR_2 | OR4_FLR_2 | IC_PATROOM1_MULT5_FLR_2 | IC_PATROOM2_FLR_2 | IC_PATROOM3_MULT6_FLR_2 | ICU_FLR_2 | ICU_NURSESTN_LOBBY_FLR_2 | CORRIDOR_FLR_2 | OR_NURSESTN_LOBBY_FLR_2 | PATROOM1_MULT10_FLR_3 | PATROOM2_FLR_3 | PATROOM3_MULT10_FLR_3 | PATROOM4_FLR_3 | PATROOM5_MULT10_FLR_3 | PHYSTHERAPY_FLR_3 | PATROOM6_FLR_3 | PATROOM7_MULT10_FLR_3 | PATROOM8_FLR_3 | NURSESTN_LOBBY_FLR_3 | LAB_FLR_3 | CORRIDOR_SE_FLR_3 | CORRIDOR_NW_FLR_3 | PATROOM1_MULT10_FLR_4 | PATROOM2_FLR_4 | PATROOM3_MULT10_FLR_4 | PATROOM4_FLR_4 | PATROOM5_MULT10_FLR_4 | RADIOLOGY_FLR_4 | PATROOM6_FLR_4 | PATROOM7_MULT10_FLR_4 | PATROOM8_FLR_4 | NURSESTN_LOBBY_FLR_4 | LAB_FLR_4 | CORRIDOR_SE_FLR_4 | CORRIDOR_NW_FLR_4 | DINING_FLR_5 | NURSESTN_LOBBY_FLR_5 | KITCHEN_FLR_5 | OFFICE1_FLR_5 | OFFICE2_MULT5_FLR_5 | OFFICE3_FLR_5 | OFFICE4_MULT6_FLR_5 | CORRIDOR_FLR_5 |

OccupantComfortDataSummaryMonthly

| BASEMENT | ER_EXAM1_MULT4_FLR_1 | ER_TRAUMA1_FLR_1 | ER_EXAM3_MULT4_FLR_1 | ER_TRAUMA2_FLR_1 | ER_TRIAGE_MULT4_FLR_1 | OFFICE1_MULT4_FLR_1 | LOBBY_RECORDS_FLR_1 | CORRIDOR_FLR_1 | ER_NURSESTN_LOBBY_FLR_1 | OR1_FLR_2 | OR2_MULT5_FLR_2 | OR3_FLR_2 | OR4_FLR_2 | IC_PATROOM1_MULT5_FLR_2 | IC_PATROOM2_FLR_2 | IC_PATROOM3_MULT6_FLR_2 | ICU_FLR_2 | ICU_NURSESTN_LOBBY_FLR_2 | CORRIDOR_FLR_2 | OR_NURSESTN_LOBBY_FLR_2 | PATROOM1_MULT10_FLR_3 | PATROOM2_FLR_3 | PATROOM3_MULT10_FLR_3 | PATROOM4_FLR_3 | PATROOM5_MULT10_FLR_3 | PHYSTHERAPY_FLR_3 | PATROOM6_FLR_3 | PATROOM7_MULT10_FLR_3 | PATROOM8_FLR_3 | NURSESTN_LOBBY_FLR_3 | LAB_FLR_3 | CORRIDOR_SE_FLR_3 | CORRIDOR_NW_FLR_3 | PATROOM1_MULT10_FLR_4 | PATROOM2_FLR_4 | PATROOM3_MULT10_FLR_4 | PATROOM4_FLR_4 | PATROOM5_MULT10_FLR_4 | RADIOLOGY_FLR_4 | PATROOM6_FLR_4 | PATROOM7_MULT10_FLR_4 | PATROOM8_FLR_4 | NURSESTN_LOBBY_FLR_4 | LAB_FLR_4 | CORRIDOR_SE_FLR_4 | CORRIDOR_NW_FLR_4 | DINING_FLR_5 | NURSESTN_LOBBY_FLR_5 | KITCHEN_FLR_5 | OFFICE1_FLR_5 | OFFICE2_MULT5_FLR_5 | OFFICE3_FLR_5 | OFFICE4_MULT6_FLR_5 | CORRIDOR_FLR_5 |

ChillerReportMonthly

| HEAT RECOVERY CHILLER | COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV_1_COOLC | VAV_ER_COOLC | VAV_OR_COOLC | VAV_ICU_COOLC | VAV_PATRMS_COOLC | VAV_2_COOLC | VAV_LABS_COOLC | CAV_KITCHEN_COOLC |

WindowReportMonthly

| OFFICE1_MULT4_FLR_1_WALL_SOUTH_WINDOW | LOBBY_RECORDS_FLR_1_WALL_2_WEST | ER_NURSESTN_LOBBY_FLR_1_WALL_1_EAST_WINDOW | IC_PATROOM1_MULT5_FLR_2_WALL_NORTH_WINDOW | IC_PATROOM2_FLR_2_WALL_NORTH_WINDOW | IC_PATROOM2_FLR_2_WALL_WEST_WINDOW | IC_PATROOM3_MULT6_FLR_2_WALL_WEST_WINDOW | ICU_FLR_2_WALL_WEST_WINDOW | OR_NURSESTN_LOBBY_FLR_2_WALL_SOUTH_WINDOW | PATROOM1_MULT10_FLR_3_WALL_SOUTH_WINDOW | PATROOM2_FLR_3_WALL_EAST_WINDOW | PATROOM2_FLR_3_WALL_SOUTH_WINDOW | PATROOM3_MULT10_FLR_3_WALL_EAST_WINDOW | PATROOM4_FLR_3_WALL_NORTH_WINDOW | PATROOM4_FLR_3_WALL_EAST_WINDOW | PATROOM5_MULT10_FLR_3_WALL_NORTH_WINDOW | PATROOM6_FLR_3_WALL_SOUTH_WINDOW | PATROOM6_FLR_3_WALL_WEST_WINDOW | PATROOM7_MULT10_FLR_3_WALL_WEST_WINDOW | PATROOM8_FLR_3_WALL_NORTH_WINDOW | PATROOM8_FLR_3_WALL_WEST_WINDOW | PATROOM1_MULT10_FLR_4_WALL_SOUTH_WINDOW | PATROOM2_FLR_4_WALL_EAST_WINDOW | PATROOM2_FLR_4_WALL_SOUTH_WINDOW | PATROOM3_MULT10_FLR_4_WALL_EAST_WINDOW | PATROOM4_FLR_4_WALL_NORTH_WINDOW | PATROOM4_FLR_4_WALL_EAST_WINDOW | PATROOM5_MULT10_FLR_4_WALL_NORTH_WINDOW | PATROOM6_FLR_4_WALL_SOUTH_WINDOW | PATROOM6_FLR_4_WALL_WEST_WINDOW | PATROOM7_MULT10_FLR_4_WALL_WEST_WINDOW | PATROOM8_FLR_4_WALL_NORTH_WINDOW | PATROOM8_FLR_4_WALL_WEST_WINDOW | DINING_FLR_5_WALL_SOUTH_WINDOW | OFFICE1_FLR_5_WALL_SOUTH_WINDOW | OFFICE1_FLR_5_WALL_WEST_WINDOW | OFFICE2_MULT5_FLR_5_WALL_WEST_WINDOW | OFFICE3_FLR_5_WALL_NORTH_WINDOW | OFFICE3_FLR_5_WALL_WEST_WINDOW | OFFICE4_MULT6_FLR_5_WALL_NORTH_WINDOW |

WindowEnergyReportMonthly

| OFFICE1_MULT4_FLR_1_WALL_SOUTH_WINDOW | LOBBY_RECORDS_FLR_1_WALL_2_WEST | ER_NURSESTN_LOBBY_FLR_1_WALL_1_EAST_WINDOW | IC_PATROOM1_MULT5_FLR_2_WALL_NORTH_WINDOW | IC_PATROOM2_FLR_2_WALL_NORTH_WINDOW | IC_PATROOM2_FLR_2_WALL_WEST_WINDOW | IC_PATROOM3_MULT6_FLR_2_WALL_WEST_WINDOW | ICU_FLR_2_WALL_WEST_WINDOW | OR_NURSESTN_LOBBY_FLR_2_WALL_SOUTH_WINDOW | PATROOM1_MULT10_FLR_3_WALL_SOUTH_WINDOW | PATROOM2_FLR_3_WALL_EAST_WINDOW | PATROOM2_FLR_3_WALL_SOUTH_WINDOW | PATROOM3_MULT10_FLR_3_WALL_EAST_WINDOW | PATROOM4_FLR_3_WALL_NORTH_WINDOW | PATROOM4_FLR_3_WALL_EAST_WINDOW | PATROOM5_MULT10_FLR_3_WALL_NORTH_WINDOW | PATROOM6_FLR_3_WALL_SOUTH_WINDOW | PATROOM6_FLR_3_WALL_WEST_WINDOW | PATROOM7_MULT10_FLR_3_WALL_WEST_WINDOW | PATROOM8_FLR_3_WALL_NORTH_WINDOW | PATROOM8_FLR_3_WALL_WEST_WINDOW | PATROOM1_MULT10_FLR_4_WALL_SOUTH_WINDOW | PATROOM2_FLR_4_WALL_EAST_WINDOW | PATROOM2_FLR_4_WALL_SOUTH_WINDOW | PATROOM3_MULT10_FLR_4_WALL_EAST_WINDOW | PATROOM4_FLR_4_WALL_NORTH_WINDOW | PATROOM4_FLR_4_WALL_EAST_WINDOW | PATROOM5_MULT10_FLR_4_WALL_NORTH_WINDOW | PATROOM6_FLR_4_WALL_SOUTH_WINDOW | PATROOM6_FLR_4_WALL_WEST_WINDOW | PATROOM7_MULT10_FLR_4_WALL_WEST_WINDOW | PATROOM8_FLR_4_WALL_NORTH_WINDOW | PATROOM8_FLR_4_WALL_WEST_WINDOW | DINING_FLR_5_WALL_SOUTH_WINDOW | OFFICE1_FLR_5_WALL_SOUTH_WINDOW | OFFICE1_FLR_5_WALL_WEST_WINDOW | OFFICE2_MULT5_FLR_5_WALL_WEST_WINDOW | OFFICE3_FLR_5_WALL_NORTH_WINDOW | OFFICE3_FLR_5_WALL_WEST_WINDOW | OFFICE4_MULT6_FLR_5_WALL_NORTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | ER_EXAM1_MULT4_FLR_1 | ER_TRAUMA1_FLR_1 | ER_EXAM3_MULT4_FLR_1 | ER_TRAUMA2_FLR_1 | ER_TRIAGE_MULT4_FLR_1 | OFFICE1_MULT4_FLR_1 | LOBBY_RECORDS_FLR_1 | CORRIDOR_FLR_1 | ER_NURSESTN_LOBBY_FLR_1 | OR1_FLR_2 | OR2_MULT5_FLR_2 | OR3_FLR_2 | OR4_FLR_2 | IC_PATROOM1_MULT5_FLR_2 | IC_PATROOM2_FLR_2 | IC_PATROOM3_MULT6_FLR_2 | ICU_FLR_2 | ICU_NURSESTN_LOBBY_FLR_2 | CORRIDOR_FLR_2 | OR_NURSESTN_LOBBY_FLR_2 | PATROOM1_MULT10_FLR_3 | PATROOM2_FLR_3 | PATROOM3_MULT10_FLR_3 | PATROOM4_FLR_3 | PATROOM5_MULT10_FLR_3 | PHYSTHERAPY_FLR_3 | PATROOM6_FLR_3 | PATROOM7_MULT10_FLR_3 | PATROOM8_FLR_3 | NURSESTN_LOBBY_FLR_3 | LAB_FLR_3 | CORRIDOR_SE_FLR_3 | CORRIDOR_NW_FLR_3 | PATROOM1_MULT10_FLR_4 | PATROOM2_FLR_4 | PATROOM3_MULT10_FLR_4 | PATROOM4_FLR_4 | PATROOM5_MULT10_FLR_4 | RADIOLOGY_FLR_4 | PATROOM6_FLR_4 | PATROOM7_MULT10_FLR_4 | PATROOM8_FLR_4 | NURSESTN_LOBBY_FLR_4 | LAB_FLR_4 | CORRIDOR_SE_FLR_4 | CORRIDOR_NW_FLR_4 | DINING_FLR_5 | NURSESTN_LOBBY_FLR_5 | KITCHEN_FLR_5 | OFFICE1_FLR_5 | OFFICE2_MULT5_FLR_5 | OFFICE3_FLR_5 | OFFICE4_MULT6_FLR_5 | CORRIDOR_FLR_5 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | ER_EXAM1_MULT4_FLR_1 | ER_TRAUMA1_FLR_1 | ER_EXAM3_MULT4_FLR_1 | ER_TRAUMA2_FLR_1 | ER_TRIAGE_MULT4_FLR_1 | OFFICE1_MULT4_FLR_1 | LOBBY_RECORDS_FLR_1 | CORRIDOR_FLR_1 | ER_NURSESTN_LOBBY_FLR_1 | OR1_FLR_2 | OR2_MULT5_FLR_2 | OR3_FLR_2 | OR4_FLR_2 | IC_PATROOM1_MULT5_FLR_2 | IC_PATROOM2_FLR_2 | IC_PATROOM3_MULT6_FLR_2 | ICU_FLR_2 | ICU_NURSESTN_LOBBY_FLR_2 | CORRIDOR_FLR_2 | OR_NURSESTN_LOBBY_FLR_2 | PATROOM1_MULT10_FLR_3 | PATROOM2_FLR_3 | PATROOM3_MULT10_FLR_3 | PATROOM4_FLR_3 | PATROOM5_MULT10_FLR_3 | PHYSTHERAPY_FLR_3 | PATROOM6_FLR_3 | PATROOM7_MULT10_FLR_3 | PATROOM8_FLR_3 | NURSESTN_LOBBY_FLR_3 | LAB_FLR_3 | CORRIDOR_SE_FLR_3 | CORRIDOR_NW_FLR_3 | PATROOM1_MULT10_FLR_4 | PATROOM2_FLR_4 | PATROOM3_MULT10_FLR_4 | PATROOM4_FLR_4 | PATROOM5_MULT10_FLR_4 | RADIOLOGY_FLR_4 | PATROOM6_FLR_4 | PATROOM7_MULT10_FLR_4 | PATROOM8_FLR_4 | NURSESTN_LOBBY_FLR_4 | LAB_FLR_4 | CORRIDOR_SE_FLR_4 | CORRIDOR_NW_FLR_4 | DINING_FLR_5 | NURSESTN_LOBBY_FLR_5 | KITCHEN_FLR_5 | OFFICE1_FLR_5 | OFFICE2_MULT5_FLR_5 | OFFICE3_FLR_5 | OFFICE4_MULT6_FLR_5 | CORRIDOR_FLR_5 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SHWSYS1 WATER HEATER | SWH DISHWASHING BOOSTER | SWH LAUNDRY | DUMMY WATER HEATER |

DaylightingReportMonthly

| OFFICE1_FLR_5_DAYLCTRL | OFFICE3_FLR_5_DAYLCTRL | LOBBY_RECORDS_FLR_1_DAYLCTRL | OFFICE4_MULT6_FLR_5_DAYLCTRL | OFFICE2_MULT5_FLR_5_DAYLCTRL | DINING_FLR_5_DAYLCTRL |

CoilReportMonthly

| VAV_PATRMS_EXTRAWATERHEATC | VAV_ER_EXTRAWATERHEATC | VAV_OR_EXTRAWATERHEATC | VAV_ICU_EXTRAWATERHEATC | VAV_LABS_EXTRAWATERHEATC | BASEMENT VAV BOX REHEAT COIL | ER_EXAM1_MULT4_FLR_1 VAV BOX REHEAT COIL | ER_TRAUMA1_FLR_1 VAV BOX REHEAT COIL | ER_EXAM3_MULT4_FLR_1 VAV BOX REHEAT COIL | ER_TRAUMA2_FLR_1 VAV BOX REHEAT COIL | ER_TRIAGE_MULT4_FLR_1 VAV BOX REHEAT COIL | OFFICE1_MULT4_FLR_1 VAV BOX REHEAT COIL | LOBBY_RECORDS_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_1 VAV BOX REHEAT COIL | ER_NURSESTN_LOBBY_FLR_1 VAV BOX REHEAT COIL | OR1_FLR_2 VAV BOX REHEAT COIL | OR2_MULT5_FLR_2 VAV BOX REHEAT COIL | OR3_FLR_2 VAV BOX REHEAT COIL | OR4_FLR_2 VAV BOX REHEAT COIL | IC_PATROOM1_MULT5_FLR_2 VAV BOX REHEAT COIL | IC_PATROOM2_FLR_2 VAV BOX REHEAT COIL | IC_PATROOM3_MULT6_FLR_2 VAV BOX REHEAT COIL | ICU_FLR_2 VAV BOX REHEAT COIL | ICU_NURSESTN_LOBBY_FLR_2 VAV BOX REHEAT COIL | CORRIDOR_FLR_2 VAV BOX REHEAT COIL | OR_NURSESTN_LOBBY_FLR_2 VAV BOX REHEAT COIL | PATROOM1_MULT10_FLR_3 VAV BOX REHEAT COIL | PATROOM2_FLR_3 VAV BOX REHEAT COIL | PATROOM3_MULT10_FLR_3 VAV BOX REHEAT COIL | PATROOM4_FLR_3 VAV BOX REHEAT COIL | PATROOM5_MULT10_FLR_3 VAV BOX REHEAT COIL | PHYSTHERAPY_FLR_3 VAV BOX REHEAT COIL | PATROOM6_FLR_3 VAV BOX REHEAT COIL | PATROOM7_MULT10_FLR_3 VAV BOX REHEAT COIL | PATROOM8_FLR_3 VAV BOX REHEAT COIL | NURSESTN_LOBBY_FLR_3 VAV BOX REHEAT COIL | LAB_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_SE_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_NW_FLR_3 VAV BOX REHEAT COIL | PATROOM1_MULT10_FLR_4 VAV BOX REHEAT COIL | PATROOM2_FLR_4 VAV BOX REHEAT COIL | PATROOM3_MULT10_FLR_4 VAV BOX REHEAT COIL | PATROOM4_FLR_4 VAV BOX REHEAT COIL | PATROOM5_MULT10_FLR_4 VAV BOX REHEAT COIL | RADIOLOGY_FLR_4 VAV BOX REHEAT COIL | PATROOM6_FLR_4 VAV BOX REHEAT COIL | PATROOM7_MULT10_FLR_4 VAV BOX REHEAT COIL | PATROOM8_FLR_4 VAV BOX REHEAT COIL | NURSESTN_LOBBY_FLR_4 VAV BOX REHEAT COIL | LAB_FLR_4 VAV BOX REHEAT COIL | CORRIDOR_SE_FLR_4 VAV BOX REHEAT COIL | CORRIDOR_NW_FLR_4 VAV BOX REHEAT COIL | DINING_FLR_5 VAV BOX REHEAT COIL | NURSESTN_LOBBY_FLR_5 VAV BOX REHEAT COIL | OFFICE1_FLR_5 VAV BOX REHEAT COIL | OFFICE2_MULT5_FLR_5 VAV BOX REHEAT COIL | OFFICE3_FLR_5 VAV BOX REHEAT COIL | OFFICE4_MULT6_FLR_5 VAV BOX REHEAT COIL | CORRIDOR_FLR_5 VAV BOX REHEAT COIL | VAV_1_HEATC | VAV_ER_HEATC | VAV_OR_HEATC | VAV_ICU_HEATC | VAV_PATRMS_HEATC | VAV_2_HEATC | VAV_LABS_HEATC | CAV_KITCHEN_HEATC | VAV_PATRMS_EXTRAELECHEATC | VAV_ER_EXTRAELECHEATC | VAV_OR_EXTRAELECHEATC | VAV_ICU_EXTRAELECHEATC | VAV_LABS_EXTRAELECHEATC | VAV_1_COOLC | VAV_ER_COOLC | VAV_OR_COOLC | VAV_ICU_COOLC | VAV_PATRMS_COOLC | VAV_2_COOLC | VAV_LABS_COOLC | CAV_KITCHEN_COOLC |

PlantLoopDemandReportMonthly

| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | HEAT RECOVERY WATER LOOP | HEAT RECOVERY CHILLER BYPASS LOOP | TOWERWATERSYS |

FanReportMonthly

| CAV_KITCHEN_FAN | VAV_1_FAN | VAV_2_FAN | VAV_ER_FAN | VAV_OR_FAN | VAV_ICU_FAN | VAV_PATRMS_FAN | VAV_LABS_FAN | KITCHEN_FLR_5 EXHAUST FAN | DINING_FLR_5 DUMMY EXHAUST FAN | NURSESTN_LOBBY_FLR_5 DUMMY EXHAUST FAN | OFFICE1_FLR_5 DUMMY EXHAUST FAN | OFFICE2_MULT5_FLR_5 DUMMY EXHAUST FAN | OFFICE3_FLR_5 DUMMY EXHAUST FAN | OFFICE4_MULT6_FLR_5 DUMMY EXHAUST FAN | CORRIDOR_FLR_5 DUMMY EXHAUST FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | HEAT RECOVERY CIRC PUMP | HEAT RECOVERY CHILLER BYPASS LOOP PUMP | SHWSYS1 PUMP | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | HEAT RECOVERY WATER LOOP | HEAT RECOVERY CHILLER BYPASS LOOP | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | ER_EXAM1_MULT4_FLR_1 | ER_TRAUMA1_FLR_1 | ER_EXAM3_MULT4_FLR_1 | ER_TRAUMA2_FLR_1 | ER_TRIAGE_MULT4_FLR_1 | OFFICE1_MULT4_FLR_1 | LOBBY_RECORDS_FLR_1 | CORRIDOR_FLR_1 | ER_NURSESTN_LOBBY_FLR_1 | OR1_FLR_2 | OR2_MULT5_FLR_2 | OR3_FLR_2 | OR4_FLR_2 | IC_PATROOM1_MULT5_FLR_2 | IC_PATROOM2_FLR_2 | IC_PATROOM3_MULT6_FLR_2 | ICU_FLR_2 | ICU_NURSESTN_LOBBY_FLR_2 | CORRIDOR_FLR_2 | OR_NURSESTN_LOBBY_FLR_2 | PATROOM1_MULT10_FLR_3 | PATROOM2_FLR_3 | PATROOM3_MULT10_FLR_3 | PATROOM4_FLR_3 | PATROOM5_MULT10_FLR_3 | PHYSTHERAPY_FLR_3 | PATROOM6_FLR_3 | PATROOM7_MULT10_FLR_3 | PATROOM8_FLR_3 | NURSESTN_LOBBY_FLR_3 | LAB_FLR_3 | CORRIDOR_SE_FLR_3 | CORRIDOR_NW_FLR_3 | PATROOM1_MULT10_FLR_4 | PATROOM2_FLR_4 | PATROOM3_MULT10_FLR_4 | PATROOM4_FLR_4 | PATROOM5_MULT10_FLR_4 | RADIOLOGY_FLR_4 | PATROOM6_FLR_4 | PATROOM7_MULT10_FLR_4 | PATROOM8_FLR_4 | NURSESTN_LOBBY_FLR_4 | LAB_FLR_4 | CORRIDOR_SE_FLR_4 | CORRIDOR_NW_FLR_4 | DINING_FLR_5 | NURSESTN_LOBBY_FLR_5 | KITCHEN_FLR_5 | OFFICE1_FLR_5 | OFFICE2_MULT5_FLR_5 | OFFICE3_FLR_5 | OFFICE4_MULT6_FLR_5 | CORRIDOR_FLR_5 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_1 | VAV_ER | VAV_OR | VAV_ICU | VAV_PATRMS | VAV_2 | VAV_LABS | CAV_KITCHEN |

AirLoopSystemComponentLoadsMonthly

| VAV_1 | VAV_ER | VAV_OR | VAV_ICU | VAV_PATRMS | VAV_2 | VAV_LABS | CAV_KITCHEN |

AirLoopSystemComponentEnergyUseMonthly

| VAV_1 | VAV_ER | VAV_OR | VAV_ICU | VAV_PATRMS | VAV_2 | VAV_LABS | CAV_KITCHEN |

MechanicalVentilationLoadsMonthly

| BASEMENT | ER_EXAM1_MULT4_FLR_1 | ER_TRAUMA1_FLR_1 | ER_EXAM3_MULT4_FLR_1 | ER_TRAUMA2_FLR_1 | ER_TRIAGE_MULT4_FLR_1 | OFFICE1_MULT4_FLR_1 | LOBBY_RECORDS_FLR_1 | CORRIDOR_FLR_1 | ER_NURSESTN_LOBBY_FLR_1 | OR1_FLR_2 | OR2_MULT5_FLR_2 | OR3_FLR_2 | OR4_FLR_2 | IC_PATROOM1_MULT5_FLR_2 | IC_PATROOM2_FLR_2 | IC_PATROOM3_MULT6_FLR_2 | ICU_FLR_2 | ICU_NURSESTN_LOBBY_FLR_2 | CORRIDOR_FLR_2 | OR_NURSESTN_LOBBY_FLR_2 | PATROOM1_MULT10_FLR_3 | PATROOM2_FLR_3 | PATROOM3_MULT10_FLR_3 | PATROOM4_FLR_3 | PATROOM5_MULT10_FLR_3 | PHYSTHERAPY_FLR_3 | PATROOM6_FLR_3 | PATROOM7_MULT10_FLR_3 | PATROOM8_FLR_3 | NURSESTN_LOBBY_FLR_3 | LAB_FLR_3 | CORRIDOR_SE_FLR_3 | CORRIDOR_NW_FLR_3 | PATROOM1_MULT10_FLR_4 | PATROOM2_FLR_4 | PATROOM3_MULT10_FLR_4 | PATROOM4_FLR_4 | PATROOM5_MULT10_FLR_4 | RADIOLOGY_FLR_4 | PATROOM6_FLR_4 | PATROOM7_MULT10_FLR_4 | PATROOM8_FLR_4 | NURSESTN_LOBBY_FLR_4 | LAB_FLR_4 | CORRIDOR_SE_FLR_4 | CORRIDOR_NW_FLR_4 | DINING_FLR_5 | NURSESTN_LOBBY_FLR_5 | KITCHEN_FLR_5 | OFFICE1_FLR_5 | OFFICE2_MULT5_FLR_5 | OFFICE3_FLR_5 | OFFICE4_MULT6_FLR_5 | CORRIDOR_FLR_5 |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2020-06-03 20:39:13

General

Value
Program Version and Build EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 20:38
RunPeriod RUNPERIOD 1
Weather File Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Latitude [deg] 32.17
Longitude [deg] -110.9
Elevation [m] 809.00
Time Zone -7.0
North Axis Angle [deg] -90.0
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 5799.60 1196.93 1667.08 1268.48 1667.11
Above Ground Wall Area [m2] 5197.44 1066.84 1496.10 1138.38 1496.12
Window Opening Area [m2] 848.39 144.86 223.69 293.66 186.18
Gross Window-Wall Ratio [%] 14.63 12.10 13.42 23.15 11.17
Above Ground Window-Wall Ratio [%] 16.32 13.58 14.95 25.80 12.44


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 5799.60 1196.93 1667.08 1268.48 1667.11
Above Ground Wall Area [m2] 5197.44 1066.84 1496.10 1138.38 1496.12
Window Opening Area [m2] 848.39 144.86 223.69 293.66 186.18
Gross Window-Wall Ratio [%] 14.63 12.10 13.42 23.15 11.17
Above Ground Window-Wall Ratio [%] 16.32 13.58 14.95 25.80 12.44


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3739.37
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 3739.35 Yes Yes 9120.27 1.00 0.00 602.16 0.00 0.00 6.8889 37.17 8.0700
ER_EXAM1_MULT4_FLR_1 27.87 Yes Yes 118.96 4.00 26.02 0.00 0.00 0.00 15.0695 4.65 16.1400
ER_TRAUMA1_FLR_1 27.87 Yes Yes 118.96 1.00 45.53 0.00 0.00 0.00 15.0695 4.65 43.0400
ER_EXAM3_MULT4_FLR_1 27.87 Yes Yes 118.96 4.00 19.51 0.00 0.00 0.00 15.0695 4.65 16.1400
ER_TRAUMA2_FLR_1 27.87 Yes Yes 118.96 1.00 45.53 0.00 0.00 0.00 15.0695 4.65 43.0400
ER_TRIAGE_MULT4_FLR_1 27.87 Yes Yes 118.96 4.00 26.02 0.00 0.00 0.00 15.0695 4.65 21.5271
OFFICE1_MULT4_FLR_1 13.94 Yes Yes 59.50 5.00 13.01 0.00 2.96 2.96 6.8889 13.27 11.8400
LOBBY_RECORDS_FLR_1 1474.81 Yes Yes 6294.92 1.00 409.78 0.00 62.63 62.63 8.7941 69.70 1.0800
CORRIDOR_FLR_1 569.03 Yes Yes 2428.79 1.00 91.07 0.00 0.00 0.00 7.6424 92.94 0.0000
ER_NURSESTN_LOBBY_FLR_1 1235.61 Yes Yes 5273.95 1.00 110.58 0.00 30.42 30.42 11.1729 69.70 14.6300
OR1_FLR_2 55.74 Yes Yes 237.91 1.00 65.05 0.00 0.00 0.00 24.3264 18.59 43.0400
OR2_MULT5_FLR_2 55.74 Yes Yes 237.91 5.00 26.02 0.00 0.00 0.00 24.3264 18.59 43.0400
OR3_FLR_2 55.74 Yes Yes 237.91 1.00 39.03 0.00 0.00 0.00 24.3264 18.59 43.0400
OR4_FLR_2 222.97 Yes Yes 951.70 1.00 0.00 0.00 0.00 0.00 24.3264 18.59 43.0400
IC_PATROOM1_MULT5_FLR_2 20.90 Yes Yes 89.21 5.00 19.51 0.00 4.91 4.91 13.4549 18.59 32.2800
IC_PATROOM2_FLR_2 27.87 Yes Yes 118.96 1.00 45.53 0.00 11.44 11.44 13.4549 18.59 32.2800
IC_PATROOM3_MULT6_FLR_2 20.90 Yes Yes 89.21 6.00 19.51 0.00 4.91 4.91 13.4549 18.59 32.2800
ICU_FLR_2 617.96 Yes Yes 2637.63 1.00 214.68 0.00 25.03 25.03 13.4549 18.59 32.2800
ICU_NURSESTN_LOBBY_FLR_2 668.77 Yes Yes 2854.51 1.00 0.00 0.00 0.00 0.00 12.5938 69.70 21.5200
CORRIDOR_FLR_2 569.03 Yes Yes 2428.79 1.00 91.07 0.00 0.00 0.00 7.6424 92.94 0.0000
OR_NURSESTN_LOBBY_FLR_2 1012.64 Yes Yes 4322.24 1.00 182.14 0.00 35.76 35.76 10.4625 69.70 11.1900
PATROOM1_MULT10_FLR_3 20.90 Yes Yes 89.21 10.00 19.51 0.00 4.91 4.91 7.3195 18.59 21.5200
PATROOM2_FLR_3 34.84 Yes Yes 148.71 1.00 52.04 0.00 13.08 13.08 7.3195 18.59 21.5200
PATROOM3_MULT10_FLR_3 20.21 Yes Yes 86.26 10.00 18.87 0.00 4.74 4.74 7.3195 18.59 21.5200
PATROOM4_FLR_3 34.84 Yes Yes 148.71 1.00 52.04 0.00 13.08 13.08 7.3195 18.59 21.5200
PATROOM5_MULT10_FLR_3 20.90 Yes Yes 89.21 10.00 19.51 0.00 4.91 4.91 7.3195 18.59 21.5200
PHYSTHERAPY_FLR_3 487.74 Yes Yes 2081.82 1.00 0.00 0.00 0.00 0.00 9.7952 18.59 16.1400
PATROOM6_FLR_3 27.87 Yes Yes 118.96 1.00 45.53 0.00 11.44 11.44 7.3195 18.59 21.5200
PATROOM7_MULT10_FLR_3 20.21 Yes Yes 86.26 10.00 18.87 0.00 4.74 4.74 7.3195 18.59 21.5200
PATROOM8_FLR_3 27.87 Yes Yes 118.96 1.00 45.53 0.00 11.44 11.44 7.3195 18.59 21.5200
NURSESTN_LOBBY_FLR_3 905.80 Yes Yes 3866.25 1.00 0.00 0.00 0.00 0.00 10.4625 69.70 11.1900
LAB_FLR_3 264.77 Yes Yes 1129.43 1.00 0.00 0.00 0.00 0.00 14.3160 18.59 43.0400
CORRIDOR_SE_FLR_3 566.71 Yes Yes 2418.88 1.00 45.53 0.00 0.00 0.00 7.6424 92.94 0.0000
CORRIDOR_NW_FLR_3 566.71 Yes Yes 2418.88 1.00 45.53 0.00 0.00 0.00 7.6424 92.94 0.0000
PATROOM1_MULT10_FLR_4 20.90 Yes Yes 89.21 10.00 19.51 0.00 4.91 4.91 7.3195 18.59 21.5200
PATROOM2_FLR_4 34.84 Yes Yes 148.71 1.00 52.04 0.00 13.08 13.08 7.3195 18.59 21.5200
PATROOM3_MULT10_FLR_4 20.21 Yes Yes 86.26 10.00 18.87 0.00 4.74 4.74 7.3195 18.59 21.5200
PATROOM4_FLR_4 34.84 Yes Yes 148.71 1.00 52.04 0.00 13.08 13.08 7.3195 18.59 21.5200
PATROOM5_MULT10_FLR_4 20.90 Yes Yes 89.21 10.00 19.51 0.00 4.91 4.91 7.3195 18.59 21.5200
RADIOLOGY_FLR_4 487.74 Yes Yes 2081.82 1.00 0.00 0.00 0.00 0.00 10.1181 18.59 107.6389
PATROOM6_FLR_4 27.87 Yes Yes 118.96 1.00 45.53 0.00 11.44 11.44 7.3195 18.59 21.5200
PATROOM7_MULT10_FLR_4 20.21 Yes Yes 86.26 10.00 18.87 0.00 4.74 4.74 7.3195 18.59 21.5200
PATROOM8_FLR_4 27.87 Yes Yes 118.96 1.00 45.53 0.00 11.44 11.44 7.3195 18.59 21.5200
NURSESTN_LOBBY_FLR_4 905.80 Yes Yes 3866.22 1.00 0.00 0.00 0.00 0.00 10.4625 69.70 11.1900
LAB_FLR_4 264.77 Yes Yes 1129.43 1.00 0.00 0.00 0.00 0.00 14.3160 18.59 43.0400
CORRIDOR_SE_FLR_4 566.71 Yes Yes 2418.88 1.00 45.53 0.00 0.00 0.00 7.6424 92.94 0.0000
CORRIDOR_NW_FLR_4 566.71 Yes Yes 2418.88 1.00 45.53 0.00 0.00 0.00 7.6424 92.94 0.0000
DINING_FLR_5 696.77 Yes Yes 2974.04 1.00 227.67 0.00 35.76 35.76 4.3056 9.29 10.7600
NURSESTN_LOBBY_FLR_5 1040.51 Yes Yes 4441.23 1.00 104.08 0.00 0.00 0.00 10.4625 69.70 11.1900
KITCHEN_FLR_5 929.03 Yes Yes 3965.37 1.00 260.20 0.00 0.00 0.00 11.7327 18.59 243.2033
OFFICE1_FLR_5 69.70 Yes Yes 297.50 1.00 71.56 0.00 17.98 17.98 6.8889 13.28 10.7600
OFFICE2_MULT5_FLR_5 69.68 Yes Yes 297.41 5.00 32.52 0.00 8.17 8.17 6.8889 13.28 10.7600
OFFICE3_FLR_5 69.68 Yes Yes 297.41 1.00 71.55 0.00 17.98 17.98 6.8889 13.28 10.7600
OFFICE4_MULT6_FLR_5 13.94 Yes Yes 59.50 6.00 13.01 0.00 2.96 2.96 6.8889 13.27 10.7600
CORRIDOR_FLR_5 501.68 Yes Yes 2141.32 1.00 78.06 0.00 0.00 0.00 7.6424 92.94 0.0000
Total 22436.18     88922.27   5197.44 602.16 848.39 848.39 9.5074 29.26 23.8413
Conditioned Total 22436.18     88922.27   5197.44 602.16 848.39 848.39 9.5074 29.26 23.8413
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2020-06-03 20:39:13

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 18-MAY-14:20 07-DEC-06:10 - - - 16-JUN-12:00
Heating 11481.85 291175.26 0.00 0.00 0.00 0.00
Cooling 216157.55 0.00 0.00 0.00 0.00 0.00
Interior Lighting 179377.56 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 342825.45 59978.20 0.00 0.00 0.00 0.00
Exterior Equipment 167583.53 0.00 0.00 0.00 0.00 0.00
Fans 133854.31 0.00 0.00 0.00 0.00 0.00
Pumps 26858.57 0.00 0.00 0.00 0.00 0.00
Heat Rejection 22654.27 0.00 0.00 0.00 0.00 0.00
Humidification 102785.38 0.00 0.00 0.00 0.00 0.00
Heat Recovery 7966.87 0.00 0.00 0.00 0.00 0.00
Water Systems 2250.53 17147.66 0.00 0.00 0.00 0.00
Refrigeration 4411.83 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1218207.71 368301.12 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating Boiler 0.00 291175.26 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 216157.55 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 179377.56 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 274324.97 0.00 0.00 0.00 0.00 0.00
  Cooking 67475.48 59978.20 0.00 0.00 0.00 0.00
  ReachInFreezer 555.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 470.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 4119.89 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 162962.64 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 501.00 0.00 0.00 0.00 0.00 0.00
Fans General 133854.31 0.00 0.00 0.00 0.00 0.00
Pumps General 26858.57 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 22654.27 0.00 0.00 0.00 0.00 0.00
Humidification General 102785.38 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 7966.87 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 2250.53 17147.66 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 724.15 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 1664.78 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 2022.90 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2020-06-03 20:39:13

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 476.27 860.43 0.00 0.00 0.00
Cooling 9431.61 0.00 0.00 0.00 0.00
Interior Lighting 10382.81 0.00 0.00 0.00 0.00
Exterior Lighting 491.28 0.00 0.00 0.00 0.00
Interior Equipment 21829.22 3026.50 0.00 0.00 0.00
Exterior Equipment 8164.82 0.00 0.00 0.00 0.00
Fans 9436.46 0.00 0.00 0.00 0.00
Pumps 1355.00 0.00 0.00 0.00 0.00
Heat Rejection 654.28 0.00 0.00 0.00 0.00
Humidification 3534.72 0.00 0.00 0.00 0.00
Heat Recovery 550.32 0.00 0.00 0.00 0.00
Water Systems 83.61 1154.92 0.00 0.00 0.00
Refrigeration 374.96 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 66765.36 5041.85 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 21.23 38.35 0.00 0.00 0.00
Cooling 420.38 0.00 0.00 0.00 0.00
Interior Lighting 462.77 0.00 0.00 0.00 0.00
Exterior Lighting 21.90 0.00 0.00 0.00 0.00
Interior Equipment 972.95 134.89 0.00 0.00 0.00
Exterior Equipment 363.91 0.00 0.00 0.00 0.00
Fans 420.59 0.00 0.00 0.00 0.00
Pumps 60.39 0.00 0.00 0.00 0.00
Heat Rejection 29.16 0.00 0.00 0.00 0.00
Humidification 157.55 0.00 0.00 0.00 0.00
Heat Recovery 24.53 0.00 0.00 0.00 0.00
Water Systems 3.73 51.48 0.00 0.00 0.00
Refrigeration 16.71 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 2975.79 224.72 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 21.23 38.35 0.00 0.00 0.00
Cooling 420.38 0.00 0.00 0.00 0.00
Interior Lighting 462.77 0.00 0.00 0.00 0.00
Exterior Lighting 21.90 0.00 0.00 0.00 0.00
Interior Equipment 972.95 134.89 0.00 0.00 0.00
Exterior Equipment 363.91 0.00 0.00 0.00 0.00
Fans 420.59 0.00 0.00 0.00 0.00
Pumps 60.39 0.00 0.00 0.00 0.00
Heat Rejection 29.16 0.00 0.00 0.00 0.00
Humidification 157.55 0.00 0.00 0.00 0.00
Heat Recovery 24.53 0.00 0.00 0.00 0.00
Water Systems 3.73 51.48 0.00 0.00 0.00
Refrigeration 16.71 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 2975.79 224.72 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2020-06-03 20:39:13

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 5.14 0.554123 0.402000 2.07 1.00 0.500000 0.000688 0.000331 2.07 12.80 0.008000
ER_EXAM1_MULT4_FLR_1 VAV BOX COMPONENT 1.59 1.00 1.00 1.59 1.00 0.500000 0.007111 0.000288 1.59 12.80 0.008000
ER_TRAUMA1_FLR_1 VAV BOX COMPONENT 0.396383 1.00 1.00 0.396383 1.00 0.500000 0.007111 0.000078 0.396383 12.80 0.008000
ER_EXAM3_MULT4_FLR_1 VAV BOX COMPONENT 1.59 1.00 1.00 1.59 1.00 0.500000 0.007111 0.000280 1.59 12.80 0.008000
ER_TRAUMA2_FLR_1 VAV BOX COMPONENT 0.396383 1.00 1.00 0.396383 1.00 0.500000 0.007111 0.000078 0.396383 12.80 0.008000
ER_TRIAGE_MULT4_FLR_1 VAV BOX COMPONENT 1.59 1.00 1.00 1.59 1.00 0.500000 0.007111 0.000288 1.59 12.80 0.008000
OFFICE1_MULT4_FLR_1 VAV BOX COMPONENT 0.320019 0.165909 0.158000 0.050563 1.00 0.500000 0.002296 0.000039 0.074193 12.80 0.008000
LOBBY_RECORDS_FLR_1 VAV BOX COMPONENT 1.75 0.642282 0.428000 0.748874 1.00 0.500000 0.000593 0.000281 0.748874 12.80 0.008000
CORRIDOR_FLR_1 VAV BOX COMPONENT 0.521243 0.831861 0.499000 0.260100 1.00 0.500000 0.000458 0.000075 0.260100 12.80 0.008000
ER_NURSESTN_LOBBY_FLR_1 VAV BOX COMPONENT 2.81 0.334909 0.223000 0.626923 0.893091 0.500000 0.001138 0.000151 0.626923 12.80 0.008000
OR1_FLR_2 VAV BOX COMPONENT 0.990917       0.600000 0.500000 0.008888 0.000115 0.594550 12.80 0.008000
OR2_MULT5_FLR_2 VAV BOX COMPONENT 4.95       0.600000 0.500000 0.008888 0.000517 2.97 12.80 0.008000
OR3_FLR_2 VAV BOX COMPONENT 0.990917       0.600000 0.500000 0.008888 0.000107 0.594550 12.80 0.008000
OR4_FLR_2 VAV BOX COMPONENT 3.96       0.600000 0.500000 0.008888 0.000380 2.38 12.80 0.008000
IC_PATROOM1_MULT5_FLR_2 VAV BOX COMPONENT 0.757874 0.980670 1.00 0.757874 1.00 0.500000 0.003626 0.000164 0.757874 12.80 0.008000
IC_PATROOM2_FLR_2 VAV BOX COMPONENT 0.229799 0.862463 1.00 0.229799 1.00 0.500000 0.004123 0.000056 0.229799 12.80 0.008000
IC_PATROOM3_MULT6_FLR_2 VAV BOX COMPONENT 0.891869 1.00 1.00 0.891869 1.00 0.500000 0.003556 0.000194 0.891869 12.80 0.008000
ICU_FLR_2 VAV BOX COMPONENT 4.39 1.00 1.00 4.39 1.00 0.500000 0.003556 0.000783 4.39 12.80 0.008000
ICU_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT 1.88 0.271239 0.181000 0.340061 0.723305 0.500000 0.001405 0.000054 0.340061 12.80 0.008000
CORRIDOR_FLR_2 VAV BOX COMPONENT 0.500330 0.866631 0.520000 0.260172 1.00 0.500000 0.000440 0.000071 0.260172 12.80 0.008000
OR_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT 2.26 0.341259 0.227000 0.513278 0.910025 0.500000 0.001116 0.000158 0.513278 12.80 0.008000
PATROOM1_MULT10_FLR_3 VAV BOX COMPONENT 1.49 1.00 0.500000 0.743225 0.952446 0.500000 0.003556 0.000197 0.743225 12.80 0.008000
PATROOM2_FLR_3 VAV BOX COMPONENT 0.247742 1.00 0.500000 0.123871 0.571467 0.500000 0.003556 0.000040 0.123871 12.80 0.008000
PATROOM3_MULT10_FLR_3 VAV BOX COMPONENT 1.44 1.00 0.500000 0.718515 0.985199 0.500000 0.003556 0.000190 0.718515 12.80 0.008000
PATROOM4_FLR_3 VAV BOX COMPONENT 0.247742 1.00 0.500000 0.123871 0.571467 0.500000 0.003556 0.000040 0.123871 12.80 0.008000
PATROOM5_MULT10_FLR_3 VAV BOX COMPONENT 1.49 1.00 0.500000 0.743225 0.952446 0.500000 0.003556 0.000197 0.743225 12.80 0.008000
PHYSTHERAPY_FLR_3 VAV BOX COMPONENT 1.11 0.333570 0.250000 0.278546 0.889519 0.500000 0.001142 0.000045 0.278546 12.80 0.008000
PATROOM6_FLR_3 VAV BOX COMPONENT 0.198193 1.00 0.500000 0.099097 0.714334 0.500000 0.003556 0.000034 0.099097 12.80 0.008000
PATROOM7_MULT10_FLR_3 VAV BOX COMPONENT 1.44 1.00 0.500000 0.718515 0.985199 0.500000 0.003556 0.000191 0.718515 12.80 0.008000
PATROOM8_FLR_3 VAV BOX COMPONENT 0.198193 1.00 0.500000 0.099097 0.714334 0.500000 0.003556 0.000034 0.099097 12.80 0.008000
NURSESTN_LOBBY_FLR_3 VAV BOX COMPONENT 1.64 0.420159 0.280000 0.459974 1.00 0.500000 0.000907 0.000074 0.459974 12.80 0.008000
LAB_FLR_3 VAV BOX COMPONENT 1.18 0.170842 1.00 1.18 1.00 0.500000 0.002230 0.000189 1.18 12.80 0.008000
CORRIDOR_SE_FLR_3 VAV BOX COMPONENT 0.507065 0.851631 0.511000 0.259110 1.00 0.500000 0.000447 0.000041 0.259110 12.80 0.008000
CORRIDOR_NW_FLR_3 VAV BOX COMPONENT 0.508798 0.848730 0.509000 0.258978 1.00 0.500000 0.000449 0.000041 0.258978 12.80 0.008000
PATROOM1_MULT10_FLR_4 VAV BOX COMPONENT 1.49 1.00 0.500000 0.743225 0.952446 0.500000 0.003556 0.000198 0.743225 12.80 0.008000
PATROOM2_FLR_4 VAV BOX COMPONENT 0.247742 1.00 0.500000 0.123871 0.571467 0.500000 0.003556 0.000040 0.123871 12.80 0.008000
PATROOM3_MULT10_FLR_4 VAV BOX COMPONENT 1.44 1.00 0.500000 0.718515 0.985199 0.500000 0.003556 0.000191 0.718515 12.80 0.008000
PATROOM4_FLR_4 VAV BOX COMPONENT 0.247742 1.00 0.500000 0.123871 0.571467 0.500000 0.003556 0.000040 0.123871 12.80 0.008000
PATROOM5_MULT10_FLR_4 VAV BOX COMPONENT 1.49 1.00 0.500000 0.743225 0.952446 0.500000 0.003556 0.000197 0.743225 12.80 0.008000
RADIOLOGY_FLR_4 VAV BOX COMPONENT 4.45 0.083542 0.063000 0.280271 0.300000 0.500000 0.004561 0.000045 0.280271 12.80 0.008000
PATROOM6_FLR_4 VAV BOX COMPONENT 0.198193 1.00 0.500000 0.099097 0.714334 0.500000 0.003556 0.000034 0.099097 12.80 0.008000
PATROOM7_MULT10_FLR_4 VAV BOX COMPONENT 1.44 1.00 0.500000 0.718515 0.985199 0.500000 0.003556 0.000191 0.718515 12.80 0.008000
PATROOM8_FLR_4 VAV BOX COMPONENT 0.198193 1.00 0.500000 0.099097 0.714334 0.500000 0.003556 0.000034 0.099097 12.80 0.008000
NURSESTN_LOBBY_FLR_4 VAV BOX COMPONENT 1.76 0.391583 0.261000 0.460051 1.00 0.500000 0.000973 0.000074 0.460051 12.80 0.008000
LAB_FLR_4 VAV BOX COMPONENT 1.19 0.169992 1.00 1.19 1.00 0.500000 0.002241 0.000190 1.19 12.80 0.008000
CORRIDOR_SE_FLR_4 VAV BOX COMPONENT 0.571037 0.756223 0.454000 0.259251 1.00 0.500000 0.000504 0.000041 0.259251 12.80 0.008000
CORRIDOR_NW_FLR_4 VAV BOX COMPONENT 0.568569 0.759507 0.456000 0.259267 1.00 0.500000 0.000502 0.000041 0.259267 12.80 0.008000
DINING_FLR_5 VAV BOX COMPONENT 2.19 0.242653 0.619000 1.35 0.647074 0.500000 0.001570 0.000375 1.35 12.80 0.008000
NURSESTN_LOBBY_FLR_5 VAV BOX COMPONENT 2.68 0.295562 0.197000 0.528470 0.788166 0.500000 0.001289 0.000227 0.528470 12.80 0.008000
OFFICE1_FLR_5 VAV BOX COMPONENT 0.286000 0.185693 0.176000 0.050336 0.495180 0.500000 0.002052 0.000054 0.100956 12.80 0.008000
OFFICE2_MULT5_FLR_5 VAV BOX COMPONENT 1.03 0.257074 0.244000 0.251970 0.685530 0.500000 0.001482 0.000151 0.285310 12.80 0.008000
OFFICE3_FLR_5 VAV BOX COMPONENT 0.334663 0.158649 0.151000 0.050534 0.423065 0.500000 0.002402 0.000053 0.100654 12.80 0.008000
OFFICE4_MULT6_FLR_5 VAV BOX COMPONENT 0.433897 0.146839 0.139000 0.060312 1.00 0.500000 0.002595 0.000059 0.111028 12.80 0.008000
CORRIDOR_FLR_5 VAV BOX COMPONENT 0.821105 0.465565 0.279000 0.229088 1.00 0.500000 0.000818 0.000113 0.229088 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 18895.53 0.000331 798.43
ER_EXAM1_MULT4_FLR_1 VAV BOX REHEAT COIL 16445.26 0.000288 715.38
ER_TRAUMA1_FLR_1 VAV BOX REHEAT COIL 4463.18 0.000078 198.41
ER_EXAM3_MULT4_FLR_1 VAV BOX REHEAT COIL 15995.57 0.000280 691.10
ER_TRAUMA2_FLR_1 VAV BOX REHEAT COIL 4464.67 0.000078 198.50
ER_TRIAGE_MULT4_FLR_1 VAV BOX REHEAT COIL 16450.50 0.000288 715.67
OFFICE1_MULT4_FLR_1 VAV BOX REHEAT COIL 2249.53 0.000039 177.96
LOBBY_RECORDS_FLR_1 VAV BOX REHEAT COIL 16036.98 0.000281 911.92
CORRIDOR_FLR_1 VAV BOX REHEAT COIL 4295.01 0.000075 217.91
ER_NURSESTN_LOBBY_FLR_1 VAV BOX REHEAT COIL 8602.30 0.000151 407.43
OR1_FLR_2 VAV BOX REHEAT COIL 6590.74 0.000115 291.73
OR2_MULT5_FLR_2 VAV BOX REHEAT COIL 29546.33 0.000517 1272.02
OR3_FLR_2 VAV BOX REHEAT COIL 6141.46 0.000107 266.88
OR4_FLR_2 VAV BOX REHEAT COIL 21738.87 0.000380 918.58
IC_PATROOM1_MULT5_FLR_2 VAV BOX REHEAT COIL 9345.92 0.000164 426.86
IC_PATROOM2_FLR_2 VAV BOX REHEAT COIL 3196.44 0.000056 152.16
IC_PATROOM3_MULT6_FLR_2 VAV BOX REHEAT COIL 11073.50 0.000194 506.81
ICU_FLR_2 VAV BOX REHEAT COIL 44766.09 0.000783 1938.71
ICU_NURSESTN_LOBBY_FLR_2 VAV BOX REHEAT COIL 3108.46 0.000054 131.35
CORRIDOR_FLR_2 VAV BOX REHEAT COIL 4057.21 0.000071 202.20
OR_NURSESTN_LOBBY_FLR_2 VAV BOX REHEAT COIL 9056.54 0.000158 470.36
PATROOM1_MULT10_FLR_3 VAV BOX REHEAT COIL 11270.06 0.000197 555.35
PATROOM2_FLR_3 VAV BOX REHEAT COIL 2288.46 0.000040 121.04
PATROOM3_MULT10_FLR_3 VAV BOX REHEAT COIL 10879.95 0.000190 535.80
PATROOM4_FLR_3 VAV BOX REHEAT COIL 2284.35 0.000040 120.74
PATROOM5_MULT10_FLR_3 VAV BOX REHEAT COIL 11239.61 0.000197 553.21
PHYSTHERAPY_FLR_3 VAV BOX REHEAT COIL 2546.16 0.000045 107.59
PATROOM6_FLR_3 VAV BOX REHEAT COIL 1918.79 0.000034 103.59
PATROOM7_MULT10_FLR_3 VAV BOX REHEAT COIL 10896.76 0.000191 536.98
PATROOM8_FLR_3 VAV BOX REHEAT COIL 1915.42 0.000034 103.33
NURSESTN_LOBBY_FLR_3 VAV BOX REHEAT COIL 4204.57 0.000074 177.66
LAB_FLR_3 VAV BOX REHEAT COIL 10795.02 0.000189 456.14
CORRIDOR_SE_FLR_3 VAV BOX REHEAT COIL 2368.50 0.000041 100.08
CORRIDOR_NW_FLR_3 VAV BOX REHEAT COIL 2367.29 0.000041 100.03
PATROOM1_MULT10_FLR_4 VAV BOX REHEAT COIL 11294.80 0.000198 557.09
PATROOM2_FLR_4 VAV BOX REHEAT COIL 2294.71 0.000040 121.51
PATROOM3_MULT10_FLR_4 VAV BOX REHEAT COIL 10901.99 0.000191 537.35
PATROOM4_FLR_4 VAV BOX REHEAT COIL 2290.32 0.000040 121.18
PATROOM5_MULT10_FLR_4 VAV BOX REHEAT COIL 11262.40 0.000197 554.81
RADIOLOGY_FLR_4 VAV BOX REHEAT COIL 2561.92 0.000045 108.25
PATROOM6_FLR_4 VAV BOX REHEAT COIL 1924.44 0.000034 104.04
PATROOM7_MULT10_FLR_4 VAV BOX REHEAT COIL 10920.70 0.000191 538.67
PATROOM8_FLR_4 VAV BOX REHEAT COIL 1920.83 0.000034 103.75
NURSESTN_LOBBY_FLR_4 VAV BOX REHEAT COIL 4205.27 0.000074 177.69
LAB_FLR_4 VAV BOX REHEAT COIL 10848.98 0.000190 458.42
CORRIDOR_SE_FLR_4 VAV BOX REHEAT COIL 2369.79 0.000041 100.14
CORRIDOR_NW_FLR_4 VAV BOX REHEAT COIL 2369.94 0.000041 100.14
DINING_FLR_5 VAV BOX REHEAT COIL 21434.45 0.000375 1072.93
NURSESTN_LOBBY_FLR_5 VAV BOX REHEAT COIL 12973.53 0.000227 809.59
OFFICE1_FLR_5 VAV BOX REHEAT COIL 3060.92 0.000054 242.15
OFFICE2_MULT5_FLR_5 VAV BOX REHEAT COIL 8650.49 0.000151 684.34
OFFICE3_FLR_5 VAV BOX REHEAT COIL 3051.76 0.000053 241.42
OFFICE4_MULT6_FLR_5 VAV BOX REHEAT COIL 3366.29 0.000059 266.30
CORRIDOR_FLR_5 VAV BOX REHEAT COIL 6479.85 0.000113 465.38
VAV_1_HEATC 58869.04 0.001030 1784.90
VAV_ER_EXTRAWATERHEATC 0.000000 0.000000 1.00
VAV_ER_HEATC 0.000000 0.000000 1.00
VAV_OR_EXTRAWATERHEATC 0.000000 0.000000 1.00
VAV_OR_HEATC 0.000000 0.000000 1.00
VAV_ICU_EXTRAWATERHEATC 0.000000 0.000000 1.00
VAV_ICU_HEATC 0.000000 0.000000 1.00
VAV_PATRMS_EXTRAWATERHEATC 40462.52 0.000708 1313.84
VAV_PATRMS_HEATC 40462.52 0.000708 1313.84
VAV_2_HEATC 61971.73 0.001084 1913.70
VAV_LABS_EXTRAWATERHEATC 0.000000 0.000000 1.00
VAV_LABS_HEATC 0.000000 0.000000 1.00
CAV_KITCHEN_HEATC 0.000000 0.000000 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [m3/s]
KITCHEN_FLR_5 CAV BOX 18.75
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_1 7.60 4.87 15.18 4.87 15.03 15.03 0.300000 0.323825 15.03
VAV_ER 5.55 5.55 5.55 5.55 5.55 5.55 1.00 1.00 5.55
VAV_OR 10.90 10.90 10.90 10.90 10.90 10.90 1.00 1.00 10.90
VAV_ICU 6.27 6.27 6.27 6.27 6.27 6.27 1.00 1.00 6.27
VAV_PATRMS 6.74 6.74 13.48 6.74 13.48 13.48 0.500000 0.500000 13.48
VAV_2 9.72 5.04 18.90 5.04 18.78 18.78 0.300000 0.268366 18.78
VAV_LABS 2.37 2.37 2.37 2.37 2.37 2.37 1.00 1.00 2.37
CAV_KITCHEN 18.75 18.75 18.75 18.75 18.75 18.75 1.00 1.00 18.75
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_1_OA_CONTROLLER 15.03  
VAV_ER_OA_CONTROLLER 5.55 0.924842
VAV_OR_OA_CONTROLLER 10.90 2.18
VAV_ICU_OA_CONTROLLER 6.27 2.08
VAV_PATRMS_OA_CONTROLLER 13.48 4.49
VAV_2_OA_CONTROLLER 18.78  
VAV_LABS_OA_CONTROLLER 2.37 0.618684
CAV_KITCHEN_OA_CONTROLLER 18.75 1.88
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV_1 OA HEAT RECOVERY 4.33
ICU OA HEAT RECOVERY 2.08
PATRMS OA HEAT RECOVERY 4.49
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Inlet Air Humidity Ratio Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio
VAV_1_COOLC 300843.43 0.008604 15.03 0.007808 28.84 7.22 10.88 0.007808
VAV_ER_COOLC 97122.13 0.002778 5.55 0.008629 26.21 7.22 10.88 0.008629
VAV_OR_COOLC 178529.87 0.005106 10.90 0.008037 25.56 7.22 10.88 0.008037
VAV_ICU_COOLC 128117.69 0.003664 6.27 0.007656 29.18 7.22 10.88 0.007656
VAV_PATRMS_COOLC 269901.53 0.007719 13.48 0.007631 28.86 7.22 10.88 0.007631
VAV_2_COOLC 358522.22 0.010254 18.78 0.007970 28.01 7.22 10.88 0.007970
VAV_LABS_COOLC 39858.74 0.001140 2.37 0.007898 25.92 7.22 10.88 0.007898
CAV_KITCHEN_COOLC 300392.74 0.008591 18.75 0.008240 25.68 7.22 10.88 0.008240
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_1_FAN 15.03
VAV_ER_FAN 5.55
VAV_OR_FAN 10.90
VAV_ICU_FAN 6.27
VAV_PATRMS_FAN 13.48
VAV_2_FAN 18.78
VAV_LABS_FAN 2.37
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_1_COOLC_CONTROLLER 0.008604 0.000055
VAV_1_HEATC_CONTROLLER 0.001030  
VAV_ER_EXTRAWATERHEATC_CONTROLLER 0.000000  
VAV_ER_COOLC_CONTROLLER 0.002778 0.000171
VAV_ER_HEATC_CONTROLLER 0.000000  
VAV_OR_EXTRAWATERHEATC_CONTROLLER 0.000000  
VAV_OR_COOLC_CONTROLLER 0.005106 0.000093
VAV_OR_HEATC_CONTROLLER 0.000000  
VAV_ICU_EXTRAWATERHEATC_CONTROLLER 0.000000  
VAV_ICU_COOLC_CONTROLLER 0.003664 0.000130
VAV_ICU_HEATC_CONTROLLER 0.000000  
VAV_PATRMS_EXTRAWATERHEATC_CONTROLLER 0.000708  
VAV_PATRMS_COOLC_CONTROLLER 0.007719 0.000062
VAV_PATRMS_HEATC_CONTROLLER 0.000708  
VAV_2_COOLC_CONTROLLER 0.010254 0.000046
VAV_2_HEATC_CONTROLLER 0.001084  
VAV_LABS_EXTRAWATERHEATC_CONTROLLER 0.000000  
VAV_LABS_COOLC_CONTROLLER 0.001140 0.000418
VAV_LABS_HEATC_CONTROLLER 0.000000  
CAV_KITCHEN_COOLC_CONTROLLER 0.008591 0.000055
CAV_KITCHEN_HEATC_CONTROLLER 0.000000  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
VAV_ER HUMIDIFIER 0.000025 0.000037 96450.70 100000.00
VAV_OR HUMIDIFIER 0.000048 0.000037 96450.70 100000.00
VAV_ICU HUMIDIFIER 0.000027 0.000037 96450.70 100000.00
VAV_PATRMS HUMIDIFIER 0.000059 0.000037 96450.70 100000.00
VAV_LABS HUMIDIFIER 0.000010 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

User-Specified Nominal Capacity [W] Design Size Nominal Capacity [W]
VAV_ER_EXTRAELECHEATC 10000000.00  
VAV_OR_EXTRAELECHEATC 10000000.00  
VAV_ICU_EXTRAELECHEATC 10000000.00  
VAV_PATRMS_EXTRAELECHEATC 10000000.00 40462.52
VAV_LABS_EXTRAELECHEATC 10000000.00  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_KITCHEN_FAN 18.75
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP SECONDARY 0.047856 9063.59
HEAT RECOVERY CHILLER BYPASS LOOP PUMP 0.047856 3021.20
HEATSYS1 PUMP 0.011678 2954.09
HEAT RECOVERY CIRC PUMP 0.005911  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.047856 5.74
HEAT RECOVERY CHILLER BYPASS LOOP 0.047856 5.74
SHWSYS1 0.000196 0.023481
HEATSYS1 0.011678 1.40
COOLSYS1_SUPPLY 0.047856 5.74
HEAT RECOVERY WATER LOOP 0.005911 0.709372
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
HEAT RECOVERY CHILLER BYPASS HEAT EXCHANGER 0.047856 0.047856 200874.95 8.33
BYPASS HEAT EXCHANGER 0.047856 0.047856 200874.95 8.33
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s] Design Size Heat Recovery Water Flow Rate [m3/s]
HEAT RECOVERY CHILLER 0.047856 0.004917 171912.43 112154.07 0.005911 0.005911
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SHWSYS1 PUMP 0.000196 25.00
COOLSYS1 CHILLER1 PUMP 0.023928 1510.60
COOLSYS1 CHILLER2 PUMP 0.023928 1510.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s] Source Side Design Flow Rate [m3/s]
SHWSYS1 WATER HEATER 0.000196  
DUMMY WATER HEATER 0.011678 0.005911
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 667444.25 667444.25 0.011678
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.047856 0.023329 801942.79 801100.52 0.040614
COOLSYS1 CHILLER2 0.047856 0.023329 801942.79 801100.52 0.040614
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.087140 10.46
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.087140 18257.83
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 32.84 735334.23 6.57 91916.78
TOWERWATERSYS COOLTOWER 2 32.84 735334.23 6.57 91916.78
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2020-06-03 20:39:13

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
ER_EXAM1_MULT4_FLR_1_WALL_SOUTH ER_EXAM1_MULT4_FLR_1_WALL_SOUTH_DOOR |
ER_TRAUMA1_FLR_1_WALL_EAST ER_TRAUMA1_FLR_1_WALL_EAST_DOOR |
ER_TRAUMA1_FLR_1_WALL_SOUTH ER_TRAUMA1_FLR_1_WALL_SOUTH_DOOR |
ER_EXAM3_MULT4_FLR_1_WALL_EAST ER_EXAM3_MULT4_FLR_1_WALL_EAST_DOOR |
ER_TRAUMA2_FLR_1_WALL_NORTH ER_TRAUMA2_FLR_1_WALL_NORTH_DOOR |
ER_TRAUMA2_FLR_1_WALL_EAST ER_TRAUMA2_FLR_1_WALL_EAST_DOOR |
ER_TRIAGE_MULT4_FLR_1_WALL_NORTH ER_TRIAGE_MULT4_FLR_1_WALL_NORTH_DOOR |
OFFICE1_MULT4_FLR_1_WALL_SOUTH OFFICE1_MULT4_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_RECORDS_FLR_1_WALL_NORTH LOBBY_RECORDS_FLR_1_WALL_NORTH_DOOR1 | LOBBY_RECORDS_FLR_1_WALL_NORTH_DOOR3 | LOBBY_RECORDS_FLR_1_WALL_NORTH_DOOR2 |
LOBBY_RECORDS_FLR_1_WALL_1_WEST LOBBY_RECORDS_FLR_1_WALL_2_WEST |
LOBBY_RECORDS_FLR_1_WALL_1_SOUTH LOBBY_RECORDS_FLR_1_WALL_1_SOUTH_DOOR |
LOBBY_RECORDS_FLR_1_WALL_2_SOUTH LOBBY_RECORDS_FLR_1_WALL_2_SOUTH_DOOR | LOBBY_RECORDS_FLR_1_WALL_2_SOUTH_ROLLDOOR |
CORRIDOR_FLR_1_WALL_NORTH CORRIDOR_FLR_1_WALL_NORTH_DOOR2 | CORRIDOR_FLR_1_WALL_NORTH_DOOR1 |
CORRIDOR_FLR_1_WALL_SOUTH CORRIDOR_FLR_1_WALL_SOUTH_DOOR2 | CORRIDOR_FLR_1_WALL_SOUTH_DOOR1 |
ER_NURSESTN_LOBBY_FLR_1_WALL_1_EAST ER_NURSESTN_LOBBY_FLR_1_WALL_1_EAST_WINDOW |
IC_PATROOM1_MULT5_FLR_2_WALL_NORTH IC_PATROOM1_MULT5_FLR_2_WALL_NORTH_WINDOW |
IC_PATROOM2_FLR_2_WALL_NORTH IC_PATROOM2_FLR_2_WALL_NORTH_WINDOW |
IC_PATROOM2_FLR_2_WALL_WEST IC_PATROOM2_FLR_2_WALL_WEST_WINDOW |
IC_PATROOM3_MULT6_FLR_2_WALL_WEST IC_PATROOM3_MULT6_FLR_2_WALL_WEST_WINDOW |
ICU_FLR_2_WALL_WEST ICU_FLR_2_WALL_WEST_WINDOW |
OR_NURSESTN_LOBBY_FLR_2_WALL_SOUTH OR_NURSESTN_LOBBY_FLR_2_WALL_SOUTH_WINDOW |
PATROOM1_MULT10_FLR_3_WALL_SOUTH PATROOM1_MULT10_FLR_3_WALL_SOUTH_WINDOW |
PATROOM2_FLR_3_WALL_EAST PATROOM2_FLR_3_WALL_EAST_WINDOW |
PATROOM2_FLR_3_WALL_SOUTH PATROOM2_FLR_3_WALL_SOUTH_WINDOW |
PATROOM3_MULT10_FLR_3_WALL_EAST PATROOM3_MULT10_FLR_3_WALL_EAST_WINDOW |
PATROOM4_FLR_3_WALL_NORTH PATROOM4_FLR_3_WALL_NORTH_WINDOW |
PATROOM4_FLR_3_WALL_EAST PATROOM4_FLR_3_WALL_EAST_WINDOW |
PATROOM5_MULT10_FLR_3_WALL_NORTH PATROOM5_MULT10_FLR_3_WALL_NORTH_WINDOW |
PATROOM6_FLR_3_WALL_SOUTH PATROOM6_FLR_3_WALL_SOUTH_WINDOW |
PATROOM6_FLR_3_WALL_WEST PATROOM6_FLR_3_WALL_WEST_WINDOW |
PATROOM7_MULT10_FLR_3_WALL_WEST PATROOM7_MULT10_FLR_3_WALL_WEST_WINDOW |
PATROOM8_FLR_3_WALL_NORTH PATROOM8_FLR_3_WALL_NORTH_WINDOW |
PATROOM8_FLR_3_WALL_WEST PATROOM8_FLR_3_WALL_WEST_WINDOW |
PATROOM1_MULT10_FLR_4_WALL_SOUTH PATROOM1_MULT10_FLR_4_WALL_SOUTH_WINDOW |
PATROOM2_FLR_4_WALL_EAST PATROOM2_FLR_4_WALL_EAST_WINDOW |
PATROOM2_FLR_4_WALL_SOUTH PATROOM2_FLR_4_WALL_SOUTH_WINDOW |
PATROOM3_MULT10_FLR_4_WALL_EAST PATROOM3_MULT10_FLR_4_WALL_EAST_WINDOW |
PATROOM4_FLR_4_WALL_NORTH PATROOM4_FLR_4_WALL_NORTH_WINDOW |
PATROOM4_FLR_4_WALL_EAST PATROOM4_FLR_4_WALL_EAST_WINDOW |
PATROOM5_MULT10_FLR_4_WALL_NORTH PATROOM5_MULT10_FLR_4_WALL_NORTH_WINDOW |
PATROOM6_FLR_4_WALL_SOUTH PATROOM6_FLR_4_WALL_SOUTH_WINDOW |
PATROOM6_FLR_4_WALL_WEST PATROOM6_FLR_4_WALL_WEST_WINDOW |
PATROOM7_MULT10_FLR_4_WALL_WEST PATROOM7_MULT10_FLR_4_WALL_WEST_WINDOW |
PATROOM8_FLR_4_WALL_NORTH PATROOM8_FLR_4_WALL_NORTH_WINDOW |
PATROOM8_FLR_4_WALL_WEST PATROOM8_FLR_4_WALL_WEST_WINDOW |
DINING_FLR_5_WALL_SOUTH DINING_FLR_5_WALL_SOUTH_WINDOW |
OFFICE1_FLR_5_WALL_SOUTH OFFICE1_FLR_5_WALL_SOUTH_WINDOW |
OFFICE1_FLR_5_WALL_WEST OFFICE1_FLR_5_WALL_WEST_WINDOW |
OFFICE2_MULT5_FLR_5_WALL_WEST OFFICE2_MULT5_FLR_5_WALL_WEST_WINDOW |
OFFICE3_FLR_5_WALL_NORTH OFFICE3_FLR_5_WALL_NORTH_WINDOW |
OFFICE3_FLR_5_WALL_WEST OFFICE3_FLR_5_WALL_WEST_WINDOW |
OFFICE4_MULT6_FLR_5_WALL_NORTH OFFICE4_MULT6_FLR_5_WALL_NORTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2020-06-03 20:39:13

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2020-06-03 20:39:13

Version

Version ID
1 9.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 20.90 15.40 11.90 14.80 12.70 15.40 23.30 26.30 31.20 30.40 29.80 27.80


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 32.17 -110.88 -7.00 809.00 91976 1.0932


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 21.66 19.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 Hospital -90.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance

Adjust Zone Mixing

Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}
Infiltration Zones {MixingSourceZonesOnly
AllZones}
1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 55 514 57


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 -26.67 35.05 -1.22 1 1 1 -53.34 4.29E-015 0.00 70.10 -2.44 0.00 2.44 9120.27 TARP TARP 3739.35 0.00 0.00 0.00 6 0 0 Yes
2 ER_EXAM1_MULT4_FLR_1 0.0 0.00 0.00 0.00 -2.29 42.67 2.13 1 4 1 -4.57 2.80E-015 39.62 45.72 0.00 4.27 4.27 118.96 TARP TARP 27.87 26.02 24.07 0.00 6 1 0 Yes
3 ER_TRAUMA1_FLR_1 0.0 0.00 0.00 0.00 -2.29 67.06 2.13 1 1 1 -4.57 4.29E-015 64.01 70.10 0.00 4.27 4.27 118.96 TARP TARP 27.87 45.53 41.63 0.00 6 2 0 Yes
4 ER_EXAM3_MULT4_FLR_1 0.0 0.00 0.00 0.00 -6.86 67.06 2.13 1 4 1 -9.14 -4.57 64.01 70.10 0.00 4.27 4.27 118.96 TARP TARP 27.87 19.51 17.56 0.00 6 1 0 Yes
5 ER_TRAUMA2_FLR_1 0.0 0.00 0.00 0.00 -51.05 67.06 2.13 1 1 1 -53.34 -48.77 64.01 70.10 0.00 4.27 4.27 118.96 TARP TARP 27.87 45.53 41.63 0.00 6 2 0 Yes
6 ER_TRIAGE_MULT4_FLR_1 0.0 0.00 0.00 0.00 -51.05 42.67 2.13 1 4 1 -53.34 -48.77 39.62 45.72 0.00 4.27 4.27 118.96 TARP TARP 27.87 26.02 24.07 0.00 6 1 0 Yes
7 OFFICE1_MULT4_FLR_1 0.0 0.00 0.00 0.00 -2.29 7.62 2.13 1 5 1 -4.57 5.60E-016 6.10 9.14 0.00 4.27 4.27 59.50 TARP TARP 13.94 13.01 10.05 2.96 6 1 0 Yes
8 LOBBY_RECORDS_FLR_1 0.0 0.00 0.00 0.00 -16.75 14.17 2.13 1 1 1 -53.34 1.77E-015 0.00 28.96 0.00 4.27 4.27 6294.92 TARP TARP 1474.81 409.78 329.96 62.63 11 7 0 Yes
9 CORRIDOR_FLR_1 0.0 0.00 0.00 0.00 -26.67 34.29 2.13 1 1 1 -53.34 2.43E-015 28.96 39.62 0.00 4.27 4.27 2428.79 TARP TARP 569.03 91.07 83.26 0.00 7 4 0 Yes
10 ER_NURSESTN_LOBBY_FLR_1 0.0 0.00 0.00 0.00 -26.67 58.35 2.13 1 1 1 -48.77 -4.57 39.62 70.10 0.00 4.27 4.27 5273.95 TARP TARP 1235.61 110.58 80.16 30.42 10 1 0 Yes
11 OR1_FLR_2 0.0 0.00 0.00 0.00 -50.29 65.53 6.40 1 1 1 -53.34 -47.24 60.96 70.10 4.27 8.54 4.27 237.91 TARP TARP 55.74 65.05 65.05 0.00 6 0 0 Yes
12 OR2_MULT5_FLR_2 0.0 0.00 0.00 0.00 -44.20 65.53 6.40 1 5 1 -47.24 -41.15 60.96 70.10 4.27 8.54 4.27 237.91 TARP TARP 55.74 26.02 26.02 0.00 6 0 0 Yes
13 OR3_FLR_2 0.0 0.00 0.00 0.00 -50.29 44.20 6.40 1 1 1 -53.34 -47.24 39.62 48.77 4.27 8.54 4.27 237.91 TARP TARP 55.74 39.03 39.03 0.00 6 0 0 Yes
14 OR4_FLR_2 0.0 0.00 0.00 0.00 -35.05 44.20 6.40 1 1 1 -47.24 -22.86 39.62 48.77 4.27 8.54 4.27 951.70 TARP TARP 222.97 0.00 0.00 0.00 6 0 0 Yes
15 IC_PATROOM1_MULT5_FLR_2 0.0 0.00 0.00 0.00 -51.05 26.67 6.40 1 5 1 -53.34 -48.77 24.38 28.96 4.27 8.54 4.27 89.21 TARP TARP 20.90 19.51 14.61 4.91 6 1 0 Yes
16 IC_PATROOM2_FLR_2 0.0 0.00 0.00 0.00 -51.05 3.05 6.40 1 1 1 -53.34 -48.77 2.99E-015 6.10 4.27 8.54 4.27 118.96 TARP TARP 27.87 45.53 34.09 11.44 6 2 0 Yes
17 IC_PATROOM3_MULT6_FLR_2 0.0 0.00 0.00 0.00 -46.48 2.29 6.40 1 6 1 -48.77 -44.20 2.71E-015 4.57 4.27 8.54 4.27 89.21 TARP TARP 20.90 19.51 14.61 4.91 6 1 0 Yes
18 ICU_FLR_2 0.0 0.00 0.00 0.00 -10.67 14.48 6.40 1 1 1 -21.34 1.77E-015 0.00 28.96 4.27 8.54 4.27 2637.63 TARP TARP 617.96 214.68 189.65 25.03 6 1 0 Yes
19 ICU_NURSESTN_LOBBY_FLR_2 0.0 0.00 0.00 0.00 -35.05 16.76 6.40 1 1 1 -48.77 -21.34 4.57 28.96 4.27 8.54 4.27 2854.51 TARP TARP 668.77 0.00 0.00 0.00 6 0 0 Yes
20 CORRIDOR_FLR_2 0.0 0.00 0.00 0.00 -26.67 34.29 6.40 1 1 1 -53.34 2.43E-015 28.96 39.62 4.27 8.54 4.27 2428.79 TARP TARP 569.03 91.07 91.07 0.00 6 0 0 Yes
21 OR_NURSESTN_LOBBY_FLR_2 0.0 0.00 0.00 0.00 -23.18 54.78 6.40 1 1 1 -53.34 4.29E-015 39.62 70.10 4.27 8.54 4.27 4322.24 TARP TARP 1012.64 182.14 146.37 35.76 10 1 0 Yes
22 PATROOM1_MULT10_FLR_3 0.0 0.00 0.00 0.00 -2.29 41.91 10.67 1 10 1 -4.57 2.71E-015 39.62 44.20 8.54 12.80 4.27 89.21 TARP TARP 20.90 19.51 14.61 4.91 6 1 0 Yes
23 PATROOM2_FLR_3 0.0 0.00 0.00 0.00 -2.29 66.29 10.67 1 1 1 -4.57 4.29E-015 62.48 70.10 8.54 12.80 4.27 148.71 TARP TARP 34.84 52.04 38.96 13.08 6 2 0 Yes
24 PATROOM3_MULT10_FLR_3 0.0 0.00 0.00 0.00 -6.78 67.82 10.67 1 10 1 -8.99 -4.57 65.53 70.10 8.54 12.80 4.27 86.26 TARP TARP 20.21 18.87 14.13 4.74 6 1 0 Yes
25 PATROOM4_FLR_3 0.0 0.00 0.00 0.00 -51.05 66.29 10.67 1 1 1 -53.34 -48.77 62.48 70.10 8.54 12.80 4.27 148.71 TARP TARP 34.84 52.04 38.96 13.08 6 2 0 Yes
26 PATROOM5_MULT10_FLR_3 0.0 0.00 0.00 0.00 -51.05 41.91 10.67 1 10 1 -53.34 -48.77 39.62 44.20 8.54 12.80 4.27 89.21 TARP TARP 20.90 19.51 14.61 4.91 6 1 0 Yes
27 PHYSTHERAPY_FLR_3 0.0 0.00 0.00 0.00 -31.24 50.29 10.67 1 1 1 -42.67 -19.81 39.62 60.96 8.54 12.80 4.27 2081.82 TARP TARP 487.74 0.00 0.00 0.00 6 0 0 Yes
28 PATROOM6_FLR_3 0.0 0.00 0.00 0.00 -2.29 3.05 10.67 1 1 1 -4.57 3.73E-016 0.00 6.10 8.54 12.80 4.27 118.96 TARP TARP 27.87 45.53 34.09 11.44 6 2 0 Yes
29 PATROOM7_MULT10_FLR_3 0.0 0.00 0.00 0.00 -6.78 2.29 10.67 1 10 1 -8.99 -4.57 2.80E-016 4.57 8.54 12.80 4.27 86.26 TARP TARP 20.21 18.87 14.13 4.74 6 1 0 Yes
30 PATROOM8_FLR_3 0.0 0.00 0.00 0.00 -51.05 3.05 10.67 1 1 1 -53.34 -48.77 2.99E-015 6.10 8.54 12.80 4.27 118.96 TARP TARP 27.87 45.53 34.09 11.44 6 2 0 Yes
31 NURSESTN_LOBBY_FLR_3 0.0 0.00 0.00 0.00 -25.31 31.62 10.67 1 1 1 -42.67 -10.67 9.14 60.96 8.54 12.80 4.27 3866.25 TARP TARP 905.80 0.00 0.00 0.00 12 0 0 Yes
32 LAB_FLR_3 0.0 0.00 0.00 0.00 -20.75 17.40 10.67 1 1 1 -33.58 -10.67 9.14 28.96 8.54 12.80 4.27 1129.43 TARP TARP 264.77 0.00 0.00 0.00 8 0 0 Yes
33 CORRIDOR_SE_FLR_3 0.0 0.00 0.00 0.00 -13.04 41.59 10.67 1 1 1 -42.67 2.43E-015 4.57 65.53 8.54 12.80 4.27 2418.88 TARP TARP 566.71 45.53 45.53 0.00 15 0 0 Yes
34 CORRIDOR_NW_FLR_3 0.0 0.00 0.00 0.00 -40.30 28.14 10.67 1 1 1 -53.34 -10.67 4.57 65.53 8.54 12.80 4.27 2418.88 TARP TARP 566.71 45.53 45.53 0.00 15 0 0 Yes
35 PATROOM1_MULT10_FLR_4 0.0 0.00 0.00 0.00 -2.29 41.91 14.94 1 10 1 -4.57 2.71E-015 39.62 44.20 12.80 17.07 4.27 89.21 TARP TARP 20.90 19.51 14.61 4.91 6 1 0 Yes
36 PATROOM2_FLR_4 0.0 0.00 0.00 0.00 -2.29 66.29 14.94 1 1 1 -4.57 4.29E-015 62.48 70.10 12.80 17.07 4.27 148.71 TARP TARP 34.84 52.04 38.96 13.08 6 2 0 Yes
37 PATROOM3_MULT10_FLR_4 0.0 0.00 0.00 0.00 -6.78 67.82 14.94 1 10 1 -8.99 -4.57 65.53 70.10 12.80 17.07 4.27 86.26 TARP TARP 20.21 18.87 14.13 4.74 6 1 0 Yes
38 PATROOM4_FLR_4 0.0 0.00 0.00 0.00 -51.05 66.29 14.94 1 1 1 -53.34 -48.77 62.48 70.10 12.80 17.07 4.27 148.71 TARP TARP 34.84 52.04 38.96 13.08 6 2 0 Yes
39 PATROOM5_MULT10_FLR_4 0.0 0.00 0.00 0.00 -51.05 41.91 14.94 1 10 1 -53.34 -48.77 39.62 44.20 12.80 17.07 4.27 89.21 TARP TARP 20.90 19.51 14.61 4.91 6 1 0 Yes
40 RADIOLOGY_FLR_4 0.0 0.00 0.00 0.00 -31.24 50.29 14.94 1 1 1 -42.67 -19.81 39.62 60.96 12.80 17.07 4.27 2081.82 TARP TARP 487.74 0.00 0.00 0.00 6 0 0 Yes
41 PATROOM6_FLR_4 0.0 0.00 0.00 0.00 -2.29 3.05 14.94 1 1 1 -4.57 3.73E-016 0.00 6.10 12.80 17.07 4.27 118.96 TARP TARP 27.87 45.53 34.09 11.44 6 2 0 Yes
42 PATROOM7_MULT10_FLR_4 0.0 0.00 0.00 0.00 -6.78 2.29 14.94 1 10 1 -8.99 -4.57 2.80E-016 4.57 12.80 17.07 4.27 86.26 TARP TARP 20.21 18.87 14.13 4.74 6 1 0 Yes
43 PATROOM8_FLR_4 0.0 0.00 0.00 0.00 -51.05 3.05 14.94 1 1 1 -53.34 -48.77 2.99E-015 6.10 12.80 17.07 4.27 118.96 TARP TARP 27.87 45.53 34.09 11.44 6 2 0 Yes
44 NURSESTN_LOBBY_FLR_4 0.0 0.00 0.00 0.00 -25.31 31.62 14.94 1 1 1 -42.67 -10.67 9.14 60.96 12.80 17.07 4.27 3866.22 TARP TARP 905.80 0.00 0.00 0.00 12 0 0 Yes
45 LAB_FLR_4 0.0 0.00 0.00 0.00 -20.75 17.40 14.94 1 1 1 -33.58 -10.67 9.14 28.96 12.80 17.07 4.27 1129.43 TARP TARP 264.77 0.00 0.00 0.00 8 0 0 Yes
46 CORRIDOR_SE_FLR_4 0.0 0.00 0.00 0.00 -13.04 41.59 14.94 1 1 1 -42.67 2.43E-015 4.57 65.53 12.80 17.07 4.27 2418.88 TARP TARP 566.71 45.53 45.53 0.00 15 0 0 Yes
47 CORRIDOR_NW_FLR_4 0.0 0.00 0.00 0.00 -40.30 28.14 14.94 1 1 1 -53.34 -10.67 4.57 65.53 12.80 17.07 4.27 2418.88 TARP TARP 566.71 45.53 45.53 0.00 15 0 0 Yes
48 DINING_FLR_5 0.0 0.00 0.00 0.00 -11.43 54.86 19.21 1 1 1 -22.86 4.29E-015 39.62 70.10 17.07 21.34 4.27 2974.04 TARP TARP 696.77 227.67 191.91 35.76 6 1 0 Yes
49 NURSESTN_LOBBY_FLR_5 0.0 0.00 0.00 0.00 -21.34 27.43 19.21 1 1 1 -42.67 2.43E-015 15.24 39.62 17.07 21.34 4.27 4441.23 TARP TARP 1040.51 104.08 104.08 0.00 7 0 0 Yes
50 KITCHEN_FLR_5 0.0 0.00 0.00 0.00 -38.10 54.86 19.21 1 1 1 -53.34 -22.86 39.62 70.10 17.07 21.34 4.27 3965.37 TARP TARP 929.03 260.20 260.20 0.00 7 0 0 Yes
51 OFFICE1_FLR_5 0.0 0.00 0.00 0.00 -3.81 4.57 19.21 1 1 1 -7.62 5.60E-016 0.00 9.14 17.07 21.34 4.27 297.50 TARP TARP 69.70 71.56 53.58 17.98 6 2 0 Yes
52 OFFICE2_MULT5_FLR_5 0.0 0.00 0.00 0.00 -11.43 4.57 19.21 1 5 1 -15.24 -7.62 4.67E-016 9.14 17.07 21.34 4.27 297.41 TARP TARP 69.68 32.52 24.34 8.17 6 1 0 Yes
53 OFFICE3_FLR_5 0.0 0.00 0.00 0.00 -49.53 4.57 19.21 1 1 1 -53.34 -45.72 2.80E-015 9.14 17.07 21.34 4.27 297.41 TARP TARP 69.68 71.55 53.57 17.98 6 2 0 Yes
54 OFFICE4_MULT6_FLR_5 0.0 0.00 0.00 0.00 -51.05 10.67 19.21 1 6 1 -53.34 -48.77 9.14 12.19 17.07 21.34 4.27 59.50 TARP TARP 13.94 13.01 10.05 2.96 6 1 0 Yes
55 CORRIDOR_FLR_5 0.0 0.00 0.00 0.00 -34.61 21.12 19.21 1 1 1 -53.34 9.33E-016 9.14 39.62 17.07 21.34 4.27 2141.32 TARP TARP 501.68 78.06 78.06 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 3739.35 100.6 37.175 2.690E-002 6.889 8.070 0.000 0.000 0.000 0.000 14.959 No
2 ER_EXAM1_MULT4_FLR_1 27.87 6.0 4.647 0.215 15.069 16.140 0.000 0.000 0.000 0.000 31.209 No
3 ER_TRAUMA1_FLR_1 27.87 6.0 4.647 0.215 15.069 43.040 0.000 0.000 0.000 0.000 58.109 No
4 ER_EXAM3_MULT4_FLR_1 27.87 6.0 4.647 0.215 15.069 16.140 0.000 0.000 0.000 0.000 31.209 No
5 ER_TRAUMA2_FLR_1 27.87 6.0 4.647 0.215 15.069 43.040 0.000 0.000 0.000 0.000 58.109 No
6 ER_TRIAGE_MULT4_FLR_1 27.87 6.0 4.647 0.215 15.069 21.527 0.000 0.000 0.000 0.000 36.597 No
7 OFFICE1_MULT4_FLR_1 13.94 1.1 13.272 7.535E-002 6.889 11.840 0.000 0.000 0.000 0.000 18.729 No
8 LOBBY_RECORDS_FLR_1 1474.81 21.2 69.703 1.435E-002 8.794 1.080 0.000 0.000 0.000 0.000 9.874 No
9 CORRIDOR_FLR_1 569.03 6.1 92.936 1.076E-002 7.642 0.000 0.000 0.000 0.000 0.000 7.642 No
10 ER_NURSESTN_LOBBY_FLR_1 1235.61 17.7 69.703 1.435E-002 11.173 14.630 0.000 0.000 0.000 0.000 25.803 No
11 OR1_FLR_2 55.74 3.0 18.588 5.380E-002 24.326 43.040 0.000 0.000 0.000 0.000 67.366 No
12 OR2_MULT5_FLR_2 55.74 3.0 18.588 5.380E-002 24.326 43.040 0.000 0.000 0.000 0.000 67.366 No
13 OR3_FLR_2 55.74 3.0 18.588 5.380E-002 24.326 43.040 0.000 0.000 0.000 0.000 67.366 No
14 OR4_FLR_2 222.97 12.0 18.587 5.380E-002 24.326 43.040 0.000 0.000 0.000 0.000 67.366 No
15 IC_PATROOM1_MULT5_FLR_2 20.90 1.1 18.591 5.379E-002 13.455 32.280 0.000 0.000 0.000 0.000 45.735 No
16 IC_PATROOM2_FLR_2 27.87 1.5 18.588 5.380E-002 13.455 32.280 0.000 0.000 0.000 0.000 45.735 No
17 IC_PATROOM3_MULT6_FLR_2 20.90 1.1 18.591 5.379E-002 13.455 32.280 0.000 0.000 0.000 0.000 45.735 No
18 ICU_FLR_2 617.96 33.2 18.588 5.380E-002 13.455 32.280 0.000 0.000 0.000 0.000 45.735 No
19 ICU_NURSESTN_LOBBY_FLR_2 668.77 9.6 69.703 1.435E-002 12.594 21.520 0.000 0.000 0.000 0.000 34.114 No
20 CORRIDOR_FLR_2 569.03 6.1 92.936 1.076E-002 7.642 0.000 0.000 0.000 0.000 0.000 7.642 No
21 OR_NURSESTN_LOBBY_FLR_2 1012.64 14.5 69.703 1.435E-002 10.463 11.190 0.000 0.000 0.000 0.000 21.653 No
22 PATROOM1_MULT10_FLR_3 20.90 1.1 18.591 5.379E-002 7.319 21.520 0.000 0.000 0.000 0.000 28.839 No
23 PATROOM2_FLR_3 34.84 1.9 18.587 5.380E-002 7.319 21.520 0.000 0.000 0.000 0.000 28.839 No
24 PATROOM3_MULT10_FLR_3 20.21 1.1 18.586 5.380E-002 7.319 21.520 0.000 0.000 0.000 0.000 28.839 No
25 PATROOM4_FLR_3 34.84 1.9 18.587 5.380E-002 7.319 21.520 0.000 0.000 0.000 0.000 28.839 No
26 PATROOM5_MULT10_FLR_3 20.90 1.1 18.591 5.379E-002 7.319 21.520 0.000 0.000 0.000 0.000 28.839 No
27 PHYSTHERAPY_FLR_3 487.74 26.2 18.587 5.380E-002 9.795 16.140 0.000 0.000 0.000 0.000 25.935 No
28 PATROOM6_FLR_3 27.87 1.5 18.588 5.380E-002 7.319 21.520 0.000 0.000 0.000 0.000 28.839 No
29 PATROOM7_MULT10_FLR_3 20.21 1.1 18.586 5.380E-002 7.319 21.520 0.000 0.000 0.000 0.000 28.839 No
30 PATROOM8_FLR_3 27.87 1.5 18.588 5.380E-002 7.319 21.520 0.000 0.000 0.000 0.000 28.839 No
31 NURSESTN_LOBBY_FLR_3 905.80 13.0 69.703 1.435E-002 10.463 11.190 0.000 0.000 0.000 0.000 21.653 No
32 LAB_FLR_3 264.77 14.2 18.588 5.380E-002 14.316 43.040 0.000 0.000 0.000 0.000 57.356 No
33 CORRIDOR_SE_FLR_3 566.71 6.1 92.937 1.076E-002 7.642 0.000 0.000 0.000 0.000 0.000 7.642 No
34 CORRIDOR_NW_FLR_3 566.71 6.1 92.937 1.076E-002 7.642 0.000 0.000 0.000 0.000 0.000 7.642 No
35 PATROOM1_MULT10_FLR_4 20.90 1.1 18.591 5.379E-002 7.319 21.520 0.000 0.000 0.000 0.000 28.839 No
36 PATROOM2_FLR_4 34.84 1.9 18.587 5.380E-002 7.319 21.520 0.000 0.000 0.000 0.000 28.839 No
37 PATROOM3_MULT10_FLR_4 20.21 1.1 18.586 5.380E-002 7.319 21.520 0.000 0.000 0.000 0.000 28.839 No
38 PATROOM4_FLR_4 34.84 1.9 18.587 5.380E-002 7.319 21.520 0.000 0.000 0.000 0.000 28.839 No
39 PATROOM5_MULT10_FLR_4 20.90 1.1 18.591 5.379E-002 7.319 21.520 0.000 0.000 0.000 0.000 28.839 No
40 RADIOLOGY_FLR_4 487.74 26.2 18.587 5.380E-002 10.118 107.639 0.000 0.000 0.000 0.000 117.757 No
41 PATROOM6_FLR_4 27.87 1.5 18.588 5.380E-002 7.319 21.520 0.000 0.000 0.000 0.000 28.839 No
42 PATROOM7_MULT10_FLR_4 20.21 1.1 18.586 5.380E-002 7.319 21.520 0.000 0.000 0.000 0.000 28.839 No
43 PATROOM8_FLR_4 27.87 1.5 18.588 5.380E-002 7.319 21.520 0.000 0.000 0.000 0.000 28.839 No
44 NURSESTN_LOBBY_FLR_4 905.80 13.0 69.703 1.435E-002 10.463 11.190 0.000 0.000 0.000 0.000 21.653 No
45 LAB_FLR_4 264.77 14.2 18.588 5.380E-002 14.316 43.040 0.000 0.000 0.000 0.000 57.356 No
46 CORRIDOR_SE_FLR_4 566.71 6.1 92.937 1.076E-002 7.642 0.000 0.000 0.000 0.000 0.000 7.642 No
47 CORRIDOR_NW_FLR_4 566.71 6.1 92.937 1.076E-002 7.642 0.000 0.000 0.000 0.000 0.000 7.642 No
48 DINING_FLR_5 696.77 75.0 9.294 0.108 4.306 10.760 0.000 0.000 0.000 0.000 15.066 No
49 NURSESTN_LOBBY_FLR_5 1040.51 14.9 69.703 1.435E-002 10.463 11.190 0.000 0.000 0.000 0.000 21.653 No
50 KITCHEN_FLR_5 929.03 50.0 18.587 5.380E-002 11.733 81.803 161.400 0.000 0.000 0.000 254.936 No
51 OFFICE1_FLR_5 69.70 5.2 13.276 7.532E-002 6.889 10.760 0.000 0.000 0.000 0.000 17.649 No
52 OFFICE2_MULT5_FLR_5 69.68 5.2 13.276 7.532E-002 6.889 10.760 0.000 0.000 0.000 0.000 17.649 No
53 OFFICE3_FLR_5 69.68 5.2 13.276 7.532E-002 6.889 10.760 0.000 0.000 0.000 0.000 17.649 No
54 OFFICE4_MULT6_FLR_5 13.94 1.1 13.272 7.535E-002 6.889 10.760 0.000 0.000 0.000 0.000 17.649 No
55 CORRIDOR_FLR_5 501.68 5.4 92.936 1.076E-002 7.642 0.000 0.000 0.000 0.000 0.000 7.642 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation
1 BASEMENT BLDG_OCC_SCH BASEMENT 3739.35 100.6 100.6 2.690E-002 37.175 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 101 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
2 ER_EXAM1_MULT4_FLR_1 BLDG_OCC_EXTD_SCH ER_EXAM1_MULT4_FLR_1 27.87 6.0 6.0 0.215 4.647 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
3 ER_TRAUMA1_FLR_1 BLDG_OCC_EXTD_SCH ER_TRAUMA1_FLR_1 27.87 6.0 6.0 0.215 4.647 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
4 ER_EXAM3_MULT4_FLR_1 BLDG_OCC_EXTD_SCH ER_EXAM3_MULT4_FLR_1 27.87 6.0 6.0 0.215 4.647 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
5 ER_TRAUMA2_FLR_1 BLDG_OCC_EXTD_SCH ER_TRAUMA2_FLR_1 27.87 6.0 6.0 0.215 4.647 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
6 ER_TRIAGE_MULT4_FLR_1 BLDG_OCC_EXTD_SCH ER_TRIAGE_MULT4_FLR_1 27.87 6.0 6.0 0.215 4.647 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
7 OFFICE1_MULT4_FLR_1 BLDG_OCC_SCH OFFICE1_MULT4_FLR_1 13.94 1.1 1.1 7.535E-002 13.272 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
8 LOBBY_RECORDS_FLR_1 BLDG_OCC_SCH LOBBY_RECORDS_FLR_1 1474.81 21.2 21.2 1.435E-002 69.703 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
9 CORRIDOR_FLR_1 BLDG_OCC_EXTD_SCH CORRIDOR_FLR_1 569.03 6.1 6.1 1.076E-002 92.936 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
10 ER_NURSESTN_LOBBY_FLR_1 BLDG_OCC_EXTD_SCH ER_NURSESTN_LOBBY_FLR_1 1235.61 17.7 17.7 1.435E-002 69.703 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 18 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
11 OR1_FLR_2 BLDG_OCC_SCH OR1_FLR_2 55.74 3.0 3.0 5.380E-002 18.588 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
12 OR2_MULT5_FLR_2 BLDG_OCC_SCH OR2_MULT5_FLR_2 55.74 3.0 3.0 5.380E-002 18.588 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
13 OR3_FLR_2 BLDG_OCC_SCH OR3_FLR_2 55.74 3.0 3.0 5.380E-002 18.588 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
14 OR4_FLR_2 BLDG_OCC_SCH OR4_FLR_2 222.97 12.0 12.0 5.380E-002 18.587 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 12 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
15 IC_PATROOM1_MULT5_FLR_2 BLDG_OCC_EXTD_SCH IC_PATROOM1_MULT5_FLR_2 20.90 1.1 1.1 5.379E-002 18.591 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
16 IC_PATROOM2_FLR_2 BLDG_OCC_EXTD_SCH IC_PATROOM2_FLR_2 27.87 1.5 1.5 5.380E-002 18.588 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
17 IC_PATROOM3_MULT6_FLR_2 BLDG_OCC_EXTD_SCH IC_PATROOM3_MULT6_FLR_2 20.90 1.1 1.1 5.379E-002 18.591 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
18 ICU_FLR_2 BLDG_OCC_EXTD_SCH ICU_FLR_2 617.96 33.2 33.2 5.380E-002 18.588 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 33 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
19 ICU_NURSESTN_LOBBY_FLR_2 BLDG_OCC_EXTD_SCH ICU_NURSESTN_LOBBY_FLR_2 668.77 9.6 9.6 1.435E-002 69.703 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 10 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
20 CORRIDOR_FLR_2 BLDG_OCC_EXTD_SCH CORRIDOR_FLR_2 569.03 6.1 6.1 1.076E-002 92.936 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
21 OR_NURSESTN_LOBBY_FLR_2 BLDG_OCC_EXTD_SCH OR_NURSESTN_LOBBY_FLR_2 1012.64 14.5 14.5 1.435E-002 69.703 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 15 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
22 PATROOM1_MULT10_FLR_3 BLDG_OCC_EXTD_SCH PATROOM1_MULT10_FLR_3 20.90 1.1 1.1 5.379E-002 18.591 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
23 PATROOM2_FLR_3 BLDG_OCC_EXTD_SCH PATROOM2_FLR_3 34.84 1.9 1.9 5.380E-002 18.587 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
24 PATROOM3_MULT10_FLR_3 BLDG_OCC_EXTD_SCH PATROOM3_MULT10_FLR_3 20.21 1.1 1.1 5.380E-002 18.586 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
25 PATROOM4_FLR_3 BLDG_OCC_EXTD_SCH PATROOM4_FLR_3 34.84 1.9 1.9 5.380E-002 18.587 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
26 PATROOM5_MULT10_FLR_3 BLDG_OCC_EXTD_SCH PATROOM5_MULT10_FLR_3 20.90 1.1 1.1 5.379E-002 18.591 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
27 PHYSTHERAPY_FLR_3 BLDG_OCC_SCH PHYSTHERAPY_FLR_3 487.74 26.2 26.2 5.380E-002 18.587 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 26 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
28 PATROOM6_FLR_3 BLDG_OCC_EXTD_SCH PATROOM6_FLR_3 27.87 1.5 1.5 5.380E-002 18.588 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
29 PATROOM7_MULT10_FLR_3 BLDG_OCC_EXTD_SCH PATROOM7_MULT10_FLR_3 20.21 1.1 1.1 5.380E-002 18.586 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
30 PATROOM8_FLR_3 BLDG_OCC_EXTD_SCH PATROOM8_FLR_3 27.87 1.5 1.5 5.380E-002 18.588 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
31 NURSESTN_LOBBY_FLR_3 BLDG_OCC_EXTD_SCH NURSESTN_LOBBY_FLR_3 905.80 13.0 13.0 1.435E-002 69.703 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
32 LAB_FLR_3 BLDG_OCC_SCH LAB_FLR_3 264.77 14.2 14.2 5.380E-002 18.588 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 14 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
33 CORRIDOR_SE_FLR_3 BLDG_OCC_EXTD_SCH CORRIDOR_SE_FLR_3 566.71 6.1 6.1 1.076E-002 92.937 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
34 CORRIDOR_NW_FLR_3 BLDG_OCC_EXTD_SCH CORRIDOR_NW_FLR_3 566.71 6.1 6.1 1.076E-002 92.937 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
35 PATROOM1_MULT10_FLR_4 BLDG_OCC_EXTD_SCH PATROOM1_MULT10_FLR_4 20.90 1.1 1.1 5.379E-002 18.591 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
36 PATROOM2_FLR_4 BLDG_OCC_EXTD_SCH PATROOM2_FLR_4 34.84 1.9 1.9 5.380E-002 18.587 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
37 PATROOM3_MULT10_FLR_4 BLDG_OCC_EXTD_SCH PATROOM3_MULT10_FLR_4 20.21 1.1 1.1 5.380E-002 18.586 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
38 PATROOM4_FLR_4 BLDG_OCC_EXTD_SCH PATROOM4_FLR_4 34.84 1.9 1.9 5.380E-002 18.587 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
39 PATROOM5_MULT10_FLR_4 BLDG_OCC_EXTD_SCH PATROOM5_MULT10_FLR_4 20.90 1.1 1.1 5.379E-002 18.591 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
40 RADIOLOGY_FLR_4 BLDG_OCC_SCH RADIOLOGY_FLR_4 487.74 26.2 26.2 5.380E-002 18.587 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 26 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
41 PATROOM6_FLR_4 BLDG_OCC_EXTD_SCH PATROOM6_FLR_4 27.87 1.5 1.5 5.380E-002 18.588 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
42 PATROOM7_MULT10_FLR_4 BLDG_OCC_EXTD_SCH PATROOM7_MULT10_FLR_4 20.21 1.1 1.1 5.380E-002 18.586 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
43 PATROOM8_FLR_4 BLDG_OCC_EXTD_SCH PATROOM8_FLR_4 27.87 1.5 1.5 5.380E-002 18.588 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
44 NURSESTN_LOBBY_FLR_4 BLDG_OCC_EXTD_SCH NURSESTN_LOBBY_FLR_4 905.80 13.0 13.0 1.435E-002 69.703 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
45 LAB_FLR_4 BLDG_OCC_SCH LAB_FLR_4 264.77 14.2 14.2 5.380E-002 18.588 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 14 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
46 CORRIDOR_SE_FLR_4 BLDG_OCC_EXTD_SCH CORRIDOR_SE_FLR_4 566.71 6.1 6.1 1.076E-002 92.937 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
47 CORRIDOR_NW_FLR_4 BLDG_OCC_EXTD_SCH CORRIDOR_NW_FLR_4 566.71 6.1 6.1 1.076E-002 92.937 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
48 DINING_FLR_5 BLDG_OCC_EXTD_SCH DINING_FLR_5 696.77 75.0 75.0 0.108 9.294 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 75 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
49 NURSESTN_LOBBY_FLR_5 BLDG_OCC_SCH NURSESTN_LOBBY_FLR_5 1040.51 14.9 14.9 1.435E-002 69.703 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 15 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
50 KITCHEN_FLR_5 BLDG_OCC_EXTD_SCH KITCHEN_FLR_5 929.03 50.0 50.0 5.380E-002 18.587 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 50 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
51 OFFICE1_FLR_5 BLDG_OCC_SCH OFFICE1_FLR_5 69.70 5.2 5.2 7.532E-002 13.276 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 5 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
52 OFFICE2_MULT5_FLR_5 BLDG_OCC_SCH OFFICE2_MULT5_FLR_5 69.68 5.2 5.2 7.532E-002 13.276 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 5 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
53 OFFICE3_FLR_5 BLDG_OCC_SCH OFFICE3_FLR_5 69.68 5.2 5.2 7.532E-002 13.276 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 5 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
54 OFFICE4_MULT6_FLR_5 BLDG_OCC_SCH OFFICE4_MULT6_FLR_5 13.94 1.1 1.1 7.535E-002 13.272 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 1 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
55 CORRIDOR_FLR_5 BLDG_OCC_EXTD_SCH CORRIDOR_FLR_5 501.68 5.4 5.4 1.076E-002 92.936 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 5 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS BLDG_LIGHT_OFFICE_BSMT_SCH BASEMENT 3739.35 100.6 25760.000 6.889 256.093 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 25760.000
2 ER_EXAM1_MULT4_FLR_1_LIGHTS BLDG_LIGHT_EXAM_SCH ER_EXAM1_MULT4_FLR_1 27.87 6.0 420.000 15.069 70.028 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 420.000
3 ER_TRAUMA1_FLR_1_LIGHTS BLDG_LIGHT_EXTD_SCH ER_TRAUMA1_FLR_1 27.87 6.0 420.000 15.069 70.028 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 420.000
4 ER_EXAM3_MULT4_FLR_1_LIGHTS BLDG_LIGHT_EXAM_SCH ER_EXAM3_MULT4_FLR_1 27.87 6.0 420.000 15.069 70.028 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 420.000
5 ER_TRAUMA2_FLR_1_LIGHTS BLDG_LIGHT_EXTD_SCH ER_TRAUMA2_FLR_1 27.87 6.0 420.000 15.069 70.028 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 420.000
6 ER_TRIAGE_MULT4_FLR_1_LIGHTS BLDG_LIGHT_EXTD_SCH ER_TRIAGE_MULT4_FLR_1 27.87 6.0 420.000 15.069 70.028 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 420.000
7 OFFICE1_MULT4_FLR_1_LIGHTS BLDG_LIGHT_OFFICE_SCH OFFICE1_MULT4_FLR_1 13.94 1.1 96.000 6.889 91.429 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 96.000
8 LOBBY_RECORDS_FLR_1_LIGHTS BLDG_LIGHT_LOBBYFLR1_SCH LOBBY_RECORDS_FLR_1 1474.81 21.2 12969.654 8.794 612.973 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 12969.654
9 CORRIDOR_FLR_1_LIGHTS BLDG_LIGHT_CORRIDOR_SCH CORRIDOR_FLR_1 569.03 6.1 4348.750 7.642 710.255 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4348.750
10 ER_NURSESTN_LOBBY_FLR_1_LIGHTS BLDG_LIGHT_NURSEFLR1_SCH ER_NURSESTN_LOBBY_FLR_1 1235.61 17.7 13805.400 11.173 778.783 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 13805.400
11 OR1_FLR_2_LIGHTS BLDG_LIGHT_SCH OR1_FLR_2 55.74 3.0 1356.000 24.326 452.181 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1356.000
12 OR2_MULT5_FLR_2_LIGHTS BLDG_LIGHT_SCH OR2_MULT5_FLR_2 55.74 3.0 1356.000 24.326 452.181 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1356.000
13 OR3_FLR_2_LIGHTS BLDG_LIGHT_SCH OR3_FLR_2 55.74 3.0 1356.000 24.326 452.181 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1356.000
14 OR4_FLR_2_LIGHTS BLDG_LIGHT_SCH OR4_FLR_2 222.97 12.0 5424.000 24.326 452.166 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 5424.000
15 IC_PATROOM1_MULT5_FLR_2_LIGHTS BLDG_LIGHT_EXTD_SCH IC_PATROOM1_MULT5_FLR_2 20.90 1.1 281.250 13.455 250.133 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 281.250
16 IC_PATROOM2_FLR_2_LIGHTS BLDG_LIGHT_EXTD_SCH IC_PATROOM2_FLR_2 27.87 1.5 375.000 13.455 250.100 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 375.000
17 IC_PATROOM3_MULT6_FLR_2_LIGHTS BLDG_LIGHT_EXTD_SCH IC_PATROOM3_MULT6_FLR_2 20.90 1.1 281.250 13.455 250.133 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 281.250
18 ICU_FLR_2_LIGHTS BLDG_LIGHT_EXTD_SCH ICU_FLR_2 617.96 33.2 8314.643 13.455 250.093 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 8314.643
19 ICU_NURSESTN_LOBBY_FLR_2_LIGHTS BLDG_LIGHT_EXTD_SCH ICU_NURSESTN_LOBBY_FLR_2 668.77 9.6 8422.311 12.594 877.818 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 8422.311
20 CORRIDOR_FLR_2_LIGHTS BLDG_LIGHT_CORRIDOR_SCH CORRIDOR_FLR_2 569.03 6.1 4348.750 7.642 710.255 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4348.750
21 OR_NURSESTN_LOBBY_FLR_2_LIGHTS BLDG_LIGHT_NURSEFLR234_SCH OR_NURSESTN_LOBBY_FLR_2 1012.64 14.5 10594.800 10.463 729.268 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 10594.800
22 PATROOM1_MULT10_FLR_3_LIGHTS BLDG_LIGHT_EXTD_SCH PATROOM1_MULT10_FLR_3 20.90 1.1 153.000 7.319 136.073 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 153.000
23 PATROOM2_FLR_3_LIGHTS BLDG_LIGHT_EXTD_SCH PATROOM2_FLR_3 34.84 1.9 255.000 7.319 136.044 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 255.000
24 PATROOM3_MULT10_FLR_3_LIGHTS BLDG_LIGHT_EXTD_SCH PATROOM3_MULT10_FLR_3 20.21 1.1 147.913 7.319 136.037 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 147.913
25 PATROOM4_FLR_3_LIGHTS BLDG_LIGHT_EXTD_SCH PATROOM4_FLR_3 34.84 1.9 255.000 7.319 136.044 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 255.000
26 PATROOM5_MULT10_FLR_3_LIGHTS BLDG_LIGHT_EXTD_SCH PATROOM5_MULT10_FLR_3 20.90 1.1 153.000 7.319 136.073 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 153.000
27 PHYSTHERAPY_FLR_3_LIGHTS BLDG_LIGHT_RADIOLOGY_SCH PHYSTHERAPY_FLR_3 487.74 26.2 4777.500 9.795 182.067 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4777.500
28 PATROOM6_FLR_3_LIGHTS BLDG_LIGHT_EXTD_SCH PATROOM6_FLR_3 27.87 1.5 204.000 7.319 136.054 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 204.000
29 PATROOM7_MULT10_FLR_3_LIGHTS BLDG_LIGHT_EXTD_SCH PATROOM7_MULT10_FLR_3 20.21 1.1 147.913 7.319 136.037 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 147.913
30 PATROOM8_FLR_3_LIGHTS BLDG_LIGHT_EXTD_SCH PATROOM8_FLR_3 27.87 1.5 204.000 7.319 136.054 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 204.000
31 NURSESTN_LOBBY_FLR_3_LIGHTS BLDG_LIGHT_NURSEFLR234_SCH NURSESTN_LOBBY_FLR_3 905.80 13.0 9477.000 10.463 729.269 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 9477.000
32 LAB_FLR_3_LIGHTS BLDG_LIGHT_SCH LAB_FLR_3 264.77 14.2 3790.500 14.316 266.101 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3790.500
33 CORRIDOR_SE_FLR_3_LIGHTS BLDG_LIGHT_CORRIDOR_SCH CORRIDOR_SE_FLR_3 566.71 6.1 4331.000 7.642 710.256 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4331.000
34 CORRIDOR_NW_FLR_3_LIGHTS BLDG_LIGHT_CORRIDOR_SCH CORRIDOR_NW_FLR_3 566.71 6.1 4331.000 7.642 710.256 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4331.000
35 PATROOM1_MULT10_FLR_4_LIGHTS BLDG_LIGHT_EXTD_SCH PATROOM1_MULT10_FLR_4 20.90 1.1 153.000 7.319 136.073 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 153.000
36 PATROOM2_FLR_4_LIGHTS BLDG_LIGHT_EXTD_SCH PATROOM2_FLR_4 34.84 1.9 255.000 7.319 136.044 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 255.000
37 PATROOM3_MULT10_FLR_4_LIGHTS BLDG_LIGHT_EXTD_SCH PATROOM3_MULT10_FLR_4 20.21 1.1 147.913 7.319 136.037 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 147.913
38 PATROOM4_FLR_4_LIGHTS BLDG_LIGHT_EXTD_SCH PATROOM4_FLR_4 34.84 1.9 255.000 7.319 136.044 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 255.000
39 PATROOM5_MULT10_FLR_4_LIGHTS BLDG_LIGHT_EXTD_SCH PATROOM5_MULT10_FLR_4 20.90 1.1 153.000 7.319 136.073 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 153.000
40 RADIOLOGY_FLR_4_LIGHTS BLDG_LIGHT_RADIOLOGY_SCH RADIOLOGY_FLR_4 487.74 26.2 4935.000 10.118 188.069 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4935.000
41 PATROOM6_FLR_4_LIGHTS BLDG_LIGHT_EXTD_SCH PATROOM6_FLR_4 27.87 1.5 204.000 7.319 136.054 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 204.000
42 PATROOM7_MULT10_FLR_4_LIGHTS BLDG_LIGHT_EXTD_SCH PATROOM7_MULT10_FLR_4 20.21 1.1 147.913 7.319 136.037 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 147.913
43 PATROOM8_FLR_4_LIGHTS BLDG_LIGHT_EXTD_SCH PATROOM8_FLR_4 27.87 1.5 204.000 7.319 136.054 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 204.000
44 NURSESTN_LOBBY_FLR_4_LIGHTS BLDG_LIGHT_NURSEFLR234_SCH NURSESTN_LOBBY_FLR_4 905.80 13.0 9477.000 10.463 729.269 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 9477.000
45 LAB_FLR_4_LIGHTS BLDG_LIGHT_SCH LAB_FLR_4 264.77 14.2 3790.500 14.316 266.101 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3790.500
46 CORRIDOR_SE_FLR_4_LIGHTS BLDG_LIGHT_CORRIDOR_SCH CORRIDOR_SE_FLR_4 566.71 6.1 4331.000 7.642 710.256 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4331.000
47 CORRIDOR_NW_FLR_4_LIGHTS BLDG_LIGHT_CORRIDOR_SCH CORRIDOR_NW_FLR_4 566.71 6.1 4331.000 7.642 710.256 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4331.000
48 DINING_FLR_5_LIGHTS BLDG_LIGHT_EXTD_SCH DINING_FLR_5 696.77 75.0 3000.000 4.306 40.015 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3000.000
49 NURSESTN_LOBBY_FLR_5_LIGHTS BLDG_LIGHT_LOBBYFLR5_SCH NURSESTN_LOBBY_FLR_5 1040.51 14.9 10886.400 10.463 729.265 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 10886.400
50 KITCHEN_FLR_5_LIGHTS BLDG_LIGHT_EXTD_SCH KITCHEN_FLR_5 929.03 50.0 10900.000 11.733 218.079 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 10900.000
51 OFFICE1_FLR_5_LIGHTS BLDG_LIGHT_OFFICE_SCH OFFICE1_FLR_5 69.70 5.2 480.126 6.889 91.456 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 480.126
52 OFFICE2_MULT5_FLR_5_LIGHTS BLDG_LIGHT_OFFICE_SCH OFFICE2_MULT5_FLR_5 69.68 5.2 480.000 6.889 91.458 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 480.000
53 OFFICE3_FLR_5_LIGHTS BLDG_LIGHT_OFFICE_SCH OFFICE3_FLR_5 69.68 5.2 480.000 6.889 91.458 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 480.000
54 OFFICE4_MULT6_FLR_5_LIGHTS BLDG_LIGHT_OFFICE_SCH OFFICE4_MULT6_FLR_5 13.94 1.1 96.000 6.889 91.429 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 96.000
55 CORRIDOR_FLR_5_LIGHTS BLDG_LIGHT_CORRIDOR_SCH CORRIDOR_FLR_5 501.68 5.4 3834.000 7.642 710.250 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 3834.000


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BLDG_EQUIP_SCH BASEMENT 3739.35 100.6 30176.533 8.070 300.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 30176.533
2 ER_EXAM1_MULT4_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH ER_EXAM1_MULT4_FLR_1 27.87 6.0 449.837 16.140 75.003 0.000 0.500 0.000 0.500 MiscPlug 0.000 449.837
3 ER_TRAUMA1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH ER_TRAUMA1_FLR_1 27.87 6.0 1199.564 43.040 200.007 0.000 0.500 0.000 0.500 MiscPlug 0.000 1199.564
4 ER_EXAM3_MULT4_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH ER_EXAM3_MULT4_FLR_1 27.87 6.0 449.837 16.140 75.003 0.000 0.500 0.000 0.500 MiscPlug 0.000 449.837
5 ER_TRAUMA2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH ER_TRAUMA2_FLR_1 27.87 6.0 1199.564 43.040 200.007 0.000 0.500 0.000 0.500 MiscPlug 0.000 1199.564
6 ER_TRIAGE_MULT4_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH ER_TRIAGE_MULT4_FLR_1 27.87 6.0 599.980 21.527 100.037 0.000 0.500 0.000 0.500 MiscPlug 0.000 599.980
7 OFFICE1_MULT4_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH OFFICE1_MULT4_FLR_1 13.94 1.1 164.996 11.840 157.139 0.000 0.500 0.000 0.500 MiscPlug 0.000 164.996
8 LOBBY_RECORDS_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_RECORDS_FLR_1 1474.81 21.2 1592.796 1.080 75.279 0.000 0.500 0.000 0.500 MiscPlug 0.000 1592.796
9 ER_NURSESTN_LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH ER_NURSESTN_LOBBY_FLR_1 1235.61 17.7 18076.981 14.630 1019.749 0.000 0.500 0.000 0.500 MiscPlug 0.000 18076.981
10 OR1_FLR_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH OR1_FLR_2 55.74 3.0 2399.128 43.040 800.029 0.000 0.500 0.000 0.500 MiscPlug 0.000 2399.128
11 OR2_MULT5_FLR_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH OR2_MULT5_FLR_2 55.74 3.0 2399.128 43.040 800.029 0.000 0.500 0.000 0.500 MiscPlug 0.000 2399.128
12 OR3_FLR_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH OR3_FLR_2 55.74 3.0 2399.128 43.040 800.029 0.000 0.500 0.000 0.500 MiscPlug 0.000 2399.128
13 OR4_FLR_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH OR4_FLR_2 222.97 12.0 9596.512 43.040 800.003 0.000 0.500 0.000 0.500 MiscPlug 0.000 9596.512
14 IC_PATROOM1_MULT5_FLR_2_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH IC_PATROOM1_MULT5_FLR_2 20.90 1.1 674.755 32.280 600.102 0.000 0.500 0.000 0.500 MiscPlug 0.000 674.755
15 IC_PATROOM2_FLR_2_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH IC_PATROOM2_FLR_2 27.87 1.5 899.673 32.280 600.022 0.000 0.500 0.000 0.500 MiscPlug 0.000 899.673
16 IC_PATROOM3_MULT6_FLR_2_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH IC_PATROOM3_MULT6_FLR_2 20.90 1.1 674.755 32.280 600.102 0.000 0.500 0.000 0.500 MiscPlug 0.000 674.755
17 ICU_FLR_2_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH ICU_FLR_2 617.96 33.2 19947.893 32.280 600.005 0.000 0.500 0.000 0.500 MiscPlug 0.000 19947.893
18 ICU_NURSESTN_LOBBY_FLR_2_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH ICU_NURSESTN_LOBBY_FLR_2 668.77 9.6 14391.883 21.520 1499.998 0.000 0.500 0.000 0.500 MiscPlug 0.000 14391.883
19 OR_NURSESTN_LOBBY_FLR_2_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH OR_NURSESTN_LOBBY_FLR_2 1012.64 14.5 11331.477 11.190 779.975 0.000 0.500 0.000 0.500 MiscPlug 0.000 11331.477
20 PATROOM1_MULT10_FLR_3_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH PATROOM1_MULT10_FLR_3 20.90 1.1 449.837 21.520 400.068 0.000 0.500 0.000 0.500 MiscPlug 0.000 449.837
21 PATROOM2_FLR_3_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH PATROOM2_FLR_3 34.84 1.9 749.728 21.520 399.983 0.000 0.500 0.000 0.500 MiscPlug 0.000 749.728
22 PATROOM3_MULT10_FLR_3_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH PATROOM3_MULT10_FLR_3 20.21 1.1 434.881 21.520 399.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 434.881
23 PATROOM4_FLR_3_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH PATROOM4_FLR_3 34.84 1.9 749.728 21.520 399.983 0.000 0.500 0.000 0.500 MiscPlug 0.000 749.728
24 PATROOM5_MULT10_FLR_3_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH PATROOM5_MULT10_FLR_3 20.90 1.1 449.837 21.520 400.068 0.000 0.500 0.000 0.500 MiscPlug 0.000 449.837
25 PHYSTHERAPY_FLR_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PHYSTHERAPY_FLR_3 487.74 26.2 7872.139 16.140 300.001 0.000 0.500 0.000 0.500 MiscPlug 0.000 7872.139
26 PATROOM6_FLR_3_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH PATROOM6_FLR_3 27.87 1.5 599.782 21.520 400.015 0.000 0.500 0.000 0.500 MiscPlug 0.000 599.782
27 PATROOM7_MULT10_FLR_3_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH PATROOM7_MULT10_FLR_3 20.21 1.1 434.881 21.520 399.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 434.881
28 PATROOM8_FLR_3_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH PATROOM8_FLR_3 27.87 1.5 599.782 21.520 400.015 0.000 0.500 0.000 0.500 MiscPlug 0.000 599.782
29 NURSESTN_LOBBY_FLR_3_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH NURSESTN_LOBBY_FLR_3 905.80 13.0 10135.954 11.190 779.977 0.000 0.500 0.000 0.500 MiscPlug 0.000 10135.954
30 LAB_FLR_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAB_FLR_3 264.77 14.2 11395.859 43.040 800.013 0.000 0.500 0.000 0.500 MiscPlug 0.000 11395.859
31 PATROOM1_MULT10_FLR_4_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH PATROOM1_MULT10_FLR_4 20.90 1.1 449.837 21.520 400.068 0.000 0.500 0.000 0.500 MiscPlug 0.000 449.837
32 PATROOM2_FLR_4_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH PATROOM2_FLR_4 34.84 1.9 749.728 21.520 399.983 0.000 0.500 0.000 0.500 MiscPlug 0.000 749.728
33 PATROOM3_MULT10_FLR_4_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH PATROOM3_MULT10_FLR_4 20.21 1.1 434.881 21.520 399.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 434.881
34 PATROOM4_FLR_4_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH PATROOM4_FLR_4 34.84 1.9 749.728 21.520 399.983 0.000 0.500 0.000 0.500 MiscPlug 0.000 749.728
35 PATROOM5_MULT10_FLR_4_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH PATROOM5_MULT10_FLR_4 20.90 1.1 449.837 21.520 400.068 0.000 0.500 0.000 0.500 MiscPlug 0.000 449.837
36 RADIOLOGY_FLR_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH RADIOLOGY_FLR_4 487.74 26.2 52499.895 107.639 2000.728 0.000 0.500 0.000 0.500 MiscPlug 0.000 52499.895
37 PATROOM6_FLR_4_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH PATROOM6_FLR_4 27.87 1.5 599.782 21.520 400.015 0.000 0.500 0.000 0.500 MiscPlug 0.000 599.782
38 PATROOM7_MULT10_FLR_4_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH PATROOM7_MULT10_FLR_4 20.21 1.1 434.881 21.520 399.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 434.881
39 PATROOM8_FLR_4_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH PATROOM8_FLR_4 27.87 1.5 599.782 21.520 400.015 0.000 0.500 0.000 0.500 MiscPlug 0.000 599.782
40 NURSESTN_LOBBY_FLR_4_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH NURSESTN_LOBBY_FLR_4 905.80 13.0 10135.954 11.190 779.977 0.000 0.500 0.000 0.500 MiscPlug 0.000 10135.954
41 LAB_FLR_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAB_FLR_4 264.77 14.2 11395.859 43.040 800.013 0.000 0.500 0.000 0.500 MiscPlug 0.000 11395.859
42 DINING_FLR_5_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH DINING_FLR_5 696.77 75.0 7497.275 10.760 100.000 0.000 0.500 0.000 0.500 MiscPlug 0.000 7497.275
43 NURSESTN_LOBBY_FLR_5_MISCPLUG_EQUIP BLDG_EQUIP_SCH NURSESTN_LOBBY_FLR_5 1040.51 14.9 11643.352 11.190 779.973 0.000 0.500 0.000 0.500 MiscPlug 0.000 11643.352
44 KITCHEN_FLR_5_MISCPLUG_EQUIP BLDG_EQUIP_EXTD_SCH KITCHEN_FLR_5 929.03 50.0 74972.753 80.700 1500.001 0.000 0.500 0.000 0.500 Cooking 0.000 74972.753
45 OFFICE1_FLR_5_MISCPLUG_EQUIP BLDG_EQUIP_SCH OFFICE1_FLR_5 69.70 5.2 749.924 10.760 142.848 0.000 0.500 0.000 0.500 MiscPlug 0.000 749.924
46 OFFICE2_MULT5_FLR_5_MISCPLUG_EQUIP BLDG_EQUIP_SCH OFFICE2_MULT5_FLR_5 69.68 5.2 749.728 10.760 142.851 0.000 0.500 0.000 0.500 MiscPlug 0.000 749.728
47 OFFICE3_FLR_5_MISCPLUG_EQUIP BLDG_EQUIP_SCH OFFICE3_FLR_5 69.68 5.2 749.728 10.760 142.851 0.000 0.500 0.000 0.500 MiscPlug 0.000 749.728
48 OFFICE4_MULT6_FLR_5_MISCPLUG_EQUIP BLDG_EQUIP_SCH OFFICE4_MULT6_FLR_5 13.94 1.1 149.946 10.760 142.805 0.000 0.500 0.000 0.500 MiscPlug 0.000 149.946
49 KITCHEN_FLR_5_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_5 929.03 50.0 555.000 0.597 11.104 0.000 0.250 0.000 0.750 ReachInFreezer 555.000 555.000
50 KITCHEN_FLR_5_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_5 929.03 50.0 470.000 0.506 9.403 0.000 0.250 0.000 0.750 ReachInRefrigerator 470.000 470.000


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 KITCHEN_FLR_5_MISCPLUGGAS_EQUIP BLDG_EQUIP_EXTD_SCH KITCHEN_FLR_5 929.03 50.0 149945.507 161.400 3000.002 0.000 0.500 0.000 0.500 Cooking 0.000 149945.507


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.761 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 AIR_WALL 4 1 1 0.167 4.809 0.900 0.900 0.700 0.700 Rough
5 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
6 EXT_SLAB_8IN_WITH_CARPET 9 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_FLOOR 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
8 INT_SLAB_CEILING 14 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
9 NONRES_ROOF 18 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
10 NONRES_EXT_WALL 21 3 9 0.167 0.9837 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL 22 3 9 0.167 0.7800 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_NORTH_CFACTOR 34 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_EAST_CFACTOR 35 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_SOUTH_CFACTOR 36 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
15 BASEMENT_WALL_WEST_CFACTOR 37 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.5677
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 AIR_WALL_MATERIAL 0.0000 0.000 0.000 0.000 0.2079
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
7 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
8 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
9 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
12 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
13 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
14 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
15 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
16 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
17 NONRES_EXTERIOR_WALL_INSULATION 0.0000 0.000 0.000 0.000 0.8493
18 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
19 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
20 RES_EXTERIOR_WALL_INSULATION 0.0000 0.000 0.000 0.000 1.115
21 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
22 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
23 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
24 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1010000 2.1010000 2.1010000  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.7613636 1.7613636 1.7613636  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 1 0.0000000 0.0000000 -0.0000000 -0.0000000
16 0 4.8088691 4.8088691 4.8088691  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
47 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
48 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
49 0 21.361010 0.87247630E-01 5.4456762  
50 9 0.31844121E-15 0.33891907E-16 -0.14717764E-09 -0.34085343E-17
51 8 0.21517510E-07 0.13210865E-12 0.37403321E-03 -0.24466149E-09
52 7 -0.12129356E-01 0.68855956E-08 -0.22924263E-01 0.13791520E-03
53 6 0.40230169 0.24029480E-05 0.46949424 -0.47118258E-02
54 5 -5.1608121 0.89965799E-04 -4.4213154 0.62814943E-01
55 4 32.871256 0.73775273E-03 21.362378 -0.42037561
56 3 -110.94624 0.16114037E-02 -55.469893 1.5111496
57 2 196.85374 0.90819125E-03 77.733479 -2.8963115
58 1 -171.06207 0.97128343E-04 -55.213590 2.7437919
59 0 57.057407 0.55402955E-06 15.565444  
60 9 -0.41768822E-14 0.27520919E-16 -0.15672466E-09 0.83927561E-16
61 8 0.22856702E-07 0.10578700E-12 0.38803401E-03 -0.25988854E-09
62 7 -0.12546900E-01 0.54357740E-08 -0.23525379E-01 0.14266284E-03
63 6 0.41364683 0.18861797E-05 0.47915075 -0.48455579E-02
64 5 -5.2715232 0.70271773E-04 -4.4954566 0.64187715E-01
65 4 33.360936 0.57369956E-03 21.652120 -0.42687724
66 3 -111.98802 0.12481219E-02 -56.042688 1.5262008
67 2 197.88617 0.70096321E-03 78.258916 -2.9127067
68 1 -171.44340 0.74721452E-04 -55.366563 2.7504751
69 0 57.057407 0.42462867E-06 15.540328  
70 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
71 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
72 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
73 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
74 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
75 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
76 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
77 0 1.0055995 0.48413807E-04 60.838472  
78 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
79 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
80 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
81 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
82 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
83 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
84 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
85 0 1.0055995 0.48413807E-04 60.838472  
86 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
87 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
88 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
89 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
90 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
91 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
92 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
93 0 1.0055995 0.48413807E-04 60.838472  
94 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
95 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
96 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
97 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
98 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
99 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
100 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
101 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.46_SHGC_0.25 30 1 VerySmooth 2.615 0.252 0.162 0.276
2 NONRESEASTWINDOW_U_0.46_SHGC_0.25 31 1 VerySmooth 2.615 0.252 0.162 0.276
3 RESWINDOW_U_0.46_SHGC_0.25 32 1 VerySmooth 2.615 0.252 0.162 0.276
4 RESEASTWINDOW_U_0.46_SHGC_0.25 33 1 VerySmooth 2.615 0.252 0.162 0.276


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 NONRES WINDOW GLAZING LAYER SpectralAverage   2.53892E-002 0.16139 0.61607 0.61607 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 0.12001 1.00000 No
2 NONRES EAST GLAZING LAYER SpectralAverage   2.53892E-002 0.16139 0.61607 0.61607 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 0.12001 1.00000 No
3 RES WINDOW GLAZING LAYER SpectralAverage   2.53892E-002 0.16139 0.61607 0.61607 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 0.12001 1.00000 No
4 RES EAST GLAZING LAYER SpectralAverage   2.53892E-002 0.16139 0.61607 0.61607 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 0.12001 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Calculation Method Value {days} Allowable Number Figures in Shadow Overlap {} Polygon Clipping Algorithm Sky Diffuse Modeling Algorithm External Shading Calculation Method Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 AverageOverDaysInFrequency 30 15000 SutherlandHodgman SimpleSkyDiffuseModeling InternalCalculation No No No


Zone/Window Adjacency Daylighting Counts

Zone Name Number of Exterior Windows Number of Exterior Windows in Adjacent Zones
1 LOBBY_RECORDS_FLR_1 1 0
2 DINING_FLR_5 1 0
3 OFFICE1_FLR_5 2 0
4 OFFICE2_MULT5_FLR_5 1 0
5 OFFICE3_FLR_5 2 0
6 OFFICE4_MULT6_FLR_5 1 0


Zone/Window Adjacency Daylighting Matrix

Zone Name Number of Adjacent Zones with Windows Adjacent Zone Names - 1st 100 (max)
1 LOBBY_RECORDS_FLR_1 0  
2 DINING_FLR_5 0  
3 OFFICE1_FLR_5 0  
4 OFFICE2_MULT5_FLR_5 0  
5 OFFICE3_FLR_5 0  
6 OFFICE4_MULT6_FLR_5 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Outdoors Air-Cooled 2.300
2 RACK2 1 0 Outdoors Air-Cooled 6.930


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH DISHWASHING BOOSTER 2.2712E-002 3000.0 1.676 1.5228
2 WaterHeater:Mixed SWH LAUNDRY 1.1356 87921.3 0.536 0.4981
3 WaterHeater:Mixed SHWSYS1 WATER HEATER 2.2712 175842.6 0.000 0.0000
4 WaterHeater:Mixed DUMMY WATER HEATER 1.8927E-002 0.0 0.000 0.0000


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 60.58 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 60.58 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 60.58 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 60.58 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 60.58 -999.00 0 No No
6 BASEMENT_CEILING 0 0.00 0.00 0.00 0 2.44 0.00 60.58 -999.00 0 No No
7 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 60.58 -999.00 0 No No
8 ER_EXAM1_MULT4_FLR_1_WALL_SOUTH 0 1014.74 182.89 21.34 0 4.27 6.10 5.23 0.00 0 No No
9 ER_EXAM1_MULT4_FLR_1_WALL_SOUTH_DOOR 0 1014.74 182.89 21.34 0 4.27 6.10 5.23 0.00 0 No No
10 ER_EXAM1_MULT4_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 6.10 5.23 0.00 0 No No
11 ER_EXAM1_MULT4_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 4.27 6.10 5.23 0.00 0 No No
12 ER_EXAM1_MULT4_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 4.27 6.10 5.23 0.00 0 No No
13 ER_EXAM1_MULT4_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.27 6.10 5.23 0.00 0 No No
14 ER_EXAM1_MULT4_FLR_1_CEILING 0 0.00 0.00 0.00 0 4.27 6.10 5.23 0.00 0 No No
15 ER_EXAM1_MULT4_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 6.10 5.23 0.00 0 No No
16 ER_TRAUMA1_FLR_1_WALL_EAST 0 564.63 218.86 21.34 0 4.27 10.67 5.23 0.00 0 No No
17 ER_TRAUMA1_FLR_1_WALL_EAST_DOOR 0 564.63 218.86 21.34 0 4.27 10.67 5.23 0.00 0 No No
18 ER_TRAUMA1_FLR_1_WALL_SOUTH 0 1014.74 182.89 21.34 0 4.27 10.67 5.23 0.00 0 No No
19 ER_TRAUMA1_FLR_1_WALL_SOUTH_DOOR 0 1014.74 182.89 21.34 0 4.27 10.67 5.23 0.00 0 No No
20 ER_TRAUMA1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.00 0 No No
21 ER_TRAUMA1_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.00 0 No No
22 ER_TRAUMA1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.00 0 No No
23 ER_TRAUMA1_FLR_1_CEILING 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.00 0 No No
24 ER_TRAUMA1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.00 0 No No
25 ER_EXAM3_MULT4_FLR_1_WALL_EAST 0 564.63 218.86 21.34 0 4.27 4.57 5.23 0.00 0 No No
26 ER_EXAM3_MULT4_FLR_1_WALL_EAST_DOOR 0 564.63 218.86 21.34 0 4.27 4.57 5.23 0.00 0 No No
27 ER_EXAM3_MULT4_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 4.57 5.23 0.00 0 No No
28 ER_EXAM3_MULT4_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 4.57 5.23 0.00 0 No No
29 ER_EXAM3_MULT4_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 4.27 4.57 5.23 0.00 0 No No
30 ER_EXAM3_MULT4_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.27 4.57 5.23 0.00 0 No No
31 ER_EXAM3_MULT4_FLR_1_CEILING 0 0.00 0.00 0.00 0 4.27 4.57 5.23 0.00 0 No No
32 ER_EXAM3_MULT4_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 4.57 5.23 0.00 0 No No
33 ER_TRAUMA2_FLR_1_WALL_NORTH 0 923.69 218.86 21.34 0 4.27 10.67 5.23 0.00 0 No No
34 ER_TRAUMA2_FLR_1_WALL_NORTH_DOOR 0 923.69 218.86 21.34 0 4.27 10.67 5.23 0.00 0 No No
35 ER_TRAUMA2_FLR_1_WALL_EAST 0 564.63 218.86 21.34 0 4.27 10.67 5.23 0.00 0 No No
36 ER_TRAUMA2_FLR_1_WALL_EAST_DOOR 0 564.63 218.86 21.34 0 4.27 10.67 5.23 0.00 0 No No
37 ER_TRAUMA2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.00 0 No No
38 ER_TRAUMA2_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.00 0 No No
39 ER_TRAUMA2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.00 0 No No
40 ER_TRAUMA2_FLR_1_CEILING 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.00 0 No No
41 ER_TRAUMA2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.00 0 No No
42 ER_TRIAGE_MULT4_FLR_1_WALL_NORTH 0 923.69 218.86 21.34 0 4.27 6.10 5.23 0.00 0 No No
43 ER_TRIAGE_MULT4_FLR_1_WALL_NORTH_DOOR 0 923.69 218.86 21.34 0 4.27 6.10 5.23 0.00 0 No No
44 ER_TRIAGE_MULT4_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 4.27 6.10 5.23 0.00 0 No No
45 ER_TRIAGE_MULT4_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 6.10 5.23 0.00 0 No No
46 ER_TRIAGE_MULT4_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 4.27 6.10 5.23 0.00 0 No No
47 ER_TRIAGE_MULT4_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.27 6.10 5.23 0.00 0 No No
48 ER_TRIAGE_MULT4_FLR_1_CEILING 0 0.00 0.00 0.00 0 4.27 6.10 5.23 0.00 0 No No
49 ER_TRIAGE_MULT4_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 6.10 5.23 0.00 0 No No
50 OFFICE1_MULT4_FLR_1_WALL_SOUTH 0 1014.74 182.89 21.34 0 4.27 3.05 3.66 0.23 4 No No
51 OFFICE1_MULT4_FLR_1_WALL_SOUTH_WINDOW 0 1014.74 182.89 21.34 0 4.27 3.05 3.66 0.23 1 No No
52 OFFICE1_MULT4_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 3.05 3.66 0.23 0 No No
53 OFFICE1_MULT4_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 4.27 3.05 3.66 0.23 0 No No
54 OFFICE1_MULT4_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 4.27 3.05 3.66 0.23 0 No No
55 OFFICE1_MULT4_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.27 3.05 3.66 0.23 0 No No
56 OFFICE1_MULT4_FLR_1_CEILING 0 0.00 0.00 0.00 0 4.27 3.05 3.66 0.23 0 No No
57 OFFICE1_MULT4_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 3.05 3.66 0.23 0 No No
58 LOBBY_RECORDS_FLR_1_WALL_NORTH 0 923.69 218.86 21.34 0 4.27 96.01 35.84 0.15 4 No No
59 LOBBY_RECORDS_FLR_1_WALL_NORTH_DOOR1 0 923.69 218.86 21.34 0 4.27 96.01 35.84 0.15 0 No No
60 LOBBY_RECORDS_FLR_1_WALL_NORTH_DOOR3 0 923.69 218.86 21.34 0 4.27 96.01 35.84 0.15 0 No No
61 LOBBY_RECORDS_FLR_1_WALL_NORTH_DOOR2 0 923.69 218.86 21.34 0 4.27 96.01 35.84 0.15 0 No No
62 LOBBY_RECORDS_FLR_1_WALL_1_WEST 0 571.16 149.36 21.34 0 4.27 96.01 35.84 0.15 4 No No
63 LOBBY_RECORDS_FLR_1_WALL_2_WEST 0 571.16 149.36 21.34 0 4.27 96.01 35.84 0.15 1 No No
64 LOBBY_RECORDS_FLR_1_WALL_1_SOUTH 0 1014.74 182.89 21.34 0 4.27 96.01 35.84 0.15 4 No No
65 LOBBY_RECORDS_FLR_1_WALL_1_SOUTH_DOOR 0 1014.74 182.89 21.34 0 4.27 96.01 35.84 0.15 0 No No
66 LOBBY_RECORDS_FLR_1_WALL_2_SOUTH 0 1014.74 182.89 21.34 0 4.27 96.01 35.84 0.15 4 No No
67 LOBBY_RECORDS_FLR_1_WALL_2_SOUTH_DOOR 0 1014.74 182.89 21.34 0 4.27 96.01 35.84 0.15 0 No No
68 LOBBY_RECORDS_FLR_1_WALL_2_SOUTH_ROLLDOOR 0 1014.74 182.89 21.34 0 4.27 96.01 35.84 0.15 0 No No
69 LOBBY_RECORDS_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 4.27 96.01 35.84 0.15 0 No No
70 LOBBY_RECORDS_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 4.27 96.01 35.84 0.15 0 No No
71 LOBBY_RECORDS_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 4.27 96.01 35.84 0.15 0 No No
72 LOBBY_RECORDS_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 4.27 96.01 35.84 0.15 0 No No
73 LOBBY_RECORDS_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 4.27 96.01 35.84 0.15 0 No No
74 LOBBY_RECORDS_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.27 96.01 35.84 0.15 0 No No
75 LOBBY_RECORDS_FLR_1_CEILING 0 0.00 0.00 0.00 0 4.27 96.01 35.84 0.15 0 No No
76 LOBBY_RECORDS_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 96.01 35.84 0.15 0 No No
77 CORRIDOR_FLR_1_WALL_1_WEST 0 0.00 0.00 0.00 0 4.27 21.34 17.78 0.00 0 No No
78 CORRIDOR_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 4.27 21.34 17.78 0.00 0 No No
79 CORRIDOR_FLR_1_WALL_NORTH 0 923.69 218.86 21.34 0 4.27 21.34 17.78 0.00 0 No No
80 CORRIDOR_FLR_1_WALL_NORTH_DOOR2 0 923.69 218.86 21.34 0 4.27 21.34 17.78 0.00 0 No No
81 CORRIDOR_FLR_1_WALL_NORTH_DOOR1 0 923.69 218.86 21.34 0 4.27 21.34 17.78 0.00 0 No No
82 CORRIDOR_FLR_1_WALL_SOUTH 0 1014.74 182.89 21.34 0 4.27 21.34 17.78 0.00 0 No No
83 CORRIDOR_FLR_1_WALL_SOUTH_DOOR2 0 1014.74 182.89 21.34 0 4.27 21.34 17.78 0.00 0 No No
84 CORRIDOR_FLR_1_WALL_SOUTH_DOOR1 0 1014.74 182.89 21.34 0 4.27 21.34 17.78 0.00 0 No No
85 CORRIDOR_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 4.27 21.34 17.78 0.00 0 No No
86 CORRIDOR_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.27 21.34 17.78 0.00 0 No No
87 CORRIDOR_FLR_1_CEILING 0 0.00 0.00 0.00 0 4.27 21.34 17.78 0.00 0 No No
88 CORRIDOR_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 21.34 17.78 0.00 0 No No
89 ER_NURSESTN_LOBBY_FLR_1_WALL_1_EAST 0 564.63 218.86 21.34 0 4.27 25.91 33.09 0.28 4 No No
90 ER_NURSESTN_LOBBY_FLR_1_WALL_1_EAST_WINDOW 0 564.63 218.86 21.34 0 4.27 25.91 33.09 0.28 1 No No
91 ER_NURSESTN_LOBBY_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 4.27 25.91 33.09 0.28 0 No No
92 ER_NURSESTN_LOBBY_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 4.27 25.91 33.09 0.28 0 No No
93 ER_NURSESTN_LOBBY_FLR_1_WALL_1_WEST 0 0.00 0.00 0.00 0 4.27 25.91 33.09 0.28 0 No No
94 ER_NURSESTN_LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 4.27 25.91 33.09 0.28 0 No No
95 ER_NURSESTN_LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 4.27 25.91 33.09 0.28 0 No No
96 ER_NURSESTN_LOBBY_FLR_1_WALL_1_SOUTH 0 0.00 0.00 0.00 0 4.27 25.91 33.09 0.28 0 No No
97 ER_NURSESTN_LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 4.27 25.91 33.09 0.28 0 No No
98 ER_NURSESTN_LOBBY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 4.27 25.91 33.09 0.28 0 No No
99 ER_NURSESTN_LOBBY_FLR_1_CEILING 0 0.00 0.00 0.00 0 4.27 25.91 33.09 0.28 0 No No
100 ER_NURSESTN_LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 25.91 33.09 0.28 0 No No
101 OR1_FLR_2_WALL_NORTH 0 923.69 218.86 21.34 0 4.27 15.24 7.32 0.00 0 No No
102 OR1_FLR_2_WALL_EAST 0 564.63 218.86 21.34 0 4.27 15.24 7.32 0.00 0 No No
103 OR1_FLR_2_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 15.24 7.32 0.00 0 No No
104 OR1_FLR_2_WALL_WEST 0 0.00 0.00 0.00 0 4.27 15.24 7.32 0.00 0 No No
105 OR1_FLR_2_FLOOR 0 0.00 0.00 0.00 0 4.27 15.24 7.32 0.00 0 No No
106 OR1_FLR_2_CEILING 0 0.00 0.00 0.00 0 4.27 15.24 7.32 0.00 0 No No
107 OR1_FLR_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 15.24 7.32 0.00 0 No No
108 OR2_MULT5_FLR_2_WALL_EAST 0 564.63 218.86 21.34 0 4.27 6.10 7.32 0.00 0 No No
109 OR2_MULT5_FLR_2_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 6.10 7.32 0.00 0 No No
110 OR2_MULT5_FLR_2_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 6.10 7.32 0.00 0 No No
111 OR2_MULT5_FLR_2_WALL_WEST 0 0.00 0.00 0.00 0 4.27 6.10 7.32 0.00 0 No No
112 OR2_MULT5_FLR_2_FLOOR 0 0.00 0.00 0.00 0 4.27 6.10 7.32 0.00 0 No No
113 OR2_MULT5_FLR_2_CEILING 0 0.00 0.00 0.00 0 4.27 6.10 7.32 0.00 0 No No
114 OR2_MULT5_FLR_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 6.10 7.32 0.00 0 No No
115 OR3_FLR_2_WALL_NORTH 0 923.69 218.86 21.34 0 4.27 9.14 7.32 0.00 0 No No
116 OR3_FLR_2_WALL_EAST 0 0.00 0.00 0.00 0 4.27 9.14 7.32 0.00 0 No No
117 OR3_FLR_2_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 9.14 7.32 0.00 0 No No
118 OR3_FLR_2_WALL_WEST 0 0.00 0.00 0.00 0 4.27 9.14 7.32 0.00 0 No No
119 OR3_FLR_2_FLOOR 0 0.00 0.00 0.00 0 4.27 9.14 7.32 0.00 0 No No
120 OR3_FLR_2_CEILING 0 0.00 0.00 0.00 0 4.27 9.14 7.32 0.00 0 No No
121 OR3_FLR_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 9.14 7.32 0.00 0 No No
122 OR4_FLR_2_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 0.00 13.30 -999.00 0 No No
123 OR4_FLR_2_WALL_EAST 0 0.00 0.00 0.00 0 4.27 0.00 13.30 -999.00 0 No No
124 OR4_FLR_2_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 0.00 13.30 -999.00 0 No No
125 OR4_FLR_2_WALL_WEST 0 0.00 0.00 0.00 0 4.27 0.00 13.30 -999.00 0 No No
126 OR4_FLR_2_FLOOR 0 0.00 0.00 0.00 0 4.27 0.00 13.30 -999.00 0 No No
127 OR4_FLR_2_CEILING 0 0.00 0.00 0.00 0 4.27 0.00 13.30 -999.00 0 No No
128 OR4_FLR_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 0.00 13.30 -999.00 0 No No
129 IC_PATROOM1_MULT5_FLR_2_WALL_NORTH 0 923.69 218.86 21.34 0 4.27 4.57 4.57 0.25 4 No No
130 IC_PATROOM1_MULT5_FLR_2_WALL_NORTH_WINDOW 0 923.69 218.86 21.34 0 4.27 4.57 4.57 0.25 1 No No
131 IC_PATROOM1_MULT5_FLR_2_WALL_WEST 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
132 IC_PATROOM1_MULT5_FLR_2_WALL_EAST 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
133 IC_PATROOM1_MULT5_FLR_2_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
134 IC_PATROOM1_MULT5_FLR_2_FLOOR 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
135 IC_PATROOM1_MULT5_FLR_2_CEILING 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
136 IC_PATROOM1_MULT5_FLR_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
137 IC_PATROOM2_FLR_2_WALL_NORTH 0 923.69 218.86 21.34 0 4.27 10.67 5.23 0.25 4 No No
138 IC_PATROOM2_FLR_2_WALL_NORTH_WINDOW 0 923.69 218.86 21.34 0 4.27 10.67 5.23 0.25 1 No No
139 IC_PATROOM2_FLR_2_WALL_WEST 0 571.16 149.36 21.34 0 4.27 10.67 5.23 0.25 4 No No
140 IC_PATROOM2_FLR_2_WALL_WEST_WINDOW 0 571.16 149.36 21.34 0 4.27 10.67 5.23 0.25 1 No No
141 IC_PATROOM2_FLR_2_WALL_EAST 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
142 IC_PATROOM2_FLR_2_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
143 IC_PATROOM2_FLR_2_FLOOR 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
144 IC_PATROOM2_FLR_2_CEILING 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
145 IC_PATROOM2_FLR_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
146 IC_PATROOM3_MULT6_FLR_2_WALL_WEST 0 571.16 149.36 21.34 0 4.27 4.57 4.57 0.25 4 No No
147 IC_PATROOM3_MULT6_FLR_2_WALL_WEST_WINDOW 0 571.16 149.36 21.34 0 4.27 4.57 4.57 0.25 1 No No
148 IC_PATROOM3_MULT6_FLR_2_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
149 IC_PATROOM3_MULT6_FLR_2_WALL_EAST 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
150 IC_PATROOM3_MULT6_FLR_2_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
151 IC_PATROOM3_MULT6_FLR_2_FLOOR 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
152 IC_PATROOM3_MULT6_FLR_2_CEILING 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
153 IC_PATROOM3_MULT6_FLR_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
154 ICU_FLR_2_WALL_SOUTH 0 1014.74 182.89 21.34 0 4.27 50.30 24.57 0.12 4 No No
155 ICU_FLR_2_WALL_WEST 0 571.16 149.36 21.34 0 4.27 50.30 24.57 0.12 4 No No
156 ICU_FLR_2_WALL_WEST_WINDOW 0 571.16 149.36 21.34 0 4.27 50.30 24.57 0.12 1 No No
157 ICU_FLR_2_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 50.30 24.57 0.12 0 No No
158 ICU_FLR_2_WALL_EAST 0 0.00 0.00 0.00 0 4.27 50.30 24.57 0.12 0 No No
159 ICU_FLR_2_FLOOR 0 0.00 0.00 0.00 0 4.27 50.30 24.57 0.12 0 No No
160 ICU_FLR_2_CEILING 0 0.00 0.00 0.00 0 4.27 50.30 24.57 0.12 0 No No
161 ICU_FLR_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 50.30 24.57 0.12 0 No No
162 ICU_NURSESTN_LOBBY_FLR_2_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 0.00 25.82 -999.00 0 No No
163 ICU_NURSESTN_LOBBY_FLR_2_WALL_WEST 0 0.00 0.00 0.00 0 4.27 0.00 25.82 -999.00 0 No No
164 ICU_NURSESTN_LOBBY_FLR_2_WALL_EAST 0 0.00 0.00 0.00 0 4.27 0.00 25.82 -999.00 0 No No
165 ICU_NURSESTN_LOBBY_FLR_2_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 0.00 25.82 -999.00 0 No No
166 ICU_NURSESTN_LOBBY_FLR_2_FLOOR 0 0.00 0.00 0.00 0 4.27 0.00 25.82 -999.00 0 No No
167 ICU_NURSESTN_LOBBY_FLR_2_CEILING 0 0.00 0.00 0.00 0 4.27 0.00 25.82 -999.00 0 No No
168 ICU_NURSESTN_LOBBY_FLR_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 0.00 25.82 -999.00 0 No No
169 CORRIDOR_FLR_2_WALL_NORTH 0 923.69 218.86 21.34 0 4.27 21.34 17.78 0.00 0 No No
170 CORRIDOR_FLR_2_WALL_SOUTH 0 1014.74 182.89 21.34 0 4.27 21.34 17.78 0.00 0 No No
171 CORRIDOR_FLR_2_WALL_EAST 0 0.00 0.00 0.00 0 4.27 21.34 17.78 0.00 0 No No
172 CORRIDOR_FLR_2_WALL_WEST 0 0.00 0.00 0.00 0 4.27 21.34 17.78 0.00 0 No No
173 CORRIDOR_FLR_2_FLOOR 0 0.00 0.00 0.00 0 4.27 21.34 17.78 0.00 0 No No
174 CORRIDOR_FLR_2_CEILING 0 0.00 0.00 0.00 0 4.27 21.34 17.78 0.00 0 No No
175 CORRIDOR_FLR_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 21.34 17.78 0.00 0 No No
176 OR_NURSESTN_LOBBY_FLR_2_WALL_1_NORTH 0 923.69 218.86 21.34 0 4.27 42.67 24.16 0.20 3 No No
177 OR_NURSESTN_LOBBY_FLR_2_WALL_SOUTH 0 1014.74 182.89 21.34 0 4.27 42.67 24.16 0.20 4 No No
178 OR_NURSESTN_LOBBY_FLR_2_WALL_SOUTH_WINDOW 0 1014.74 182.89 21.34 0 4.27 42.67 24.16 0.20 1 No No
179 OR_NURSESTN_LOBBY_FLR_2_WALL_2_NORTH 0 0.00 0.00 0.00 0 4.27 42.67 24.16 0.20 0 No No
180 OR_NURSESTN_LOBBY_FLR_2_WALL_3_NORTH 0 0.00 0.00 0.00 0 4.27 42.67 24.16 0.20 0 No No
181 OR_NURSESTN_LOBBY_FLR_2_WALL_1_WEST 0 0.00 0.00 0.00 0 4.27 42.67 24.16 0.20 0 No No
182 OR_NURSESTN_LOBBY_FLR_2_WALL_2_WEST 0 0.00 0.00 0.00 0 4.27 42.67 24.16 0.20 0 No No
183 OR_NURSESTN_LOBBY_FLR_2_WALL_1_EAST 0 0.00 0.00 0.00 0 4.27 42.67 24.16 0.20 0 No No
184 OR_NURSESTN_LOBBY_FLR_2_WALL_2_EAST 0 0.00 0.00 0.00 0 4.27 42.67 24.16 0.20 0 No No
185 OR_NURSESTN_LOBBY_FLR_2_FLOOR 0 0.00 0.00 0.00 0 4.27 42.67 24.16 0.20 0 No No
186 OR_NURSESTN_LOBBY_FLR_2_CEILING 0 0.00 0.00 0.00 0 4.27 42.67 24.16 0.20 0 No No
187 OR_NURSESTN_LOBBY_FLR_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 42.67 24.16 0.20 0 No No
188 PATROOM1_MULT10_FLR_3_WALL_SOUTH 0 1014.74 182.89 21.34 0 4.27 4.57 4.57 0.25 4 No No
189 PATROOM1_MULT10_FLR_3_WALL_SOUTH_WINDOW 0 1014.74 182.89 21.34 0 4.27 4.57 4.57 0.25 1 No No
190 PATROOM1_MULT10_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
191 PATROOM1_MULT10_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
192 PATROOM1_MULT10_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
193 PATROOM1_MULT10_FLR_3_FLOOR 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
194 PATROOM1_MULT10_FLR_3_CEILING 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
195 PATROOM1_MULT10_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
196 PATROOM2_FLR_3_WALL_EAST 0 564.63 218.86 21.34 0 4.27 12.19 5.72 0.25 4 No No
197 PATROOM2_FLR_3_WALL_EAST_WINDOW 0 564.63 218.86 21.34 0 4.27 12.19 5.72 0.25 1 No No
198 PATROOM2_FLR_3_WALL_SOUTH 0 1014.74 182.89 21.34 0 4.27 12.19 5.72 0.25 4 No No
199 PATROOM2_FLR_3_WALL_SOUTH_WINDOW 0 1014.74 182.89 21.34 0 4.27 12.19 5.72 0.25 1 No No
200 PATROOM2_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
201 PATROOM2_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
202 PATROOM2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
203 PATROOM2_FLR_3_CEILING 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
204 PATROOM2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
205 PATROOM3_MULT10_FLR_3_WALL_EAST 0 564.63 218.86 21.34 0 4.27 4.42 4.49 0.25 4 No No
206 PATROOM3_MULT10_FLR_3_WALL_EAST_WINDOW 0 564.63 218.86 21.34 0 4.27 4.42 4.49 0.25 1 No No
207 PATROOM3_MULT10_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
208 PATROOM3_MULT10_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
209 PATROOM3_MULT10_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
210 PATROOM3_MULT10_FLR_3_FLOOR 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
211 PATROOM3_MULT10_FLR_3_CEILING 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
212 PATROOM3_MULT10_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
213 PATROOM4_FLR_3_WALL_NORTH 0 923.69 218.86 21.34 0 4.27 12.19 5.72 0.25 4 No No
214 PATROOM4_FLR_3_WALL_NORTH_WINDOW 0 923.69 218.86 21.34 0 4.27 12.19 5.72 0.25 1 No No
215 PATROOM4_FLR_3_WALL_EAST 0 564.63 218.86 21.34 0 4.27 12.19 5.72 0.25 4 No No
216 PATROOM4_FLR_3_WALL_EAST_WINDOW 0 564.63 218.86 21.34 0 4.27 12.19 5.72 0.25 1 No No
217 PATROOM4_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
218 PATROOM4_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
219 PATROOM4_FLR_3_FLOOR 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
220 PATROOM4_FLR_3_CEILING 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
221 PATROOM4_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
222 PATROOM5_MULT10_FLR_3_WALL_NORTH 0 923.69 218.86 21.34 0 4.27 4.57 4.57 0.25 4 No No
223 PATROOM5_MULT10_FLR_3_WALL_NORTH_WINDOW 0 923.69 218.86 21.34 0 4.27 4.57 4.57 0.25 1 No No
224 PATROOM5_MULT10_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
225 PATROOM5_MULT10_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
226 PATROOM5_MULT10_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
227 PATROOM5_MULT10_FLR_3_FLOOR 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
228 PATROOM5_MULT10_FLR_3_CEILING 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
229 PATROOM5_MULT10_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
230 PHYSTHERAPY_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 0.00 22.07 -999.00 0 No No
231 PHYSTHERAPY_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 4.27 0.00 22.07 -999.00 0 No No
232 PHYSTHERAPY_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 0.00 22.07 -999.00 0 No No
233 PHYSTHERAPY_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 4.27 0.00 22.07 -999.00 0 No No
234 PHYSTHERAPY_FLR_3_FLOOR 0 0.00 0.00 0.00 0 4.27 0.00 22.07 -999.00 0 No No
235 PHYSTHERAPY_FLR_3_CEILING 0 0.00 0.00 0.00 0 4.27 0.00 22.07 -999.00 0 No No
236 PHYSTHERAPY_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 0.00 22.07 -999.00 0 No No
237 PATROOM6_FLR_3_WALL_SOUTH 0 1014.74 182.89 21.34 0 4.27 10.67 5.23 0.25 4 No No
238 PATROOM6_FLR_3_WALL_SOUTH_WINDOW 0 1014.74 182.89 21.34 0 4.27 10.67 5.23 0.25 1 No No
239 PATROOM6_FLR_3_WALL_WEST 0 571.16 149.36 21.34 0 4.27 10.67 5.23 0.25 4 No No
240 PATROOM6_FLR_3_WALL_WEST_WINDOW 0 571.16 149.36 21.34 0 4.27 10.67 5.23 0.25 1 No No
241 PATROOM6_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
242 PATROOM6_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
243 PATROOM6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
244 PATROOM6_FLR_3_CEILING 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
245 PATROOM6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
246 PATROOM7_MULT10_FLR_3_WALL_WEST 0 571.16 149.36 21.34 0 4.27 4.42 4.49 0.25 4 No No
247 PATROOM7_MULT10_FLR_3_WALL_WEST_WINDOW 0 571.16 149.36 21.34 0 4.27 4.42 4.49 0.25 1 No No
248 PATROOM7_MULT10_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
249 PATROOM7_MULT10_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
250 PATROOM7_MULT10_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
251 PATROOM7_MULT10_FLR_3_FLOOR 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
252 PATROOM7_MULT10_FLR_3_CEILING 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
253 PATROOM7_MULT10_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
254 PATROOM8_FLR_3_WALL_NORTH 0 923.69 218.86 21.34 0 4.27 10.67 5.23 0.25 4 No No
255 PATROOM8_FLR_3_WALL_NORTH_WINDOW 0 923.69 218.86 21.34 0 4.27 10.67 5.23 0.25 1 No No
256 PATROOM8_FLR_3_WALL_WEST 0 571.16 149.36 21.34 0 4.27 10.67 5.23 0.25 4 No No
257 PATROOM8_FLR_3_WALL_WEST_WINDOW 0 571.16 149.36 21.34 0 4.27 10.67 5.23 0.25 1 No No
258 PATROOM8_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
259 PATROOM8_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
260 PATROOM8_FLR_3_FLOOR 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
261 PATROOM8_FLR_3_CEILING 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
262 PATROOM8_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
263 NURSESTN_LOBBY_FLR_3_WALL_1_NORTH 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
264 NURSESTN_LOBBY_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
265 NURSESTN_LOBBY_FLR_3_WALL_2_NORTH 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
266 NURSESTN_LOBBY_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
267 NURSESTN_LOBBY_FLR_3_WALL_1_SOUTH 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
268 NURSESTN_LOBBY_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
269 NURSESTN_LOBBY_FLR_3_WALL_2_SOUTH 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
270 NURSESTN_LOBBY_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
271 NURSESTN_LOBBY_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
272 NURSESTN_LOBBY_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
273 NURSESTN_LOBBY_FLR_3_FLOOR 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
274 NURSESTN_LOBBY_FLR_3_CEILING 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
275 NURSESTN_LOBBY_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
276 LAB_FLR_3_WALL_1_NORTH 0 0.00 0.00 0.00 0 4.27 0.00 12.39 -999.00 0 No No
277 LAB_FLR_3_WALL_2_NORTH 0 0.00 0.00 0.00 0 4.27 0.00 12.39 -999.00 0 No No
278 LAB_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 4.27 0.00 12.39 -999.00 0 No No
279 LAB_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 4.27 0.00 12.39 -999.00 0 No No
280 LAB_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 0.00 12.39 -999.00 0 No No
281 LAB_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 4.27 0.00 12.39 -999.00 0 No No
282 LAB_FLR_3_FLOOR 0 0.00 0.00 0.00 0 4.27 0.00 12.39 -999.00 0 No No
283 LAB_FLR_3_CEILING 0 0.00 0.00 0.00 0 4.27 0.00 12.39 -999.00 0 No No
284 LAB_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 0.00 12.39 -999.00 0 No No
285 CORRIDOR_SE_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
286 CORRIDOR_SE_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
287 CORRIDOR_SE_FLR_3_WALL_1_NORTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
288 CORRIDOR_SE_FLR_3_WALL_2_NORTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
289 CORRIDOR_SE_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
290 CORRIDOR_SE_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
291 CORRIDOR_SE_FLR_3_WALL_1_SOUTH 0 1014.74 182.89 21.34 0 4.27 10.67 10.94 0.00 0 No No
292 CORRIDOR_SE_FLR_3_WALL_2_SOUTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
293 CORRIDOR_SE_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
294 CORRIDOR_SE_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
295 CORRIDOR_SE_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
296 CORRIDOR_SE_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
297 CORRIDOR_NW_FLR_3_WALL_1_SOUTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
298 CORRIDOR_SE_FLR_3_FLOOR 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
299 CORRIDOR_SE_FLR_3_CEILING 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
300 CORRIDOR_SE_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
301 CORRIDOR_NW_FLR_3_WALL_2_SOUTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
302 CORRIDOR_NW_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
303 CORRIDOR_NW_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
304 CORRIDOR_NW_FLR_3_WALL_1_NORTH 0 923.69 218.86 21.34 0 4.27 10.67 10.94 0.00 0 No No
305 CORRIDOR_NW_FLR_3_WALL_2_NORTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
306 CORRIDOR_NW_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
307 CORRIDOR_NW_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
308 CORRIDOR_NW_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
309 CORRIDOR_NW_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
310 CORRIDOR_NW_FLR_3_WALL_4_SOUTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
311 CORRIDOR_NW_FLR_3_WALL_5_SOUTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
312 CORRIDOR_NW_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
313 CORRIDOR_NW_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
314 CORRIDOR_NW_FLR_3_FLOOR 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
315 CORRIDOR_NW_FLR_3_CEILING 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
316 CORRIDOR_NW_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
317 PATROOM1_MULT10_FLR_4_WALL_SOUTH 0 1014.74 182.89 21.34 0 4.27 4.57 4.57 0.25 4 No No
318 PATROOM1_MULT10_FLR_4_WALL_SOUTH_WINDOW 0 1014.74 182.89 21.34 0 4.27 4.57 4.57 0.25 1 No No
319 PATROOM1_MULT10_FLR_4_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
320 PATROOM1_MULT10_FLR_4_WALL_EAST 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
321 PATROOM1_MULT10_FLR_4_WALL_WEST 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
322 PATROOM1_MULT10_FLR_4_FLOOR 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
323 PATROOM1_MULT10_FLR_4_CEILING 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
324 PATROOM1_MULT10_FLR_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
325 PATROOM2_FLR_4_WALL_EAST 0 564.63 218.86 21.34 0 4.27 12.19 5.72 0.25 4 No No
326 PATROOM2_FLR_4_WALL_EAST_WINDOW 0 564.63 218.86 21.34 0 4.27 12.19 5.72 0.25 1 No No
327 PATROOM2_FLR_4_WALL_SOUTH 0 1014.74 182.89 21.34 0 4.27 12.19 5.72 0.25 4 No No
328 PATROOM2_FLR_4_WALL_SOUTH_WINDOW 0 1014.74 182.89 21.34 0 4.27 12.19 5.72 0.25 1 No No
329 PATROOM2_FLR_4_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
330 PATROOM2_FLR_4_WALL_WEST 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
331 PATROOM2_FLR_4_FLOOR 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
332 PATROOM2_FLR_4_CEILING 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
333 PATROOM2_FLR_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
334 PATROOM3_MULT10_FLR_4_WALL_EAST 0 564.63 218.86 21.34 0 4.27 4.42 4.49 0.25 4 No No
335 PATROOM3_MULT10_FLR_4_WALL_EAST_WINDOW 0 564.63 218.86 21.34 0 4.27 4.42 4.49 0.25 1 No No
336 PATROOM3_MULT10_FLR_4_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
337 PATROOM3_MULT10_FLR_4_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
338 PATROOM3_MULT10_FLR_4_WALL_WEST 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
339 PATROOM3_MULT10_FLR_4_FLOOR 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
340 PATROOM3_MULT10_FLR_4_CEILING 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
341 PATROOM3_MULT10_FLR_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
342 PATROOM4_FLR_4_WALL_NORTH 0 923.69 218.86 21.34 0 4.27 12.19 5.72 0.25 4 No No
343 PATROOM4_FLR_4_WALL_NORTH_WINDOW 0 923.69 218.86 21.34 0 4.27 12.19 5.72 0.25 1 No No
344 PATROOM4_FLR_4_WALL_EAST 0 564.63 218.86 21.34 0 4.27 12.19 5.72 0.25 4 No No
345 PATROOM4_FLR_4_WALL_EAST_WINDOW 0 564.63 218.86 21.34 0 4.27 12.19 5.72 0.25 1 No No
346 PATROOM4_FLR_4_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
347 PATROOM4_FLR_4_WALL_WEST 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
348 PATROOM4_FLR_4_FLOOR 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
349 PATROOM4_FLR_4_CEILING 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
350 PATROOM4_FLR_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 12.19 5.72 0.25 0 No No
351 PATROOM5_MULT10_FLR_4_WALL_NORTH 0 923.69 218.86 21.34 0 4.27 4.57 4.57 0.25 4 No No
352 PATROOM5_MULT10_FLR_4_WALL_NORTH_WINDOW 0 923.69 218.86 21.34 0 4.27 4.57 4.57 0.25 1 No No
353 PATROOM5_MULT10_FLR_4_WALL_EAST 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
354 PATROOM5_MULT10_FLR_4_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
355 PATROOM5_MULT10_FLR_4_WALL_WEST 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
356 PATROOM5_MULT10_FLR_4_FLOOR 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
357 PATROOM5_MULT10_FLR_4_CEILING 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
358 PATROOM5_MULT10_FLR_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 4.57 4.57 0.25 0 No No
359 RADIOLOGY_FLR_4_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 0.00 22.07 -999.00 0 No No
360 RADIOLOGY_FLR_4_WALL_EAST 0 0.00 0.00 0.00 0 4.27 0.00 22.07 -999.00 0 No No
361 RADIOLOGY_FLR_4_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 0.00 22.07 -999.00 0 No No
362 RADIOLOGY_FLR_4_WALL_WEST 0 0.00 0.00 0.00 0 4.27 0.00 22.07 -999.00 0 No No
363 RADIOLOGY_FLR_4_FLOOR 0 0.00 0.00 0.00 0 4.27 0.00 22.07 -999.00 0 No No
364 RADIOLOGY_FLR_4_CEILING 0 0.00 0.00 0.00 0 4.27 0.00 22.07 -999.00 0 No No
365 RADIOLOGY_FLR_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 0.00 22.07 -999.00 0 No No
366 PATROOM6_FLR_4_WALL_SOUTH 0 1014.74 182.89 21.34 0 4.27 10.67 5.23 0.25 4 No No
367 PATROOM6_FLR_4_WALL_SOUTH_WINDOW 0 1014.74 182.89 21.34 0 4.27 10.67 5.23 0.25 1 No No
368 PATROOM6_FLR_4_WALL_WEST 0 571.16 149.36 21.34 0 4.27 10.67 5.23 0.25 4 No No
369 PATROOM6_FLR_4_WALL_WEST_WINDOW 0 571.16 149.36 21.34 0 4.27 10.67 5.23 0.25 1 No No
370 PATROOM6_FLR_4_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
371 PATROOM6_FLR_4_WALL_EAST 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
372 PATROOM6_FLR_4_FLOOR 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
373 PATROOM6_FLR_4_CEILING 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
374 PATROOM6_FLR_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
375 PATROOM7_MULT10_FLR_4_WALL_WEST 0 571.16 149.36 21.34 0 4.27 4.42 4.49 0.25 4 No No
376 PATROOM7_MULT10_FLR_4_WALL_WEST_WINDOW 0 571.16 149.36 21.34 0 4.27 4.42 4.49 0.25 1 No No
377 PATROOM7_MULT10_FLR_4_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
378 PATROOM7_MULT10_FLR_4_WALL_EAST 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
379 PATROOM7_MULT10_FLR_4_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
380 PATROOM7_MULT10_FLR_4_FLOOR 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
381 PATROOM7_MULT10_FLR_4_CEILING 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
382 PATROOM7_MULT10_FLR_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 4.42 4.49 0.25 0 No No
383 PATROOM8_FLR_4_WALL_NORTH 0 923.69 218.86 21.34 0 4.27 10.67 5.23 0.25 4 No No
384 PATROOM8_FLR_4_WALL_NORTH_WINDOW 0 923.69 218.86 21.34 0 4.27 10.67 5.23 0.25 1 No No
385 PATROOM8_FLR_4_WALL_WEST 0 571.16 149.36 21.34 0 4.27 10.67 5.23 0.25 4 No No
386 PATROOM8_FLR_4_WALL_WEST_WINDOW 0 571.16 149.36 21.34 0 4.27 10.67 5.23 0.25 1 No No
387 PATROOM8_FLR_4_WALL_EAST 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
388 PATROOM8_FLR_4_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
389 PATROOM8_FLR_4_FLOOR 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
390 PATROOM8_FLR_4_CEILING 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
391 PATROOM8_FLR_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 10.67 5.23 0.25 0 No No
392 NURSESTN_LOBBY_FLR_4_WALL_1_NORTH 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
393 NURSESTN_LOBBY_FLR_4_WALL_1_EAST 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
394 NURSESTN_LOBBY_FLR_4_WALL_2_NORTH 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
395 NURSESTN_LOBBY_FLR_4_WALL_2_EAST 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
396 NURSESTN_LOBBY_FLR_4_WALL_1_SOUTH 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
397 NURSESTN_LOBBY_FLR_4_WALL_1_WEST 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
398 NURSESTN_LOBBY_FLR_4_WALL_2_SOUTH 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
399 NURSESTN_LOBBY_FLR_4_WALL_3_SOUTH 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
400 NURSESTN_LOBBY_FLR_4_WALL_2_WEST 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
401 NURSESTN_LOBBY_FLR_4_WALL_3_WEST 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
402 NURSESTN_LOBBY_FLR_4_FLOOR 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
403 NURSESTN_LOBBY_FLR_4_CEILING 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
404 NURSESTN_LOBBY_FLR_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 0.00 21.61 -999.00 0 No No
405 LAB_FLR_4_WALL_1_NORTH 0 0.00 0.00 0.00 0 4.27 0.00 12.39 -999.00 0 No No
406 LAB_FLR_4_WALL_2_NORTH 0 0.00 0.00 0.00 0 4.27 0.00 12.39 -999.00 0 No No
407 LAB_FLR_4_WALL_1_EAST 0 0.00 0.00 0.00 0 4.27 0.00 12.39 -999.00 0 No No
408 LAB_FLR_4_WALL_2_EAST 0 0.00 0.00 0.00 0 4.27 0.00 12.39 -999.00 0 No No
409 LAB_FLR_4_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 0.00 12.39 -999.00 0 No No
410 LAB_FLR_4_WALL_WEST 0 0.00 0.00 0.00 0 4.27 0.00 12.39 -999.00 0 No No
411 LAB_FLR_4_FLOOR 0 0.00 0.00 0.00 0 4.27 0.00 12.39 -999.00 0 No No
412 LAB_FLR_4_CEILING 0 0.00 0.00 0.00 0 4.27 0.00 12.39 -999.00 0 No No
413 LAB_FLR_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 0.00 12.39 -999.00 0 No No
414 CORRIDOR_SE_FLR_4_WALL_1_WEST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
415 CORRIDOR_SE_FLR_4_WALL_2_WEST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
416 CORRIDOR_SE_FLR_4_WALL_1_NORTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
417 CORRIDOR_SE_FLR_4_WALL_2_NORTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
418 CORRIDOR_SE_FLR_4_WALL_1_EAST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
419 CORRIDOR_SE_FLR_4_WALL_2_EAST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
420 CORRIDOR_SE_FLR_4_WALL_1_SOUTH 0 1014.74 182.89 21.34 0 4.27 10.67 10.94 0.00 0 No No
421 CORRIDOR_SE_FLR_4_WALL_2_SOUTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
422 CORRIDOR_SE_FLR_4_WALL_3_SOUTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
423 CORRIDOR_SE_FLR_4_WALL_3_WEST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
424 CORRIDOR_SE_FLR_4_WALL_4_WEST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
425 CORRIDOR_SE_FLR_4_WALL_3_NORTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
426 CORRIDOR_NW_FLR_4_WALL_1_SOUTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
427 CORRIDOR_SE_FLR_4_FLOOR 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
428 CORRIDOR_SE_FLR_4_CEILING 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
429 CORRIDOR_SE_FLR_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
430 CORRIDOR_NW_FLR_4_WALL_2_SOUTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
431 CORRIDOR_NW_FLR_4_WALL_3_SOUTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
432 CORRIDOR_NW_FLR_4_WALL_1_EAST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
433 CORRIDOR_NW_FLR_4_WALL_1_NORTH 0 923.69 218.86 21.34 0 4.27 10.67 10.94 0.00 0 No No
434 CORRIDOR_NW_FLR_4_WALL_2_NORTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
435 CORRIDOR_NW_FLR_4_WALL_3_NORTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
436 CORRIDOR_NW_FLR_4_WALL_2_EAST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
437 CORRIDOR_NW_FLR_4_WALL_3_EAST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
438 CORRIDOR_NW_FLR_4_WALL_4_EAST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
439 CORRIDOR_NW_FLR_4_WALL_4_SOUTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
440 CORRIDOR_NW_FLR_4_WALL_5_SOUTH 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
441 CORRIDOR_NW_FLR_4_WALL_1_WEST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
442 CORRIDOR_NW_FLR_4_WALL_2_WEST 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
443 CORRIDOR_NW_FLR_4_FLOOR 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
444 CORRIDOR_NW_FLR_4_CEILING 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
445 CORRIDOR_NW_FLR_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 10.67 10.94 0.00 0 No No
446 DINING_FLR_5_WALL_EAST 0 564.63 218.86 21.34 0 4.27 53.34 26.13 0.16 3 No No
447 DINING_FLR_5_WALL_SOUTH 0 1014.74 182.89 21.34 0 4.27 53.34 26.13 0.16 4 No No
448 DINING_FLR_5_WALL_SOUTH_WINDOW 0 1014.74 182.89 21.34 0 4.27 53.34 26.13 0.16 1 No No
449 DINING_FLR_5_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 53.34 26.13 0.16 0 No No
450 DINING_FLR_5_WALL_WEST 0 0.00 0.00 0.00 0 4.27 53.34 26.13 0.16 0 No No
451 DINING_FLR_5_FLOOR 0 0.00 0.00 0.00 0 4.27 53.34 26.13 0.16 0 No No
452 DINING_FLR_5_CEILING 0 3390.98 203.61 0.00 0 4.27 53.34 26.13 0.16 0 No No
453 DINING_FLR_5_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 53.34 26.13 0.16 0 No No
454 NURSESTN_LOBBY_FLR_5_WALL_SOUTH 0 1014.74 182.89 21.34 0 4.27 24.38 31.03 0.00 0 No No
455 NURSESTN_LOBBY_FLR_5_WALL_1_EAST 0 0.00 0.00 0.00 0 4.27 24.38 31.03 0.00 0 No No
456 NURSESTN_LOBBY_FLR_5_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 24.38 31.03 0.00 0 No No
457 NURSESTN_LOBBY_FLR_5_WALL_2_EAST 0 0.00 0.00 0.00 0 4.27 24.38 31.03 0.00 0 No No
458 NURSESTN_LOBBY_FLR_5_WALL_WEST 0 0.00 0.00 0.00 0 4.27 24.38 31.03 0.00 0 No No
459 NURSESTN_LOBBY_FLR_5_FLOOR 0 0.00 0.00 0.00 0 4.27 24.38 31.03 0.00 0 No No
460 NURSESTN_LOBBY_FLR_5_CEILING 0 3390.98 203.61 0.00 0 4.27 24.38 31.03 0.00 0 No No
461 NURSESTN_LOBBY_FLR_5_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 24.38 31.03 0.00 0 No No
462 KITCHEN_FLR_5_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 60.96 30.48 0.00 0 No No
463 KITCHEN_FLR_5_WALL_1_WEST 0 0.00 0.00 0.00 0 4.27 60.96 30.48 0.00 0 No No
464 KITCHEN_FLR_5_WALL_NORTH 0 923.69 218.86 21.34 0 4.27 60.96 30.48 0.00 0 No No
465 KITCHEN_FLR_5_WALL_EAST 0 564.63 218.86 21.34 0 4.27 60.96 30.48 0.00 0 No No
466 KITCHEN_FLR_5_WALL_2_WEST 0 0.00 0.00 0.00 0 4.27 60.96 30.48 0.00 0 No No
467 KITCHEN_FLR_5_FLOOR 0 0.00 0.00 0.00 0 4.27 60.96 30.48 0.00 0 No No
468 KITCHEN_FLR_5_CEILING 0 3390.98 203.61 0.00 0 4.27 60.96 30.48 0.00 0 No No
469 KITCHEN_FLR_5_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 60.96 30.48 0.00 0 No No
470 OFFICE1_FLR_5_WALL_SOUTH 0 1014.74 182.89 21.34 0 4.27 16.77 8.31 0.25 4 No No
471 OFFICE1_FLR_5_WALL_SOUTH_WINDOW 0 1014.74 182.89 21.34 0 4.27 16.77 8.31 0.25 1 No No
472 OFFICE1_FLR_5_WALL_WEST 0 571.16 149.36 21.34 0 4.27 16.77 8.31 0.25 4 No No
473 OFFICE1_FLR_5_WALL_WEST_WINDOW 0 571.16 149.36 21.34 0 4.27 16.77 8.31 0.25 1 No No
474 OFFICE1_FLR_5_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 16.77 8.31 0.25 0 No No
475 OFFICE1_FLR_5_WALL_EAST 0 0.00 0.00 0.00 0 4.27 16.77 8.31 0.25 0 No No
476 OFFICE1_FLR_5_FLOOR 0 0.00 0.00 0.00 0 4.27 16.77 8.31 0.25 0 No No
477 OFFICE1_FLR_5_CEILING 0 3390.98 203.61 0.00 0 4.27 16.77 8.31 0.25 0 No No
478 OFFICE1_FLR_5_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 16.77 8.31 0.25 0 No No
479 OFFICE2_MULT5_FLR_5_WALL_WEST 0 571.16 149.36 21.34 0 4.27 7.62 8.31 0.25 4 No No
480 OFFICE2_MULT5_FLR_5_WALL_WEST_WINDOW 0 571.16 149.36 21.34 0 4.27 7.62 8.31 0.25 1 No No
481 OFFICE2_MULT5_FLR_5_WALL_NORTH 0 0.00 0.00 0.00 0 4.27 7.62 8.31 0.25 0 No No
482 OFFICE2_MULT5_FLR_5_WALL_EAST 0 0.00 0.00 0.00 0 4.27 7.62 8.31 0.25 0 No No
483 OFFICE2_MULT5_FLR_5_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 7.62 8.31 0.25 0 No No
484 OFFICE2_MULT5_FLR_5_FLOOR 0 0.00 0.00 0.00 0 4.27 7.62 8.31 0.25 0 No No
485 OFFICE2_MULT5_FLR_5_CEILING 0 3390.98 203.61 0.00 0 4.27 7.62 8.31 0.25 0 No No
486 OFFICE2_MULT5_FLR_5_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 7.62 8.31 0.25 0 No No
487 OFFICE3_FLR_5_WALL_NORTH 0 923.69 218.86 21.34 0 4.27 16.76 8.31 0.25 4 No No
488 OFFICE3_FLR_5_WALL_NORTH_WINDOW 0 923.69 218.86 21.34 0 4.27 16.76 8.31 0.25 1 No No
489 OFFICE3_FLR_5_WALL_WEST 0 571.16 149.36 21.34 0 4.27 16.76 8.31 0.25 4 No No
490 OFFICE3_FLR_5_WALL_WEST_WINDOW 0 571.16 149.36 21.34 0 4.27 16.76 8.31 0.25 1 No No
491 OFFICE3_FLR_5_WALL_EAST 0 0.00 0.00 0.00 0 4.27 16.76 8.31 0.25 0 No No
492 OFFICE3_FLR_5_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 16.76 8.31 0.25 0 No No
493 OFFICE3_FLR_5_FLOOR 0 0.00 0.00 0.00 0 4.27 16.76 8.31 0.25 0 No No
494 OFFICE3_FLR_5_CEILING 0 3390.98 203.61 0.00 0 4.27 16.76 8.31 0.25 0 No No
495 OFFICE3_FLR_5_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 16.76 8.31 0.25 0 No No
496 OFFICE4_MULT6_FLR_5_WALL_NORTH 0 923.69 218.86 21.34 0 4.27 3.05 3.66 0.23 4 No No
497 OFFICE4_MULT6_FLR_5_WALL_NORTH_WINDOW 0 923.69 218.86 21.34 0 4.27 3.05 3.66 0.23 1 No No
498 OFFICE4_MULT6_FLR_5_WALL_EAST 0 0.00 0.00 0.00 0 4.27 3.05 3.66 0.23 0 No No
499 OFFICE4_MULT6_FLR_5_WALL_SOUTH 0 0.00 0.00 0.00 0 4.27 3.05 3.66 0.23 0 No No
500 OFFICE4_MULT6_FLR_5_WALL_WEST 0 0.00 0.00 0.00 0 4.27 3.05 3.66 0.23 0 No No
501 OFFICE4_MULT6_FLR_5_FLOOR 0 0.00 0.00 0.00 0 4.27 3.05 3.66 0.23 0 No No
502 OFFICE4_MULT6_FLR_5_CEILING 0 3390.98 203.61 0.00 0 4.27 3.05 3.66 0.23 0 No No
503 OFFICE4_MULT6_FLR_5_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 3.05 3.66 0.23 0 No No
504 CORRIDOR_FLR_5_WALL_1_SOUTH 0 0.00 0.00 0.00 0 4.27 18.29 11.97 0.00 0 No No
505 CORRIDOR_FLR_5_WALL_1_EAST 0 0.00 0.00 0.00 0 4.27 18.29 11.97 0.00 0 No No
506 CORRIDOR_FLR_5_WALL_1_NORTH 0 923.69 218.86 21.34 0 4.27 18.29 11.97 0.00 0 No No
507 CORRIDOR_FLR_5_WALL_2_SOUTH 0 1014.74 182.89 21.34 0 4.27 18.29 11.97 0.00 0 No No
508 CORRIDOR_FLR_5_WALL_2_NORTH 0 0.00 0.00 0.00 0 4.27 18.29 11.97 0.00 0 No No
509 CORRIDOR_FLR_5_WALL_2_EAST 0 0.00 0.00 0.00 0 4.27 18.29 11.97 0.00 0 No No
510 CORRIDOR_FLR_5_WALL_1_WEST 0 0.00 0.00 0.00 0 4.27 18.29 11.97 0.00 0 No No
511 CORRIDOR_FLR_5_WALL_2_WEST 0 0.00 0.00 0.00 0 4.27 18.29 11.97 0.00 0 No No
512 CORRIDOR_FLR_5_FLOOR 0 0.00 0.00 0.00 0 4.27 18.29 11.97 0.00 0 No No
513 CORRIDOR_FLR_5_CEILING 0 3390.98 203.61 0.00 0 4.27 18.29 11.97 0.00 0 No No
514 CORRIDOR_FLR_5_INTERNALMASS_1 0 0.00 0.00 0.00 0 4.27 18.29 11.97 0.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 BASEMENT_INFILTRATION INFIL_SCH_PNNL BASEMENT 3739.35 100.6 0.000 0.000 N/A 0.000 0.000 0.000 0.224 0.000
2 ER_EXAM1_MULT4_FLR_1_INFILTRATION INFIL_SCH_PNNL ER_EXAM1_MULT4_FLR_1 27.87 6.0 1.591E-002 5.710E-004 5.690E-004 0.482 0.000 0.000 0.224 0.000
3 ER_TRAUMA1_FLR_1_INFILTRATION INFIL_SCH_PNNL ER_TRAUMA1_FLR_1 27.87 6.0 2.813E-002 1.009E-003 5.690E-004 0.851 0.000 0.000 0.224 0.000
4 ER_EXAM3_MULT4_FLR_1_INFILTRATION INFIL_SCH_PNNL ER_EXAM3_MULT4_FLR_1 27.87 6.0 1.221E-002 4.382E-004 5.690E-004 0.370 0.000 0.000 0.224 0.000
5 ER_TRAUMA2_FLR_1_INFILTRATION INFIL_SCH_PNNL ER_TRAUMA2_FLR_1 27.87 6.0 2.813E-002 1.009E-003 5.690E-004 0.851 0.000 0.000 0.224 0.000
6 ER_TRIAGE_MULT4_FLR_1_INFILTRATION INFIL_SCH_PNNL ER_TRIAGE_MULT4_FLR_1 27.87 6.0 1.591E-002 5.710E-004 5.690E-004 0.482 0.000 0.000 0.224 0.000
7 OFFICE1_MULT4_FLR_1_INFILTRATION INFIL_SCH_PNNL OFFICE1_MULT4_FLR_1 13.94 1.1 7.402E-003 5.312E-004 5.690E-004 0.448 0.000 0.000 0.224 0.000
8 LOBBY_RECORDS_FLR_1_INFILTRATION INFIL_SCH_PNNL LOBBY_RECORDS_FLR_1 1474.81 21.2 0.243 1.647E-004 5.690E-004 0.139 0.000 0.000 0.224 0.000
9 CORRIDOR_FLR_1_INFILTRATION INFIL_SCH_PNNL CORRIDOR_FLR_1 569.03 6.1 5.625E-002 9.886E-005 5.690E-004 8.338E-002 0.000 0.000 0.224 0.000
10 ER_NURSESTN_LOBBY_FLR_1_INFILTRATION INFIL_SCH_PNNL ER_NURSESTN_LOBBY_FLR_1 1235.61 17.7 6.292E-002 5.092E-005 5.690E-004 4.295E-002 0.000 0.000 0.224 0.000
11 OR1_FLR_2_INFILTRATION INFIL_SCH_PNNL OR1_FLR_2 55.74 3.0 3.701E-002 6.640E-004 5.690E-004 0.560 0.000 0.000 0.224 0.000
12 OR2_MULT5_FLR_2_INFILTRATION INFIL_SCH_PNNL OR2_MULT5_FLR_2 55.74 3.0 1.480E-002 2.656E-004 5.690E-004 0.224 0.000 0.000 0.224 0.000
13 OR3_FLR_2_INFILTRATION INFIL_SCH_PNNL OR3_FLR_2 55.74 3.0 2.221E-002 3.984E-004 5.690E-004 0.336 0.000 0.000 0.224 0.000
14 OR4_FLR_2_INFILTRATION INFIL_SCH_PNNL OR4_FLR_2 222.97 12.0 0.000 0.000 N/A 0.000 0.000 0.000 0.224 0.000
15 IC_PATROOM1_MULT5_FLR_2_INFILTRATION INFIL_SCH_PNNL IC_PATROOM1_MULT5_FLR_2 20.90 1.1 1.110E-002 5.312E-004 5.690E-004 0.448 0.000 0.000 0.224 0.000
16 IC_PATROOM2_FLR_2_INFILTRATION INFIL_SCH_PNNL IC_PATROOM2_FLR_2 27.87 1.5 2.591E-002 9.295E-004 5.690E-004 0.784 0.000 0.000 0.224 0.000
17 IC_PATROOM3_MULT6_FLR_2_INFILTRATION INFIL_SCH_PNNL IC_PATROOM3_MULT6_FLR_2 20.90 1.1 1.110E-002 5.312E-004 5.690E-004 0.448 0.000 0.000 0.224 0.000
18 ICU_FLR_2_INFILTRATION INFIL_SCH_PNNL ICU_FLR_2 617.96 33.2 0.122 1.977E-004 5.690E-004 0.167 0.000 0.000 0.224 0.000
19 ICU_NURSESTN_LOBBY_FLR_2_INFILTRATION INFIL_SCH_PNNL ICU_NURSESTN_LOBBY_FLR_2 668.77 9.6 0.000 0.000 N/A 0.000 0.000 0.000 0.224 0.000
20 CORRIDOR_FLR_2_INFILTRATION INFIL_SCH_PNNL CORRIDOR_FLR_2 569.03 6.1 5.181E-002 9.106E-005 5.690E-004 7.680E-002 0.000 0.000 0.224 0.000
21 OR_NURSESTN_LOBBY_FLR_2_INFILTRATION INFIL_SCH_PNNL OR_NURSESTN_LOBBY_FLR_2 1012.64 14.5 0.104 1.023E-004 5.690E-004 8.631E-002 0.000 0.000 0.224 0.000
22 PATROOM1_MULT10_FLR_3_INFILTRATION INFIL_SCH_PNNL PATROOM1_MULT10_FLR_3 20.90 1.1 1.110E-002 5.312E-004 5.690E-004 0.448 0.000 0.000 0.224 0.000
23 PATROOM2_FLR_3_INFILTRATION INFIL_SCH_PNNL PATROOM2_FLR_3 34.84 1.9 2.961E-002 8.499E-004 5.690E-004 0.717 0.000 0.000 0.224 0.000
24 PATROOM3_MULT10_FLR_3_INFILTRATION INFIL_SCH_PNNL PATROOM3_MULT10_FLR_3 20.21 1.1 1.073E-002 5.312E-004 5.690E-004 0.448 0.000 0.000 0.224 0.000
25 PATROOM4_FLR_3_INFILTRATION INFIL_SCH_PNNL PATROOM4_FLR_3 34.84 1.9 2.961E-002 8.499E-004 5.690E-004 0.717 0.000 0.000 0.224 0.000
26 PATROOM5_MULT10_FLR_3_INFILTRATION INFIL_SCH_PNNL PATROOM5_MULT10_FLR_3 20.90 1.1 1.110E-002 5.312E-004 5.690E-004 0.448 0.000 0.000 0.224 0.000
27 PHYSTHERAPY_FLR_3_INFILTRATION INFIL_SCH_PNNL PHYSTHERAPY_FLR_3 487.74 26.2 0.000 0.000 N/A 0.000 0.000 0.000 0.224 0.000
28 PATROOM6_FLR_3_INFILTRATION INFIL_SCH_PNNL PATROOM6_FLR_3 27.87 1.5 2.591E-002 9.295E-004 5.690E-004 0.784 0.000 0.000 0.224 0.000
29 PATROOM7_MULT10_FLR_3_INFILTRATION INFIL_SCH_PNNL PATROOM7_MULT10_FLR_3 20.21 1.1 1.073E-002 5.312E-004 5.690E-004 0.448 0.000 0.000 0.224 0.000
30 PATROOM8_FLR_3_INFILTRATION INFIL_SCH_PNNL PATROOM8_FLR_3 27.87 1.5 2.591E-002 9.295E-004 5.690E-004 0.784 0.000 0.000 0.224 0.000
31 NURSESTN_LOBBY_FLR_3_INFILTRATION INFIL_SCH_PNNL NURSESTN_LOBBY_FLR_3 905.80 13.0 0.000 0.000 N/A 0.000 0.000 0.000 0.224 0.000
32 LAB_FLR_3_INFILTRATION INFIL_SCH_PNNL LAB_FLR_3 264.77 14.2 0.000 0.000 N/A 0.000 0.000 0.000 0.224 0.000
33 CORRIDOR_SE_FLR_3_INFILTRATION INFIL_SCH_PNNL CORRIDOR_SE_FLR_3 566.71 6.1 2.591E-002 4.572E-005 5.690E-004 3.856E-002 0.000 0.000 0.224 0.000
34 CORRIDOR_NW_FLR_3_INFILTRATION INFIL_SCH_PNNL CORRIDOR_NW_FLR_3 566.71 6.1 2.591E-002 4.572E-005 5.690E-004 3.856E-002 0.000 0.000 0.224 0.000
35 PATROOM1_MULT10_FLR_4_INFILTRATION INFIL_SCH_PNNL PATROOM1_MULT10_FLR_4 20.90 1.1 1.110E-002 5.312E-004 5.690E-004 0.448 0.000 0.000 0.224 0.000
36 PATROOM2_FLR_4_INFILTRATION INFIL_SCH_PNNL PATROOM2_FLR_4 34.84 1.9 2.961E-002 8.499E-004 5.690E-004 0.717 0.000 0.000 0.224 0.000
37 PATROOM3_MULT10_FLR_4_INFILTRATION INFIL_SCH_PNNL PATROOM3_MULT10_FLR_4 20.21 1.1 1.073E-002 5.312E-004 5.690E-004 0.448 0.000 0.000 0.224 0.000
38 PATROOM4_FLR_4_INFILTRATION INFIL_SCH_PNNL PATROOM4_FLR_4 34.84 1.9 2.961E-002 8.499E-004 5.690E-004 0.717 0.000 0.000 0.224 0.000
39 PATROOM5_MULT10_FLR_4_INFILTRATION INFIL_SCH_PNNL PATROOM5_MULT10_FLR_4 20.90 1.1 1.110E-002 5.312E-004 5.690E-004 0.448 0.000 0.000 0.224 0.000
40 RADIOLOGY_FLR_4_INFILTRATION INFIL_SCH_PNNL RADIOLOGY_FLR_4 487.74 26.2 0.000 0.000 N/A 0.000 0.000 0.000 0.224 0.000
41 PATROOM6_FLR_4_INFILTRATION INFIL_SCH_PNNL PATROOM6_FLR_4 27.87 1.5 2.591E-002 9.295E-004 5.690E-004 0.784 0.000 0.000 0.224 0.000
42 PATROOM7_MULT10_FLR_4_INFILTRATION INFIL_SCH_PNNL PATROOM7_MULT10_FLR_4 20.21 1.1 1.073E-002 5.312E-004 5.690E-004 0.448 0.000 0.000 0.224 0.000
43 PATROOM8_FLR_4_INFILTRATION INFIL_SCH_PNNL PATROOM8_FLR_4 27.87 1.5 2.591E-002 9.295E-004 5.690E-004 0.784 0.000 0.000 0.224 0.000
44 NURSESTN_LOBBY_FLR_4_INFILTRATION INFIL_SCH_PNNL NURSESTN_LOBBY_FLR_4 905.80 13.0 0.000 0.000 N/A 0.000 0.000 0.000 0.224 0.000
45 LAB_FLR_4_INFILTRATION INFIL_SCH_PNNL LAB_FLR_4 264.77 14.2 0.000 0.000 N/A 0.000 0.000 0.000 0.224 0.000
46 CORRIDOR_SE_FLR_4_INFILTRATION INFIL_SCH_PNNL CORRIDOR_SE_FLR_4 566.71 6.1 2.591E-002 4.572E-005 5.690E-004 3.856E-002 0.000 0.000 0.224 0.000
47 CORRIDOR_NW_FLR_4_INFILTRATION INFIL_SCH_PNNL CORRIDOR_NW_FLR_4 566.71 6.1 2.591E-002 4.572E-005 5.690E-004 3.856E-002 0.000 0.000 0.224 0.000
48 DINING_FLR_5_INFILTRATION INFIL_SCH_PNNL DINING_FLR_5 696.77 75.0 0.130 1.859E-004 1.401E-004 0.157 0.000 0.000 0.224 0.000
49 NURSESTN_LOBBY_FLR_5_INFILTRATION INFIL_SCH_PNNL NURSESTN_LOBBY_FLR_5 1040.51 14.9 5.920E-002 5.689E-005 5.172E-005 4.798E-002 0.000 0.000 0.224 0.000
50 KITCHEN_FLR_5_INFILTRATION INFIL_SCH_PNNL KITCHEN_FLR_5 929.03 50.0 0.148 1.594E-004 1.245E-004 0.134 0.000 0.000 0.224 0.000
51 OFFICE1_FLR_5_INFILTRATION INFIL_SCH_PNNL OFFICE1_FLR_5 69.70 5.2 4.072E-002 5.842E-004 2.882E-004 0.493 0.000 0.000 0.224 0.000
52 OFFICE2_MULT5_FLR_5_INFILTRATION INFIL_SCH_PNNL OFFICE2_MULT5_FLR_5 69.68 5.2 1.850E-002 2.655E-004 1.810E-004 0.224 0.000 0.000 0.224 0.000
53 OFFICE3_FLR_5_INFILTRATION INFIL_SCH_PNNL OFFICE3_FLR_5 69.68 5.2 4.071E-002 5.842E-004 2.882E-004 0.493 0.000 0.000 0.224 0.000
54 OFFICE4_MULT6_FLR_5_INFILTRATION INFIL_SCH_PNNL OFFICE4_MULT6_FLR_5 13.94 1.1 7.400E-003 5.310E-004 2.746E-004 0.448 0.000 0.000 0.224 0.000
55 CORRIDOR_FLR_5_INFILTRATION INFIL_SCH_PNNL CORRIDOR_FLR_5 501.68 5.4 4.440E-002 8.850E-005 7.658E-005 7.464E-002 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 ER_EXAM1_MULT4_FLR_1 Mixing/Well-Stirred
3 ER_TRAUMA1_FLR_1 Mixing/Well-Stirred
4 ER_EXAM3_MULT4_FLR_1 Mixing/Well-Stirred
5 ER_TRAUMA2_FLR_1 Mixing/Well-Stirred
6 ER_TRIAGE_MULT4_FLR_1 Mixing/Well-Stirred
7 OFFICE1_MULT4_FLR_1 Mixing/Well-Stirred
8 LOBBY_RECORDS_FLR_1 Mixing/Well-Stirred
9 CORRIDOR_FLR_1 Mixing/Well-Stirred
10 ER_NURSESTN_LOBBY_FLR_1 Mixing/Well-Stirred
11 OR1_FLR_2 Mixing/Well-Stirred
12 OR2_MULT5_FLR_2 Mixing/Well-Stirred
13 OR3_FLR_2 Mixing/Well-Stirred
14 OR4_FLR_2 Mixing/Well-Stirred
15 IC_PATROOM1_MULT5_FLR_2 Mixing/Well-Stirred
16 IC_PATROOM2_FLR_2 Mixing/Well-Stirred
17 IC_PATROOM3_MULT6_FLR_2 Mixing/Well-Stirred
18 ICU_FLR_2 Mixing/Well-Stirred
19 ICU_NURSESTN_LOBBY_FLR_2 Mixing/Well-Stirred
20 CORRIDOR_FLR_2 Mixing/Well-Stirred
21 OR_NURSESTN_LOBBY_FLR_2 Mixing/Well-Stirred
22 PATROOM1_MULT10_FLR_3 Mixing/Well-Stirred
23 PATROOM2_FLR_3 Mixing/Well-Stirred
24 PATROOM3_MULT10_FLR_3 Mixing/Well-Stirred
25 PATROOM4_FLR_3 Mixing/Well-Stirred
26 PATROOM5_MULT10_FLR_3 Mixing/Well-Stirred
27 PHYSTHERAPY_FLR_3 Mixing/Well-Stirred
28 PATROOM6_FLR_3 Mixing/Well-Stirred
29 PATROOM7_MULT10_FLR_3 Mixing/Well-Stirred
30 PATROOM8_FLR_3 Mixing/Well-Stirred
31 NURSESTN_LOBBY_FLR_3 Mixing/Well-Stirred
32 LAB_FLR_3 Mixing/Well-Stirred
33 CORRIDOR_SE_FLR_3 Mixing/Well-Stirred
34 CORRIDOR_NW_FLR_3 Mixing/Well-Stirred
35 PATROOM1_MULT10_FLR_4 Mixing/Well-Stirred
36 PATROOM2_FLR_4 Mixing/Well-Stirred
37 PATROOM3_MULT10_FLR_4 Mixing/Well-Stirred
38 PATROOM4_FLR_4 Mixing/Well-Stirred
39 PATROOM5_MULT10_FLR_4 Mixing/Well-Stirred
40 RADIOLOGY_FLR_4 Mixing/Well-Stirred
41 PATROOM6_FLR_4 Mixing/Well-Stirred
42 PATROOM7_MULT10_FLR_4 Mixing/Well-Stirred
43 PATROOM8_FLR_4 Mixing/Well-Stirred
44 NURSESTN_LOBBY_FLR_4 Mixing/Well-Stirred
45 LAB_FLR_4 Mixing/Well-Stirred
46 CORRIDOR_SE_FLR_4 Mixing/Well-Stirred
47 CORRIDOR_NW_FLR_4 Mixing/Well-Stirred
48 DINING_FLR_5 Mixing/Well-Stirred
49 NURSESTN_LOBBY_FLR_5 Mixing/Well-Stirred
50 KITCHEN_FLR_5 Mixing/Well-Stirred
51 OFFICE1_FLR_5 Mixing/Well-Stirred
52 OFFICE2_MULT5_FLR_5 Mixing/Well-Stirred
53 OFFICE3_FLR_5 Mixing/Well-Stirred
54 OFFICE4_MULT6_FLR_5 Mixing/Well-Stirred
55 CORRIDOR_FLR_5 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 64254.36159 64254.36159 5.14215 5.14215 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 24:00:00 29.89400 5.57865E-003 3739.34736 100.58850 1.37712 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.37712 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50000 4.31558E-003 3739.34736 100.58850 1.37712 0.00000
3 ER_EXAM1_MULT4_FLR_1 Cooling 6872.46120 6872.46120 0.55010 1.58553 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 39.47000 5.57864E-003 27.87091 5.99760 0.26424 0.00000
4 ER_EXAM1_MULT4_FLR_1 Heating 1954.47435 1954.47435 9.22782E-002 0.26424 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 27.87091 5.99760 0.26424 0.00000
5 ER_TRAUMA1_FLR_1 Cooling 2643.12654 2643.12654 0.21156 0.39638 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 37.82967 5.57864E-003 27.87091 5.99760 6.60602E-002 0.00000
6 ER_TRAUMA1_FLR_1 Heating 840.52622 840.52622 3.96843E-002 6.60602E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 27.87091 5.99760 6.60602E-002 0.00000
7 ER_EXAM3_MULT4_FLR_1 Cooling 6006.88173 6006.88173 0.48082 1.58553 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 36.61050 5.57864E-003 27.87091 5.99760 0.26424 0.00000
8 ER_EXAM3_MULT4_FLR_1 Heating 1504.73464 1504.73464 7.10444E-002 0.26424 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 27.87091 5.99760 0.26424 0.00000
9 ER_TRAUMA2_FLR_1 Cooling 2642.67061 2642.67061 0.21153 0.39638 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 36.27800 5.57864E-003 27.87091 5.99760 6.60602E-002 0.00000
10 ER_TRAUMA2_FLR_1 Heating 842.01485 842.01485 3.97546E-002 6.60602E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 27.87091 5.99760 6.60602E-002 0.00000
11 ER_TRIAGE_MULT4_FLR_1 Cooling 7430.45273 7430.45273 0.59477 1.58553 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 35.94550 5.57865E-003 27.87091 5.99760 0.26424 0.00000
12 ER_TRIAGE_MULT4_FLR_1 Heating 1959.70945 1959.70945 9.25254E-002 0.26424 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 27.87091 5.99760 0.26424 0.00000
13 OFFICE1_MULT4_FLR_1 Cooling 3998.76330 3998.76330 0.32002 0.32002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 36.07850 5.57864E-003 13.93546 1.05000 3.36242E-002 0.00000
14 OFFICE1_MULT4_FLR_1 Heating 1571.42142 1571.42142 7.41929E-002 7.41929E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 13.93546 1.05000 3.36242E-002 0.00000
15 LOBBY_RECORDS_FLR_1 Cooling 21864.72387 21864.72387 1.74971 1.74971 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 39.47000 5.57864E-003 1474.81061 21.15860 0.49944 0.00000
16 LOBBY_RECORDS_FLR_1 Heating 9192.48052 9192.48052 0.43401 0.49944 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 1474.81061 21.15860 0.49944 0.00000
17 CORRIDOR_FLR_1 Cooling 6513.60249 6513.60249 0.52124 0.52124 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 37.27550 5.57864E-003 569.03112 6.12280 0.17343 0.00000
18 CORRIDOR_FLR_1 Heating 1917.80047 1917.80047 9.05471E-002 0.17343 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 569.03112 6.12280 0.17343 0.00000
19 ER_NURSESTN_LOBBY_FLR_1 Cooling 35130.77316 35130.77316 2.81131 2.81131 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 40.00200 5.57864E-003 1235.61043 17.72690 0.41843 0.00000
20 ER_NURSESTN_LOBBY_FLR_1 Heating 2872.26464 2872.26464 0.13561 0.41843 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 1235.61043 17.72690 0.41843 0.00000
21 OR1_FLR_2 Cooling 4789.24175 4789.24175 0.38327 0.99092 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 32.95300 5.57864E-003 55.74182 2.99880 0.19817 0.00000
22 OR1_FLR_2 Heating 1157.30505 1157.30505 5.46406E-002 0.19817 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 55.74182 2.99880 0.19817 0.00000
23 OR2_MULT5_FLR_2 Cooling 21020.40373 21020.40373 1.68222 4.95458 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 32.95300 5.57864E-003 55.74182 2.99880 0.99086 0.00000
24 OR2_MULT5_FLR_2 Heating 2378.65112 2378.65112 0.11231 0.99086 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 55.74182 2.99880 0.99086 0.00000
25 OR3_FLR_2 Cooling 4557.40401 4557.40401 0.36472 0.99092 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 21:10:00 32.75350 5.57864E-003 55.74182 2.99880 0.19817 0.00000
26 OR3_FLR_2 Heating 707.96084 707.96084 3.34255E-002 0.19817 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 55.74182 2.99880 0.19817 0.00000
27 OR4_FLR_2 Cooling 15849.83791 15849.83791 1.26844 3.96367 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 24:00:00 29.89400 5.57865E-003 222.96730 11.99560 0.79269 0.00000
28 OR4_FLR_2 Heating 0.00000 0.00000 0.00000 0.79269 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50000 4.31558E-003 222.96730 11.99560 0.79269 0.00000
29 IC_PATROOM1_MULT5_FLR_2 Cooling 9470.24627 9470.24627 0.75787 0.75787 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 38.27300 5.57864E-003 20.90318 1.12440 0.24773 0.00000
30 IC_PATROOM1_MULT5_FLR_2 Heating 2419.45633 2419.45633 0.11423 0.24773 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 20.90318 1.12440 0.24773 0.00000
31 IC_PATROOM2_FLR_2 Cooling 2871.54513 2871.54513 0.22980 0.22980 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 38.49467 5.57865E-003 27.87091 1.49940 6.60607E-002 0.00000
32 IC_PATROOM2_FLR_2 Heating 1096.26359 1096.26359 5.17585E-002 6.60607E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 27.87091 1.49940 6.60607E-002 0.00000
33 IC_PATROOM3_MULT6_FLR_2 Cooling 8596.79929 8596.79929 0.68798 0.89187 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 40.26800 5.57864E-003 20.90318 1.12440 0.29727 0.00000
34 IC_PATROOM3_MULT6_FLR_2 Heating 2922.40529 2922.40529 0.13798 0.29727 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 20.90318 1.12440 0.29727 0.00000
35 ICU_FLR_2 Cooling 34180.67913 34180.67913 2.73544 4.39442 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 39.82467 5.57864E-003 617.96447 33.24620 1.46472 0.00000
36 ICU_FLR_2 Heating 4604.68945 4604.68945 0.21741 1.46472 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 617.96447 33.24620 1.46472 0.00000
37 ICU_NURSESTN_LOBBY_FLR_2 Cooling 23477.70985 23477.70985 1.87879 1.87879 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 24:00:00 29.89400 5.57865E-003 668.76778 9.59460 0.22647 0.00000
38 ICU_NURSESTN_LOBBY_FLR_2 Heating 0.00000 0.00000 0.00000 0.22647 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50000 4.31558E-003 668.76778 9.59460 0.22647 0.00000
39 CORRIDOR_FLR_2 Cooling 6252.27408 6252.27408 0.50033 0.50033 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 20:40:00 33.35200 5.57864E-003 569.03112 6.12280 0.17343 0.00000
40 CORRIDOR_FLR_2 Heating 1679.51164 1679.51164 7.92965E-002 0.17343 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 569.03112 6.12280 0.17343 0.00000
41 OR_NURSESTN_LOBBY_FLR_2 Cooling 28255.68343 28255.68343 2.26114 2.26114 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 35.74600 5.57864E-003 1012.64314 14.52800 0.34293 0.00000
42 OR_NURSESTN_LOBBY_FLR_2 Heating 4365.49087 4365.49087 0.20611 0.34293 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 1012.64314 14.52800 0.34293 0.00000
43 PATROOM1_MULT10_FLR_3 Cooling 13980.29189 13980.29189 1.11880 1.48645 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 36.07850 5.57864E-003 20.90318 1.12440 0.49546 0.00000
44 PATROOM1_MULT10_FLR_3 Heating 4477.79414 4477.79414 0.21141 0.49546 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 20.90318 1.12440 0.49546 0.00000
45 PATROOM2_FLR_3 Cooling 2533.37730 2533.37730 0.20274 0.24774 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 36.07850 5.57864E-003 34.83864 1.87440 8.25758E-002 0.00000
46 PATROOM2_FLR_3 Heating 1156.43274 1156.43274 5.45992E-002 8.25758E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 34.83864 1.87440 8.25758E-002 0.00000
47 PATROOM3_MULT10_FLR_3 Cooling 10005.37240 10005.37240 0.80070 1.43703 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 40.13500 5.57864E-003 20.20824 1.08730 0.47898 0.00000
48 PATROOM3_MULT10_FLR_3 Heating 4313.50702 4313.50702 0.20366 0.47898 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 20.20824 1.08730 0.47898 0.00000
49 PATROOM4_FLR_3 Cooling 2825.19224 2825.19224 0.22609 0.24774 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 38.49467 5.57865E-003 34.83864 1.87440 8.25758E-002 0.00000
50 PATROOM4_FLR_3 Heating 1152.32756 1152.32756 5.44054E-002 8.25758E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 34.83864 1.87440 8.25758E-002 0.00000
51 PATROOM5_MULT10_FLR_3 Cooling 15137.34898 15137.34898 1.21140 1.48645 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 38.49467 5.57865E-003 20.90318 1.12440 0.49546 0.00000
52 PATROOM5_MULT10_FLR_3 Heating 4447.35710 4447.35710 0.20998 0.49546 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 20.90318 1.12440 0.49546 0.00000
53 PHYSTHERAPY_FLR_3 Cooling 13922.16092 13922.16092 1.11419 1.11419 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 22:30:00 31.29050 5.57865E-003 487.74096 26.24040 0.18582 0.00000
54 PHYSTHERAPY_FLR_3 Heating 0.00000 0.00000 0.00000 0.18582 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50000 4.31558E-003 487.74096 26.24040 0.18582 0.00000
55 PATROOM6_FLR_3 Cooling 2080.56801 2080.56801 0.16650 0.19819 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 36.41100 5.57864E-003 27.87091 1.49940 6.60607E-002 0.00000
56 PATROOM6_FLR_3 Heating 1013.17640 1013.17640 4.78355E-002 6.60607E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 27.87091 1.49940 6.60607E-002 0.00000
57 PATROOM7_MULT10_FLR_3 Cooling 10330.19367 10330.19367 0.82669 1.43703 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 40.40100 5.57864E-003 20.20824 1.08730 0.47898 0.00000
58 PATROOM7_MULT10_FLR_3 Heating 4330.30555 4330.30555 0.20445 0.47898 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 20.20824 1.08730 0.47898 0.00000
59 PATROOM8_FLR_3 Cooling 2358.04684 2358.04684 0.18871 0.19819 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 38.49467 5.57865E-003 27.87091 1.49940 6.60607E-002 0.00000
60 PATROOM8_FLR_3 Heating 1009.79964 1009.79964 4.76761E-002 6.60607E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 27.87091 1.49940 6.60607E-002 0.00000
61 NURSESTN_LOBBY_FLR_3 Cooling 20528.31351 20528.31351 1.64277 1.64277 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 22:00:00 31.75600 5.57865E-003 905.80464 12.99520 0.30675 0.00000
62 NURSESTN_LOBBY_FLR_3 Heating 0.00000 0.00000 0.00000 0.30675 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50000 4.31558E-003 905.80464 12.99520 0.30675 0.00000
63 LAB_FLR_3 Cooling 14756.64005 14756.64005 1.18096 1.18096 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 22:30:00 31.29050 5.57865E-003 264.77366 14.24460 0.30934 0.00000
64 LAB_FLR_3 Heating 0.00000 0.00000 0.00000 0.30934 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50000 4.31558E-003 264.77366 14.24460 0.30934 0.00000
65 CORRIDOR_SE_FLR_3 Cooling 6336.42766 6336.42766 0.50706 0.50706 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 37.82967 5.57864E-003 566.70854 6.09780 0.17272 0.00000
66 CORRIDOR_SE_FLR_3 Heating 0.00000 0.00000 0.00000 0.17272 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50000 4.31558E-003 566.70854 6.09780 0.17272 0.00000
67 CORRIDOR_NW_FLR_3 Cooling 6358.08198 6358.08198 0.50880 0.50880 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 32.95300 5.57864E-003 566.70854 6.09780 0.17272 0.00000
68 CORRIDOR_NW_FLR_3 Heating 0.00000 0.00000 0.00000 0.17272 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50000 4.31558E-003 566.70854 6.09780 0.17272 0.00000
69 PATROOM1_MULT10_FLR_4 Cooling 13984.66976 13984.66976 1.11915 1.48645 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 36.07850 5.57864E-003 20.90318 1.12440 0.49546 0.00000
70 PATROOM1_MULT10_FLR_4 Heating 4502.69203 4502.69203 0.21259 0.49546 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 20.90318 1.12440 0.49546 0.00000
71 PATROOM2_FLR_4 Cooling 2535.73724 2535.73724 0.20293 0.24774 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 36.07850 5.57864E-003 34.83864 1.87440 8.25758E-002 0.00000
72 PATROOM2_FLR_4 Heating 1162.71525 1162.71525 5.48957E-002 8.25758E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 34.83864 1.87440 8.25758E-002 0.00000
73 PATROOM3_MULT10_FLR_4 Cooling 10031.44183 10031.44183 0.80279 1.43703 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 40.13500 5.57864E-003 20.20824 1.08730 0.47898 0.00000
74 PATROOM3_MULT10_FLR_4 Heating 4335.69582 4335.69582 0.20470 0.47898 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 20.20824 1.08730 0.47898 0.00000
75 PATROOM4_FLR_4 Cooling 2829.32673 2829.32673 0.22642 0.24774 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 38.49467 5.57865E-003 34.83864 1.87440 8.25758E-002 0.00000
76 PATROOM4_FLR_4 Heating 1158.32908 1158.32908 5.46886E-002 8.25758E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 34.83864 1.87440 8.25758E-002 0.00000
77 PATROOM5_MULT10_FLR_4 Cooling 15146.88645 15146.88645 1.21216 1.48645 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 38.49467 5.57865E-003 20.90318 1.12440 0.49546 0.00000
78 PATROOM5_MULT10_FLR_4 Heating 4470.30953 4470.30953 0.21106 0.49546 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 20.90318 1.12440 0.49546 0.00000
79 RADIOLOGY_FLR_4 Cooling 55589.20542 55589.20542 4.44874 4.44874 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 22:20:00 31.44567 5.57865E-003 487.74096 26.24040 0.18582 0.00000
80 RADIOLOGY_FLR_4 Heating 0.00000 0.00000 0.00000 0.18582 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50000 4.31558E-003 487.74096 26.24040 0.18582 0.00000
81 PATROOM6_FLR_4 Cooling 2082.77919 2082.77919 0.16668 0.19819 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 36.41100 5.57864E-003 27.87091 1.49940 6.60607E-002 0.00000
82 PATROOM6_FLR_4 Heating 1018.84616 1018.84616 4.81031E-002 6.60607E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 27.87091 1.49940 6.60607E-002 0.00000
83 PATROOM7_MULT10_FLR_4 Cooling 10353.62655 10353.62655 0.82857 1.43703 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 40.40100 5.57864E-003 20.20824 1.08730 0.47898 0.00000
84 PATROOM7_MULT10_FLR_4 Heating 4354.40378 4354.40378 0.20559 0.47898 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 20.20824 1.08730 0.47898 0.00000
85 PATROOM8_FLR_4 Cooling 2361.49101 2361.49101 0.18898 0.19819 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 38.49467 5.57865E-003 27.87091 1.49940 6.60607E-002 0.00000
86 PATROOM8_FLR_4 Heating 1015.24040 1015.24040 4.79329E-002 6.60607E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 27.87091 1.49940 6.60607E-002 0.00000
87 NURSESTN_LOBBY_FLR_4 Cooling 22026.38273 22026.38273 1.76265 1.76265 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 22:00:00 31.75600 5.57865E-003 905.80464 12.99520 0.30675 0.00000
88 NURSESTN_LOBBY_FLR_4 Heating 0.00000 0.00000 0.00000 0.30675 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50000 4.31558E-003 905.80464 12.99520 0.30675 0.00000
89 LAB_FLR_4 Cooling 14830.39377 14830.39377 1.18686 1.18686 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 22:20:00 31.44567 5.57865E-003 264.77366 14.24460 0.30934 0.00000
90 LAB_FLR_4 Heating 0.00000 0.00000 0.00000 0.30934 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50000 4.31558E-003 264.77366 14.24460 0.30934 0.00000
91 CORRIDOR_SE_FLR_4 Cooling 7135.85293 7135.85293 0.57104 0.57104 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 38.05133 5.57865E-003 566.70854 6.09780 0.17272 0.00000
92 CORRIDOR_SE_FLR_4 Heating 0.00000 0.00000 0.00000 0.17272 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50000 4.31558E-003 566.70854 6.09780 0.17272 0.00000
93 CORRIDOR_NW_FLR_4 Cooling 7105.00627 7105.00627 0.56857 0.56857 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 32.95300 5.57864E-003 566.70854 6.09780 0.17272 0.00000
94 CORRIDOR_NW_FLR_4 Heating 0.00000 0.00000 0.00000 0.17272 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50000 4.31558E-003 566.70854 6.09780 0.17272 0.00000
95 DINING_FLR_5 Cooling 27338.62041 27338.62041 2.18807 2.18807 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 40.80000 5.57864E-003 696.77280 74.97250 0.90254 0.00000
96 DINING_FLR_5 Heating 9055.74503 9055.74503 0.42756 0.90254 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 21:40:00 0.50000 4.31558E-003 696.77280 74.97250 0.90254 0.00000
97 NURSESTN_LOBBY_FLR_5 Cooling 33522.24599 33522.24599 2.68259 2.68259 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 40.80000 5.57864E-003 1040.51405 14.92790 0.35236 0.00000
98 NURSESTN_LOBBY_FLR_5 Heating 8143.20492 8143.20492 0.38447 0.38447 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 21:40:00 0.50000 4.31558E-003 1040.51405 14.92790 0.35236 0.00000
99 KITCHEN_FLR_5 Cooling 234286.89211 234286.89211 18.74927 18.74927 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 40.80000 5.57864E-003 929.03040 49.98180 1.88354 0.00000
100 KITCHEN_FLR_5 Heating 14739.89583 14739.89583 0.69592 1.88354 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 21:00:00 0.50000 4.31558E-003 929.03040 49.98180 1.88354 0.00000
101 OFFICE1_FLR_5 Cooling 3573.67651 3573.67651 0.28600 0.28600 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 37.40850 5.57864E-003 69.69557 5.24980 3.36330E-002 0.00000
102 OFFICE1_FLR_5 Heating 2138.28895 2138.28895 0.10096 0.10096 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 69.69557 5.24980 3.36330E-002 0.00000
103 OFFICE2_MULT5_FLR_5 Cooling 12903.32650 12903.32650 1.03266 1.03266 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 40.66700 5.57864E-003 69.67728 5.24830 0.16812 0.00000
104 OFFICE2_MULT5_FLR_5 Heating 6042.92760 6042.92760 0.28531 0.28531 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 69.67728 5.24830 0.16812 0.00000
105 OFFICE3_FLR_5 Cooling 4181.75405 4181.75405 0.33466 0.33466 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 38.93800 5.57864E-003 69.67728 5.24830 3.36242E-002 0.00000
106 OFFICE3_FLR_5 Heating 2131.88980 2131.88980 0.10065 0.10065 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 69.67728 5.24830 3.36242E-002 0.00000
107 OFFICE4_MULT6_FLR_5 Cooling 5421.77243 5421.77243 0.43390 0.43390 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 38.49467 5.57865E-003 13.93546 1.05000 4.03490E-002 0.00000
108 OFFICE4_MULT6_FLR_5 Heating 2351.60660 2351.60660 0.11103 0.11103 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 13.93546 1.05000 4.03490E-002 0.00000
109 CORRIDOR_FLR_5 Cooling 10260.79278 10260.79278 0.82111 0.82111 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 40.66700 5.57864E-003 501.67642 5.39810 0.15290 0.00000
110 CORRIDOR_FLR_5 Heating 4385.99665 4385.99665 0.20708 0.20708 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 21:40:00 0.50000 4.31558E-003 501.67642 5.39810 0.15290 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_1 Cooling Sensible 264542.21 15.03009 15.03009 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_1 Heating Sensible 44391.62 3.28544 3.28544 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
3 VAV_ER Cooling Sensible 81772.44 5.54937 5.54937 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_ER Heating Sensible 12496.12 0.92484 0.92484 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
5 VAV_OR Cooling Sensible 152830.95 10.90009 10.90009 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_OR Heating Sensible 29453.89 2.17989 2.17989 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
7 VAV_ICU Cooling Sensible 112875.96 6.27396 6.27396 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
8 VAV_ICU Heating Sensible 28047.19 2.07578 2.07578 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
9 VAV_PATRMS Cooling Sensible 237703.06 13.47766 13.47766 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
10 VAV_PATRMS Heating Sensible 60698.23 4.49230 4.49230 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
11 VAV_2 Cooling Sensible 313270.82 18.78248 18.78248 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
12 VAV_2 Heating Sensible 50912.60 3.76806 3.76806 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 21:40:00
13 VAV_LABS Cooling Sensible 34137.84 2.36782 2.36782 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
14 VAV_LABS Heating Sensible 8359.43 0.61868 0.61868 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
15 CAV_KITCHEN Cooling Sensible 265268.39 18.74927 18.74927 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
16 CAV_KITCHEN Heating Sensible 25449.72 1.88354 1.88354 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.14215
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.55412
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.40200
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.06714
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.87573E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.30613E-004
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.06714
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18895.52689
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.30613E-004
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 798.43129
15 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM1_MULT4_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.58553
16 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM1_MULT4_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
17 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM1_MULT4_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
18 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM1_MULT4_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.58553
19 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM1_MULT4_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
20 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM1_MULT4_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM1_MULT4_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.11106E-003
22 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM1_MULT4_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.87741E-004
23 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM1_MULT4_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.58553
24 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM1_MULT4_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
25 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM1_MULT4_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water ER_EXAM1_MULT4_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16445.26348
27 Coil:Heating:Water ER_EXAM1_MULT4_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.87741E-004
28 Coil:Heating:Water ER_EXAM1_MULT4_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 715.38006
29 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.39638
30 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
31 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
32 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.39638
33 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
34 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.11106E-003
36 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.80916E-005
37 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.39638
38 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
39 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water ER_TRAUMA1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4463.17720
41 Coil:Heating:Water ER_TRAUMA1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.80916E-005
42 Coil:Heating:Water ER_TRAUMA1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 198.41034
43 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM3_MULT4_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.58553
44 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM3_MULT4_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
45 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM3_MULT4_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
46 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM3_MULT4_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.58553
47 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM3_MULT4_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM3_MULT4_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM3_MULT4_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.11106E-003
50 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM3_MULT4_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.79872E-004
51 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM3_MULT4_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.58553
52 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM3_MULT4_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
53 AirTerminal:SingleDuct:VAV:Reheat ER_EXAM3_MULT4_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water ER_EXAM3_MULT4_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15995.57074
55 Coil:Heating:Water ER_EXAM3_MULT4_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.79872E-004
56 Coil:Heating:Water ER_EXAM3_MULT4_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 691.09622
57 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.39638
58 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
59 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
60 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.39638
61 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.11106E-003
64 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.81177E-005
65 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.39638
66 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
67 AirTerminal:SingleDuct:VAV:Reheat ER_TRAUMA2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water ER_TRAUMA2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4464.66682
69 Coil:Heating:Water ER_TRAUMA2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.81177E-005
70 Coil:Heating:Water ER_TRAUMA2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 198.49505
71 AirTerminal:SingleDuct:VAV:Reheat ER_TRIAGE_MULT4_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.58553
72 AirTerminal:SingleDuct:VAV:Reheat ER_TRIAGE_MULT4_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
73 AirTerminal:SingleDuct:VAV:Reheat ER_TRIAGE_MULT4_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
74 AirTerminal:SingleDuct:VAV:Reheat ER_TRIAGE_MULT4_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.58553
75 AirTerminal:SingleDuct:VAV:Reheat ER_TRIAGE_MULT4_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
76 AirTerminal:SingleDuct:VAV:Reheat ER_TRIAGE_MULT4_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat ER_TRIAGE_MULT4_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.11106E-003
78 AirTerminal:SingleDuct:VAV:Reheat ER_TRIAGE_MULT4_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.87832E-004
79 AirTerminal:SingleDuct:VAV:Reheat ER_TRIAGE_MULT4_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.58553
80 AirTerminal:SingleDuct:VAV:Reheat ER_TRIAGE_MULT4_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
81 AirTerminal:SingleDuct:VAV:Reheat ER_TRIAGE_MULT4_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water ER_TRIAGE_MULT4_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16450.50439
83 Coil:Heating:Water ER_TRIAGE_MULT4_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.87832E-004
84 Coil:Heating:Water ER_TRIAGE_MULT4_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 715.66509
85 AirTerminal:SingleDuct:VAV:Reheat OFFICE1_MULT4_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.32002
86 AirTerminal:SingleDuct:VAV:Reheat OFFICE1_MULT4_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16591
87 AirTerminal:SingleDuct:VAV:Reheat OFFICE1_MULT4_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.15800
88 AirTerminal:SingleDuct:VAV:Reheat OFFICE1_MULT4_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.05629E-002
89 AirTerminal:SingleDuct:VAV:Reheat OFFICE1_MULT4_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
90 AirTerminal:SingleDuct:VAV:Reheat OFFICE1_MULT4_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat OFFICE1_MULT4_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.29643E-003
92 AirTerminal:SingleDuct:VAV:Reheat OFFICE1_MULT4_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.93597E-005
93 AirTerminal:SingleDuct:VAV:Reheat OFFICE1_MULT4_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.41929E-002
94 AirTerminal:SingleDuct:VAV:Reheat OFFICE1_MULT4_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
95 AirTerminal:SingleDuct:VAV:Reheat OFFICE1_MULT4_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water OFFICE1_MULT4_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2249.52748
97 Coil:Heating:Water OFFICE1_MULT4_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.93597E-005
98 Coil:Heating:Water OFFICE1_MULT4_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 177.96354
99 AirTerminal:SingleDuct:VAV:Reheat LOBBY_RECORDS_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.74971
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_RECORDS_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.64228
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_RECORDS_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.42800
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_RECORDS_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.74887
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_RECORDS_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_RECORDS_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_RECORDS_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.93197E-004
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_RECORDS_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.80597E-004
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_RECORDS_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.74887
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_RECORDS_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_RECORDS_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
110 Coil:Heating:Water LOBBY_RECORDS_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16036.97562
111 Coil:Heating:Water LOBBY_RECORDS_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.80597E-004
112 Coil:Heating:Water LOBBY_RECORDS_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 911.91651
113 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.52124
114 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.83186
115 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.49900
116 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.26010
117 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
118 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
119 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.58009E-004
120 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.51493E-005
121 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.26010
122 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
123 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
124 Coil:Heating:Water CORRIDOR_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4295.01411
125 Coil:Heating:Water CORRIDOR_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.51493E-005
126 Coil:Heating:Water CORRIDOR_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 217.90925
127 AirTerminal:SingleDuct:VAV:Reheat ER_NURSESTN_LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.81131
128 AirTerminal:SingleDuct:VAV:Reheat ER_NURSESTN_LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.33491
129 AirTerminal:SingleDuct:VAV:Reheat ER_NURSESTN_LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22300
130 AirTerminal:SingleDuct:VAV:Reheat ER_NURSESTN_LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.62692
131 AirTerminal:SingleDuct:VAV:Reheat ER_NURSESTN_LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.89309
132 AirTerminal:SingleDuct:VAV:Reheat ER_NURSESTN_LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
133 AirTerminal:SingleDuct:VAV:Reheat ER_NURSESTN_LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.13762E-003
134 AirTerminal:SingleDuct:VAV:Reheat ER_NURSESTN_LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.50513E-004
135 AirTerminal:SingleDuct:VAV:Reheat ER_NURSESTN_LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.62692
136 AirTerminal:SingleDuct:VAV:Reheat ER_NURSESTN_LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
137 AirTerminal:SingleDuct:VAV:Reheat ER_NURSESTN_LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
138 Coil:Heating:Water ER_NURSESTN_LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8602.29941
139 Coil:Heating:Water ER_NURSESTN_LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.50513E-004
140 Coil:Heating:Water ER_NURSESTN_LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 407.43416
141 AirTerminal:SingleDuct:VAV:Reheat OR1_FLR_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.99092
142 AirTerminal:SingleDuct:VAV:Reheat OR1_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.60000
143 AirTerminal:SingleDuct:VAV:Reheat OR1_FLR_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
144 AirTerminal:SingleDuct:VAV:Reheat OR1_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.88845E-003
145 AirTerminal:SingleDuct:VAV:Reheat OR1_FLR_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.15317E-004
146 AirTerminal:SingleDuct:VAV:Reheat OR1_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.59455
147 AirTerminal:SingleDuct:VAV:Reheat OR1_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
148 AirTerminal:SingleDuct:VAV:Reheat OR1_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
149 Coil:Heating:Water OR1_FLR_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6590.74248
150 Coil:Heating:Water OR1_FLR_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.15317E-004
151 Coil:Heating:Water OR1_FLR_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 291.73020
152 AirTerminal:SingleDuct:VAV:Reheat OR2_MULT5_FLR_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.95458
153 AirTerminal:SingleDuct:VAV:Reheat OR2_MULT5_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.60000
154 AirTerminal:SingleDuct:VAV:Reheat OR2_MULT5_FLR_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
155 AirTerminal:SingleDuct:VAV:Reheat OR2_MULT5_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.88845E-003
156 AirTerminal:SingleDuct:VAV:Reheat OR2_MULT5_FLR_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.16968E-004
157 AirTerminal:SingleDuct:VAV:Reheat OR2_MULT5_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.97275
158 AirTerminal:SingleDuct:VAV:Reheat OR2_MULT5_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
159 AirTerminal:SingleDuct:VAV:Reheat OR2_MULT5_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
160 Coil:Heating:Water OR2_MULT5_FLR_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 29546.33170
161 Coil:Heating:Water OR2_MULT5_FLR_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.16968E-004
162 Coil:Heating:Water OR2_MULT5_FLR_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1272.02279
163 AirTerminal:SingleDuct:VAV:Reheat OR3_FLR_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.99092
164 AirTerminal:SingleDuct:VAV:Reheat OR3_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.60000
165 AirTerminal:SingleDuct:VAV:Reheat OR3_FLR_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
166 AirTerminal:SingleDuct:VAV:Reheat OR3_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.88845E-003
167 AirTerminal:SingleDuct:VAV:Reheat OR3_FLR_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.07456E-004
168 AirTerminal:SingleDuct:VAV:Reheat OR3_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.59455
169 AirTerminal:SingleDuct:VAV:Reheat OR3_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
170 AirTerminal:SingleDuct:VAV:Reheat OR3_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
171 Coil:Heating:Water OR3_FLR_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6141.46464
172 Coil:Heating:Water OR3_FLR_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.07456E-004
173 Coil:Heating:Water OR3_FLR_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 266.88460
174 AirTerminal:SingleDuct:VAV:Reheat OR4_FLR_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.96367
175 AirTerminal:SingleDuct:VAV:Reheat OR4_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.60000
176 AirTerminal:SingleDuct:VAV:Reheat OR4_FLR_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
177 AirTerminal:SingleDuct:VAV:Reheat OR4_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.88845E-003
178 AirTerminal:SingleDuct:VAV:Reheat OR4_FLR_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.80362E-004
179 AirTerminal:SingleDuct:VAV:Reheat OR4_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.37820
180 AirTerminal:SingleDuct:VAV:Reheat OR4_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
181 AirTerminal:SingleDuct:VAV:Reheat OR4_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
182 Coil:Heating:Water OR4_FLR_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 21738.87462
183 Coil:Heating:Water OR4_FLR_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.80362E-004
184 Coil:Heating:Water OR4_FLR_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 918.57707
185 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM1_MULT5_FLR_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.75787
186 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM1_MULT5_FLR_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.98067
187 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM1_MULT5_FLR_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
188 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM1_MULT5_FLR_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.75787
189 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM1_MULT5_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
190 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM1_MULT5_FLR_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
191 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM1_MULT5_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.62564E-003
192 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM1_MULT5_FLR_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.63524E-004
193 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM1_MULT5_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.75787
194 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM1_MULT5_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
195 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM1_MULT5_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
196 Coil:Heating:Water IC_PATROOM1_MULT5_FLR_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9345.91752
197 Coil:Heating:Water IC_PATROOM1_MULT5_FLR_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.63524E-004
198 Coil:Heating:Water IC_PATROOM1_MULT5_FLR_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 426.85686
199 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM2_FLR_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.22980
200 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM2_FLR_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.86246
201 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM2_FLR_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
202 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM2_FLR_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.22980
203 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM2_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
204 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM2_FLR_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
205 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM2_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.12256E-003
206 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM2_FLR_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.59277E-005
207 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM2_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.22980
208 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM2_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
209 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM2_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
210 Coil:Heating:Water IC_PATROOM2_FLR_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3196.43881
211 Coil:Heating:Water IC_PATROOM2_FLR_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.59277E-005
212 Coil:Heating:Water IC_PATROOM2_FLR_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 152.16359
213 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM3_MULT6_FLR_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.89187
214 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM3_MULT6_FLR_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
215 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM3_MULT6_FLR_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
216 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM3_MULT6_FLR_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.89187
217 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM3_MULT6_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
218 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM3_MULT6_FLR_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
219 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM3_MULT6_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.55556E-003
220 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM3_MULT6_FLR_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.93752E-004
221 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM3_MULT6_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.89187
222 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM3_MULT6_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
223 AirTerminal:SingleDuct:VAV:Reheat IC_PATROOM3_MULT6_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
224 Coil:Heating:Water IC_PATROOM3_MULT6_FLR_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11073.49815
225 Coil:Heating:Water IC_PATROOM3_MULT6_FLR_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.93752E-004
226 Coil:Heating:Water IC_PATROOM3_MULT6_FLR_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 506.80611
227 AirTerminal:SingleDuct:VAV:Reheat ICU_FLR_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.39442
228 AirTerminal:SingleDuct:VAV:Reheat ICU_FLR_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
229 AirTerminal:SingleDuct:VAV:Reheat ICU_FLR_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
230 AirTerminal:SingleDuct:VAV:Reheat ICU_FLR_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 4.39442
231 AirTerminal:SingleDuct:VAV:Reheat ICU_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
232 AirTerminal:SingleDuct:VAV:Reheat ICU_FLR_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
233 AirTerminal:SingleDuct:VAV:Reheat ICU_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.55556E-003
234 AirTerminal:SingleDuct:VAV:Reheat ICU_FLR_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.83267E-004
235 AirTerminal:SingleDuct:VAV:Reheat ICU_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.39442
236 AirTerminal:SingleDuct:VAV:Reheat ICU_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
237 AirTerminal:SingleDuct:VAV:Reheat ICU_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
238 Coil:Heating:Water ICU_FLR_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 44766.09145
239 Coil:Heating:Water ICU_FLR_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.83267E-004
240 Coil:Heating:Water ICU_FLR_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1938.71110
241 AirTerminal:SingleDuct:VAV:Reheat ICU_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.87879
242 AirTerminal:SingleDuct:VAV:Reheat ICU_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.27124
243 AirTerminal:SingleDuct:VAV:Reheat ICU_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.18100
244 AirTerminal:SingleDuct:VAV:Reheat ICU_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.34006
245 AirTerminal:SingleDuct:VAV:Reheat ICU_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.72330
246 AirTerminal:SingleDuct:VAV:Reheat ICU_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
247 AirTerminal:SingleDuct:VAV:Reheat ICU_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.40466E-003
248 AirTerminal:SingleDuct:VAV:Reheat ICU_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.43883E-005
249 AirTerminal:SingleDuct:VAV:Reheat ICU_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.34006
250 AirTerminal:SingleDuct:VAV:Reheat ICU_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
251 AirTerminal:SingleDuct:VAV:Reheat ICU_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
252 Coil:Heating:Water ICU_NURSESTN_LOBBY_FLR_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3108.45633
253 Coil:Heating:Water ICU_NURSESTN_LOBBY_FLR_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.43883E-005
254 Coil:Heating:Water ICU_NURSESTN_LOBBY_FLR_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 131.34795
255 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.50033
256 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.86663
257 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.52000
258 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.26017
259 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
260 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
261 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.39633E-004
262 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.09885E-005
263 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.26017
264 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
265 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
266 Coil:Heating:Water CORRIDOR_FLR_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4057.21358
267 Coil:Heating:Water CORRIDOR_FLR_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.09885E-005
268 Coil:Heating:Water CORRIDOR_FLR_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 202.19840
269 AirTerminal:SingleDuct:VAV:Reheat OR_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.26114
270 AirTerminal:SingleDuct:VAV:Reheat OR_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.34126
271 AirTerminal:SingleDuct:VAV:Reheat OR_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22700
272 AirTerminal:SingleDuct:VAV:Reheat OR_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.51328
273 AirTerminal:SingleDuct:VAV:Reheat OR_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.91003
274 AirTerminal:SingleDuct:VAV:Reheat OR_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
275 AirTerminal:SingleDuct:VAV:Reheat OR_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.11645E-003
276 AirTerminal:SingleDuct:VAV:Reheat OR_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.58461E-004
277 AirTerminal:SingleDuct:VAV:Reheat OR_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.51328
278 AirTerminal:SingleDuct:VAV:Reheat OR_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
279 AirTerminal:SingleDuct:VAV:Reheat OR_NURSESTN_LOBBY_FLR_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
280 Coil:Heating:Water OR_NURSESTN_LOBBY_FLR_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9056.53877
281 Coil:Heating:Water OR_NURSESTN_LOBBY_FLR_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.58461E-004
282 Coil:Heating:Water OR_NURSESTN_LOBBY_FLR_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 470.35533
283 AirTerminal:SingleDuct:VAV:Reheat PATROOM1_MULT10_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.48645
284 AirTerminal:SingleDuct:VAV:Reheat PATROOM1_MULT10_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
285 AirTerminal:SingleDuct:VAV:Reheat PATROOM1_MULT10_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
286 AirTerminal:SingleDuct:VAV:Reheat PATROOM1_MULT10_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.74322
287 AirTerminal:SingleDuct:VAV:Reheat PATROOM1_MULT10_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.95245
288 AirTerminal:SingleDuct:VAV:Reheat PATROOM1_MULT10_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
289 AirTerminal:SingleDuct:VAV:Reheat PATROOM1_MULT10_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.55556E-003
290 AirTerminal:SingleDuct:VAV:Reheat PATROOM1_MULT10_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.97191E-004
291 AirTerminal:SingleDuct:VAV:Reheat PATROOM1_MULT10_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.74322
292 AirTerminal:SingleDuct:VAV:Reheat PATROOM1_MULT10_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
293 AirTerminal:SingleDuct:VAV:Reheat PATROOM1_MULT10_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
294 Coil:Heating:Water PATROOM1_MULT10_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11270.05890
295 Coil:Heating:Water PATROOM1_MULT10_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.97191E-004
296 Coil:Heating:Water PATROOM1_MULT10_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 555.34602
297 AirTerminal:SingleDuct:VAV:Reheat PATROOM2_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.24774
298 AirTerminal:SingleDuct:VAV:Reheat PATROOM2_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
299 AirTerminal:SingleDuct:VAV:Reheat PATROOM2_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
300 AirTerminal:SingleDuct:VAV:Reheat PATROOM2_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12387
301 AirTerminal:SingleDuct:VAV:Reheat PATROOM2_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.57147
302 AirTerminal:SingleDuct:VAV:Reheat PATROOM2_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
303 AirTerminal:SingleDuct:VAV:Reheat PATROOM2_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.55556E-003
304 AirTerminal:SingleDuct:VAV:Reheat PATROOM2_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.00408E-005
305 AirTerminal:SingleDuct:VAV:Reheat PATROOM2_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.12387
306 AirTerminal:SingleDuct:VAV:Reheat PATROOM2_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
307 AirTerminal:SingleDuct:VAV:Reheat PATROOM2_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
308 Coil:Heating:Water PATROOM2_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2288.45689
309 Coil:Heating:Water PATROOM2_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.00408E-005
310 Coil:Heating:Water PATROOM2_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 121.04481
311 AirTerminal:SingleDuct:VAV:Reheat PATROOM3_MULT10_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.43703
312 AirTerminal:SingleDuct:VAV:Reheat PATROOM3_MULT10_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
313 AirTerminal:SingleDuct:VAV:Reheat PATROOM3_MULT10_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
314 AirTerminal:SingleDuct:VAV:Reheat PATROOM3_MULT10_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.71852
315 AirTerminal:SingleDuct:VAV:Reheat PATROOM3_MULT10_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.98520
316 AirTerminal:SingleDuct:VAV:Reheat PATROOM3_MULT10_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
317 AirTerminal:SingleDuct:VAV:Reheat PATROOM3_MULT10_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.55556E-003
318 AirTerminal:SingleDuct:VAV:Reheat PATROOM3_MULT10_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.90365E-004
319 AirTerminal:SingleDuct:VAV:Reheat PATROOM3_MULT10_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.71852
320 AirTerminal:SingleDuct:VAV:Reheat PATROOM3_MULT10_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
321 AirTerminal:SingleDuct:VAV:Reheat PATROOM3_MULT10_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
322 Coil:Heating:Water PATROOM3_MULT10_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10879.95308
323 Coil:Heating:Water PATROOM3_MULT10_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.90365E-004
324 Coil:Heating:Water PATROOM3_MULT10_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 535.79875
325 AirTerminal:SingleDuct:VAV:Reheat PATROOM4_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.24774
326 AirTerminal:SingleDuct:VAV:Reheat PATROOM4_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
327 AirTerminal:SingleDuct:VAV:Reheat PATROOM4_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
328 AirTerminal:SingleDuct:VAV:Reheat PATROOM4_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12387
329 AirTerminal:SingleDuct:VAV:Reheat PATROOM4_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.57147
330 AirTerminal:SingleDuct:VAV:Reheat PATROOM4_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
331 AirTerminal:SingleDuct:VAV:Reheat PATROOM4_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.55556E-003
332 AirTerminal:SingleDuct:VAV:Reheat PATROOM4_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.99690E-005
333 AirTerminal:SingleDuct:VAV:Reheat PATROOM4_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.12387
334 AirTerminal:SingleDuct:VAV:Reheat PATROOM4_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
335 AirTerminal:SingleDuct:VAV:Reheat PATROOM4_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
336 Coil:Heating:Water PATROOM4_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2284.35091
337 Coil:Heating:Water PATROOM4_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.99690E-005
338 Coil:Heating:Water PATROOM4_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 120.73727
339 AirTerminal:SingleDuct:VAV:Reheat PATROOM5_MULT10_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.48645
340 AirTerminal:SingleDuct:VAV:Reheat PATROOM5_MULT10_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
341 AirTerminal:SingleDuct:VAV:Reheat PATROOM5_MULT10_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
342 AirTerminal:SingleDuct:VAV:Reheat PATROOM5_MULT10_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.74322
343 AirTerminal:SingleDuct:VAV:Reheat PATROOM5_MULT10_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.95245
344 AirTerminal:SingleDuct:VAV:Reheat PATROOM5_MULT10_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
345 AirTerminal:SingleDuct:VAV:Reheat PATROOM5_MULT10_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.55556E-003
346 AirTerminal:SingleDuct:VAV:Reheat PATROOM5_MULT10_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.96658E-004
347 AirTerminal:SingleDuct:VAV:Reheat PATROOM5_MULT10_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.74322
348 AirTerminal:SingleDuct:VAV:Reheat PATROOM5_MULT10_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
349 AirTerminal:SingleDuct:VAV:Reheat PATROOM5_MULT10_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
350 Coil:Heating:Water PATROOM5_MULT10_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11239.61295
351 Coil:Heating:Water PATROOM5_MULT10_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.96658E-004
352 Coil:Heating:Water PATROOM5_MULT10_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 553.20676
353 AirTerminal:SingleDuct:VAV:Reheat PHYSTHERAPY_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.11419
354 AirTerminal:SingleDuct:VAV:Reheat PHYSTHERAPY_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.33357
355 AirTerminal:SingleDuct:VAV:Reheat PHYSTHERAPY_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.25000
356 AirTerminal:SingleDuct:VAV:Reheat PHYSTHERAPY_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.27855
357 AirTerminal:SingleDuct:VAV:Reheat PHYSTHERAPY_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.88952
358 AirTerminal:SingleDuct:VAV:Reheat PHYSTHERAPY_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
359 AirTerminal:SingleDuct:VAV:Reheat PHYSTHERAPY_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.14219E-003
360 AirTerminal:SingleDuct:VAV:Reheat PHYSTHERAPY_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.45499E-005
361 AirTerminal:SingleDuct:VAV:Reheat PHYSTHERAPY_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.27855
362 AirTerminal:SingleDuct:VAV:Reheat PHYSTHERAPY_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
363 AirTerminal:SingleDuct:VAV:Reheat PHYSTHERAPY_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
364 Coil:Heating:Water PHYSTHERAPY_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2546.16306
365 Coil:Heating:Water PHYSTHERAPY_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.45499E-005
366 Coil:Heating:Water PHYSTHERAPY_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 107.58823
367 AirTerminal:SingleDuct:VAV:Reheat PATROOM6_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.19819
368 AirTerminal:SingleDuct:VAV:Reheat PATROOM6_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
369 AirTerminal:SingleDuct:VAV:Reheat PATROOM6_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
370 AirTerminal:SingleDuct:VAV:Reheat PATROOM6_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 9.90966E-002
371 AirTerminal:SingleDuct:VAV:Reheat PATROOM6_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.71433
372 AirTerminal:SingleDuct:VAV:Reheat PATROOM6_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
373 AirTerminal:SingleDuct:VAV:Reheat PATROOM6_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.55556E-003
374 AirTerminal:SingleDuct:VAV:Reheat PATROOM6_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.35729E-005
375 AirTerminal:SingleDuct:VAV:Reheat PATROOM6_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.90966E-002
376 AirTerminal:SingleDuct:VAV:Reheat PATROOM6_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
377 AirTerminal:SingleDuct:VAV:Reheat PATROOM6_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
378 Coil:Heating:Water PATROOM6_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1918.79405
379 Coil:Heating:Water PATROOM6_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.35729E-005
380 Coil:Heating:Water PATROOM6_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 103.59354
381 AirTerminal:SingleDuct:VAV:Reheat PATROOM7_MULT10_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.43703
382 AirTerminal:SingleDuct:VAV:Reheat PATROOM7_MULT10_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
383 AirTerminal:SingleDuct:VAV:Reheat PATROOM7_MULT10_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
384 AirTerminal:SingleDuct:VAV:Reheat PATROOM7_MULT10_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.71852
385 AirTerminal:SingleDuct:VAV:Reheat PATROOM7_MULT10_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.98520
386 AirTerminal:SingleDuct:VAV:Reheat PATROOM7_MULT10_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
387 AirTerminal:SingleDuct:VAV:Reheat PATROOM7_MULT10_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.55556E-003
388 AirTerminal:SingleDuct:VAV:Reheat PATROOM7_MULT10_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.90659E-004
389 AirTerminal:SingleDuct:VAV:Reheat PATROOM7_MULT10_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.71852
390 AirTerminal:SingleDuct:VAV:Reheat PATROOM7_MULT10_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
391 AirTerminal:SingleDuct:VAV:Reheat PATROOM7_MULT10_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
392 Coil:Heating:Water PATROOM7_MULT10_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10896.75651
393 Coil:Heating:Water PATROOM7_MULT10_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.90659E-004
394 Coil:Heating:Water PATROOM7_MULT10_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 536.98018
395 AirTerminal:SingleDuct:VAV:Reheat PATROOM8_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.19819
396 AirTerminal:SingleDuct:VAV:Reheat PATROOM8_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
397 AirTerminal:SingleDuct:VAV:Reheat PATROOM8_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.50000
398 AirTerminal:SingleDuct:VAV:Reheat PATROOM8_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 9.90966E-002
399 AirTerminal:SingleDuct:VAV:Reheat PATROOM8_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.71433
400 AirTerminal:SingleDuct:VAV:Reheat PATROOM8_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
401 AirTerminal:SingleDuct:VAV:Reheat PATROOM8_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.55556E-003
402 AirTerminal:SingleDuct:VAV:Reheat PATROOM8_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.35138E-005
403 AirTerminal:SingleDuct:VAV:Reheat PATROOM8_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 9.90966E-002
404 AirTerminal:SingleDuct:VAV:Reheat PATROOM8_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
405 AirTerminal:SingleDuct:VAV:Reheat PATROOM8_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
406 Coil:Heating:Water PATROOM8_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1915.41668
407 Coil:Heating:Water PATROOM8_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.35138E-005
408 Coil:Heating:Water PATROOM8_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 103.32745
409 AirTerminal:SingleDuct:VAV:Reheat NURSESTN_LOBBY_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.64277
410 AirTerminal:SingleDuct:VAV:Reheat NURSESTN_LOBBY_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.42016
411 AirTerminal:SingleDuct:VAV:Reheat NURSESTN_LOBBY_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.28000
412 AirTerminal:SingleDuct:VAV:Reheat NURSESTN_LOBBY_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.45997
413 AirTerminal:SingleDuct:VAV:Reheat NURSESTN_LOBBY_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
414 AirTerminal:SingleDuct:VAV:Reheat NURSESTN_LOBBY_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
415 AirTerminal:SingleDuct:VAV:Reheat NURSESTN_LOBBY_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.06799E-004
416 AirTerminal:SingleDuct:VAV:Reheat NURSESTN_LOBBY_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.35669E-005
417 AirTerminal:SingleDuct:VAV:Reheat NURSESTN_LOBBY_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.45997
418 AirTerminal:SingleDuct:VAV:Reheat NURSESTN_LOBBY_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
419 AirTerminal:SingleDuct:VAV:Reheat NURSESTN_LOBBY_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
420 Coil:Heating:Water NURSESTN_LOBBY_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4204.57439
421 Coil:Heating:Water NURSESTN_LOBBY_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.35669E-005
422 Coil:Heating:Water NURSESTN_LOBBY_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 177.66447
423 AirTerminal:SingleDuct:VAV:Reheat LAB_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.18096
424 AirTerminal:SingleDuct:VAV:Reheat LAB_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17084
425 AirTerminal:SingleDuct:VAV:Reheat LAB_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 1.00000
426 AirTerminal:SingleDuct:VAV:Reheat LAB_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.18096
427 AirTerminal:SingleDuct:VAV:Reheat LAB_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
428 AirTerminal:SingleDuct:VAV:Reheat LAB_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
429 AirTerminal:SingleDuct:VAV:Reheat LAB_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.23013E-003
430 AirTerminal:SingleDuct:VAV:Reheat LAB_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.88879E-004
431 AirTerminal:SingleDuct:VAV:Reheat LAB_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.18096
432 AirTerminal:SingleDuct:VAV:Reheat LAB_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
433 AirTerminal:SingleDuct:VAV:Reheat LAB_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
434