Program Version:EnergyPlus, Version 9.5.0-de239b2e5f, YMD=2022.03.23 15:31

Tabular Output Report in Format: HTML

Building: Exercise 2A

Environment: RUN PERIOD 1 ** Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300

Simulation Timestamp: 2022-03-23 15:31:30


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 390.17 841.61 841.61
Net Site Energy 390.17 841.61 841.61
Total Source Energy 923.89 1992.86 1992.86
Net Source Energy 923.89 1992.86 1992.86


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 463.60
Net Conditioned Building Area 463.60
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 149.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 51.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 79.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 52.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 56.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 240.49 149.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 149.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 51.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 79.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 52.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 56.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 171.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 233.45 322.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Other 114.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 518.75 322.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 171.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 233.45 322.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Other 114.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 518.75 322.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 240.493 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 240.493 100.00
     
Total On-Site and Utility Electric Sources 240.493 100.00
Total Electricity End Uses 240.493 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 -
Condensate Collection 0.00 -
Groundwater Well 0.00 -
Total On Site Water Sources 0.00 -
- - -
Initial Storage 0.00 -
Final Storage 0.00 -
Change in Storage 0.00 -
- - -
Water Supplied by Utility 0.00 -
- - -
Total On Site, Change in Storage, and Utility Water Sources 0.00 -
Total Water End Uses 0.00 -


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 25.00
Time Setpoint Not Met During Occupied Cooling 2.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 238.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

General

Value
Program Version and Build EnergyPlus, Version 9.5.0-de239b2e5f, YMD=2022.03.23 15:31
RunPeriod RUN PERIOD 1
Weather File Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300
Latitude [deg] 41.98
Longitude [deg] -87.9
Elevation [m] 201.00
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 274.20 91.50 45.60 91.50 45.60
Above Ground Wall Area [m2] 274.20 91.50 45.60 91.50 45.60
Window Opening Area [m2] 61.65 20.85 9.12 22.56 9.12
Gross Window-Wall Ratio [%] 22.48 22.79 20.00 24.66 20.00
Above Ground Window-Wall Ratio [%] 22.48 22.79 20.00 24.66 20.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 219.36 73.20 36.48 73.20 36.48
Above Ground Wall Area [m2] 219.36 73.20 36.48 73.20 36.48
Window Opening Area [m2] 61.65 20.85 9.12 22.56 9.12
Gross Window-Wall Ratio [%] 28.10 28.48 25.00 30.82 25.00
Above Ground Window-Wall Ratio [%] 28.10 28.48 25.00 30.82 25.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 463.60
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
PLENUM 463.60 No No 283.20 1.00 54.84 0.00 0.00 0.00 0.0000   0.0000
SOUTH PERIMETER 99.16 Yes Yes 239.25 1.00 73.20 0.00 22.56 22.56 15.9742 9.01 10.6495
EAST PERIMETER 42.73 Yes Yes 103.31 1.00 36.48 0.00 9.12 9.12 16.0056 8.55 10.6704
NORTH PERIMETER 96.48 Yes Yes 239.25 1.00 73.20 0.00 20.85 20.85 16.4179 8.77 10.9453
WEST PERIMETER 42.74 Yes Yes 103.31 1.00 36.48 0.00 9.12 9.12 16.0056 8.55 10.6704
CORE 182.49 Yes Yes 447.68 1.00 0.00 0.00 0.00 0.00 16.2420 9.12 10.8280
Total 463.60     1132.80   219.36 0.00 61.65 61.65 16.1777 8.92 10.7852
Conditioned Total 463.60     1132.80   219.36 0.00 61.65 61.65 16.1777 8.92 10.7852
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 463.60     283.20   54.84 0.00 0.00 0.00 0.0000   0.0000



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 19-JUL-14:00 27-JAN-07:00 - - - - - - - - - - -
Heating 0.00 42811.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 13612.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 6750.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 4500.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1804.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 26666.90 42811.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 42811.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 13612.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GeneralLights 6750.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 4500.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 1804.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 162.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 162.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 251.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 167.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 180.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 761.64 162.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 349.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 350.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 542.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 361.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 388.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1642.88 349.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 349.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 350.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 542.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 361.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 388.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1642.88 349.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
SOUTH PERIMETER CV 0.439725
EAST PERIMETER CV 0.304547
NORTH PERIMETER CV 0.427659
WEST PERIMETER CV 0.353810
CORE CV 0.579179
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
SOUTH ZONE UNITARY 0.439725 0.439725 0.439725 0.439725 0.439725 0.439725 1.00 1.00 0.439725
EAST ZONE UNITARY 0.304547 0.304547 0.304547 0.304547 0.304547 0.304547 1.00 1.00 0.304547
WEST ZONE UNITARY 0.353810 0.353810 0.353810 0.353810 0.353810 0.353810 1.00 1.00 0.353810
CORE UNITARY 0.579179 0.579179 0.579179 0.579179 0.579179 0.579179 1.00 1.00 0.579179
NORTH ZONE UNITARY 0.427659 0.427659 0.427659 0.427659 0.427659 0.427659 1.00 1.00 0.427659
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SOUTH ZONE UNITARY OA CONTROLLER 0.439725 0.103840
EAST ZONE UNITARY OA CONTROLLER 0.304547 0.047200
WEST ZONE UNITARY OA CONTROLLER 0.353810 0.047200
CORE UNITARY OA CONTROLLER 0.579179 0.188800
NORTH ZONE UNITARY OA CONTROLLER 0.427659 0.103840
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Total Cooling Capacity [W] Design Size Gross Rated Sensible Heat Ratio
SOUTH ZONE UNITARY COOLING COIL 0.439725 9027.21 0.766455
EAST ZONE UNITARY COOLING COIL 0.304547 5041.34 0.800655
WEST ZONE UNITARY COOLING COIL 0.353810 6035.42 0.800775
CORE UNITARY COOLING COIL 0.579179 12792.34 0.739546
NORTH ZONE UNITARY COOLING COIL 0.427659 8856.03 0.762894
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SOUTH ZONE UNITARY FURNACE WITH DX COOLING 0.439725 0.439725 0.439725 0.439725 8507.44 9027.21 1.00
EAST ZONE UNITARY FURNACE WITH DX COOLING 0.304547 0.304547 0.304547 0.304547 3871.67 5041.34 1.00
WEST ZONE UNITARY FURNACE WITH DX COOLING 0.353810 0.353810 0.353810 0.353810 3871.67 6035.42 1.00
CORE UNITARY FURNACE WITH DX COOLING 0.579179 0.579179 0.579179 0.579179 15192.13 12792.34 1.00
NORTH ZONE UNITARY FURNACE WITH DX COOLING 0.427659 0.427659 0.427659 0.427659 8439.81 8856.03 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
SOUTH ZONE UNITARY SUPPLY FAN 0.439725
EAST ZONE UNITARY SUPPLY FAN 0.304547
WEST ZONE UNITARY SUPPLY FAN 0.353810
CORE UNITARY SUPPLY FAN 0.579179
NORTH ZONE UNITARY SUPPLY FAN 0.427659
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
SOUTH ZONE UNITARY HEATING COIL 8507.44
EAST ZONE UNITARY HEATING COIL 3871.67
WEST ZONE UNITARY HEATING COIL 3871.67
CORE UNITARY HEATING COIL 15192.13
NORTH ZONE UNITARY HEATING COIL 8439.81
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
MAIN SOUTH OVERHANG FRONT-1 |
Mir-MAIN SOUTH OVERHANG SOUTH DOOR OVERHANG | WALL-1PF | FRONT-1 |
SOUTH DOOR OVERHANG WALL-1PF |
Mir-SOUTH DOOR OVERHANG WALL-1PF |
WALL-1PF SOUTH DOOR OVERHANG |
FRONT-1 MAIN SOUTH OVERHANG | SOUTH DOOR OVERHANG |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
FRONT-1 WF-1 | DF-1 |
RIGHT-1 WR-1 |
BACK-1 WB-1 | DB-1 |
LEFT-1 WL-1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Version

Version ID
1 9.5


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 1 60


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes No No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 1 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.200 0.200


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 20.40 20.40 20.40 20.40 21.50 22.70 22.90 23.00 23.00 21.90 20.70 20.50


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 -1.89 -3.06 -0.99 2.23 10.68 17.20 21.60 22.94 20.66 15.60 8.83 2.56


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300 41.98 -87.92 -6.00 201.00 98934 1.1759


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 FixedDefault NA NA NA 10.0


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 Exercise 2A 0.000 City 4.00000E-002 0.40000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 Simple


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 SimpleCombined


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 4


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 6 46 6


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 PLENUM 0.0 0.00 0.00 0.00 15.25 7.60 2.70 1 1 1 0.00 30.50 0.00 15.20 2.40 3.00 0.61 283.20 Simple Simple 463.60 54.84 54.84 0.00 10 0 0 No
2 SOUTH PERIMETER 0.0 0.00 0.00 0.00 15.25 1.71 1.20 1 1 1 0.00 30.50 0.00 3.70 0.00 2.40 2.44 239.25 Simple Simple 99.16 73.20 50.64 22.56 6 2 4 Yes
3 EAST PERIMETER 0.0 0.00 0.00 0.00 28.95 7.62 1.20 1 1 1 26.80 30.50 0.00 15.20 0.00 2.40 2.44 103.31 Simple Simple 42.74 36.48 27.36 9.12 6 1 0 Yes
4 NORTH PERIMETER 0.0 0.00 0.00 0.00 15.25 13.54 1.20 1 1 1 0.00 30.50 11.60 15.20 0.00 2.40 2.44 239.25 Simple Simple 96.48 73.20 52.35 20.85 6 2 0 Yes
5 WEST PERIMETER 0.0 0.00 0.00 0.00 1.55 7.62 1.20 1 1 1 0.00 3.70 0.00 15.20 0.00 2.40 2.44 103.31 Simple Simple 42.74 36.48 27.36 9.12 6 1 0 Yes
6 CORE 0.0 0.00 0.00 0.00 15.25 7.65 1.20 1 1 1 3.70 26.80 3.70 11.60 0.00 2.40 2.44 447.68 Simple Simple 182.49 0.00 0.00 0.00 6 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 PLENUM 463.60 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
2 SOUTH PERIMETER 99.16 11.0 9.015 0.111 15.974 10.649 0.000 0.000 0.000 0.000 26.624 No
3 EAST PERIMETER 42.74 5.0 8.547 0.117 16.006 10.670 0.000 0.000 0.000 0.000 26.676 No
4 NORTH PERIMETER 96.48 11.0 8.771 0.114 16.418 10.945 0.000 0.000 0.000 0.000 27.363 No
5 WEST PERIMETER 42.74 5.0 8.547 0.117 16.006 10.670 0.000 0.000 0.000 0.000 26.676 No
6 CORE 182.49 20.0 9.125 0.110 16.242 10.828 0.000 0.000 0.000 0.000 27.070 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 SOUTH PERIMETER PEOPLE 1 OFFICE OCCUPANCY 2 SOUTH PERIMETER 99.16 11.0 11.0 0.111 9.015 0.300 0.700 AutoCalculate ACTSCHD No 3.8200E-008 0 10
2 EAST PERIMETER PEOPLE 1 OFFICE OCCUPANCY 2 EAST PERIMETER 42.74 5.0 5.0 0.117 8.547 0.300 0.700 AutoCalculate ACTSCHD No 3.8200E-008 0 5
3 NORTH PERIMETER PEOPLE 1 OFFICE OCCUPANCY 2 NORTH PERIMETER 96.48 11.0 11.0 0.114 8.771 0.300 0.700 AutoCalculate ACTSCHD No 3.8200E-008 0 10
4 WEST PERIMETER PEOPLE 1 OFFICE OCCUPANCY 2 WEST PERIMETER 42.74 5.0 5.0 0.117 8.547 0.300 0.700 AutoCalculate ACTSCHD No 3.8200E-008 0 5
5 CORE PEOPLE 1 OFFICE OCCUPANCY 2 CORE 182.49 20.0 20.0 0.110 9.125 0.300 0.700 AutoCalculate ACTSCHD No 3.8200E-008 0 19


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 SOUTH PERIMETER LIGHTS 1 OFFICE LIGHTING 2 SOUTH PERIMETER 99.16 11.0 1584.000 15.974 144.000 0.200 0.590 0.200 1.000E-002 0.000 GeneralLights 0.000 1425.600
2 EAST PERIMETER LIGHTS 1 OFFICE LIGHTING 2 EAST PERIMETER 42.74 5.0 684.000 16.006 136.800 0.200 0.590 0.200 1.000E-002 0.000 GeneralLights 0.000 615.600
3 NORTH PERIMETER LIGHTS 1 OFFICE LIGHTING 2 NORTH PERIMETER 96.48 11.0 1584.000 16.418 144.000 0.200 0.590 0.200 1.000E-002 0.000 GeneralLights 0.000 1425.600
4 WEST PERIMETER LIGHTS 1 OFFICE LIGHTING 2 WEST PERIMETER 42.74 5.0 684.000 16.006 136.800 0.200 0.590 0.200 1.000E-002 0.000 GeneralLights 0.000 615.600
5 CORE LIGHTS 1 OFFICE LIGHTING 2 CORE 182.49 20.0 2964.000 16.242 148.200 0.200 0.590 0.200 1.000E-002 0.000 GeneralLights 0.000 2667.600


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 SOUTH PERIMETER ELECEQ 1 OFFICE LIGHTING 2 SOUTH PERIMETER 99.16 11.0 1056.000 10.649 96.000 0.000 0.300 0.000 0.700 General 0.000 950.400
2 EAST PERIMETER ELECEQ 1 OFFICE LIGHTING 2 EAST PERIMETER 42.74 5.0 456.000 10.670 91.200 0.000 0.300 0.000 0.700 General 0.000 410.400
3 NORTH PERIMETER ELECEQ 1 OFFICE LIGHTING 2 NORTH PERIMETER 96.48 11.0 1056.000 10.945 96.000 0.000 0.300 0.000 0.700 General 0.000 950.400
4 WEST PERIMETER ELECEQ 1 OFFICE LIGHTING 2 WEST PERIMETER 42.74 5.0 456.000 10.670 91.200 0.000 0.300 0.000 0.700 General 0.000 410.400
5 CORE ELECEQ 1 OFFICE LIGHTING 2 CORE 182.49 20.0 1976.000 10.828 98.800 0.000 0.300 0.000 0.700 General 0.000 1778.400


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 SOUTH PERIMETER INFIL 1 CONSTANT SOUTH PERIMETER 99.16 11.0 3.500E-002 3.530E-004 4.781E-004 0.527 0.000 0.000 0.224 0.000
2 EAST PERIMETER INFIL 1 CONSTANT EAST PERIMETER 42.74 5.0 1.500E-002 3.510E-004 4.112E-004 0.523 0.000 0.000 0.224 0.000
3 NORTH PERIMETER INFIL 1 CONSTANT NORTH PERIMETER 96.48 11.0 3.500E-002 3.628E-004 4.781E-004 0.527 0.000 0.000 0.224 0.000
4 WEST PERIMETER INFIL 1 CONSTANT WEST PERIMETER 42.74 5.0 1.500E-002 3.510E-004 4.112E-004 0.523 0.000 0.000 0.224 0.000
5 CORE INFIL 1 CONSTANT CORE 182.49 20.0 6.200E-002 3.397E-004 N/A 0.499 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 PLENUM Mixing/Well-Stirred
2 SOUTH PERIMETER Mixing/Well-Stirred
3 EAST PERIMETER Mixing/Well-Stirred
4 NORTH PERIMETER Mixing/Well-Stirred
5 WEST PERIMETER Mixing/Well-Stirred
6 CORE Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 1


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone SOUTH PERIMETER 1.2000
3 Zone EAST PERIMETER 1.2000
4 Zone NORTH PERIMETER 1.2000
5 Zone WEST PERIMETER 1.2000
6 Zone CORE 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone SOUTH PERIMETER 1.2000
3 Zone EAST PERIMETER 1.2000
4 Zone NORTH PERIMETER 1.2000
5 Zone WEST PERIMETER 1.2000
6 Zone CORE 1.2000


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 SOUTH PERIMETER Cooling 4041.22802 4849.47363 0.36644 0.43972 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 15:00:00 31.30000 1.43934E-002 99.16000 11.00000 0.10384 0.00000
2 SOUTH PERIMETER Heating 3033.93382 3640.72059 9.03556E-002 0.10843 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 -18.10000 7.77927E-004 99.16000 11.00000 0.10384 0.00000
3 EAST PERIMETER Cooling 2799.11300 3358.93560 0.25379 0.30455 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 09:00:00 25.30500 1.43825E-002 42.73500 5.00000 4.72000E-002 0.00000
4 EAST PERIMETER Heating 1382.98195 1659.57834 4.11879E-002 4.94255E-002 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 -18.10000 7.77927E-004 42.73500 5.00000 4.72000E-002 0.00000
5 NORTH PERIMETER Cooling 3930.33045 4716.39654 0.35638 0.42766 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 15:00:00 31.30000 1.43934E-002 96.48000 11.00000 0.10384 0.00000
6 NORTH PERIMETER Heating 2976.75034 3572.10041 8.86524E-002 0.10638 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 -18.10000 7.77927E-004 96.48000 11.00000 0.10384 0.00000
7 WEST PERIMETER Cooling 3251.49710 3901.79652 0.29484 0.35381 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 17:00:00 29.77400 1.43906E-002 42.73500 5.00000 4.72000E-002 0.00000
8 WEST PERIMETER Heating 1382.98195 1659.57834 4.11879E-002 4.94255E-002 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 -18.10000 7.77927E-004 42.73500 5.00000 4.72000E-002 0.00000
9 CORE Cooling 5322.38799 6386.86559 0.48265 0.57918 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 17:00:00 29.77400 1.43906E-002 182.49000 20.00000 0.18880 0.00000
10 CORE Heating 2986.41296 3583.69555 8.89391E-002 0.18880 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 -18.10000 7.77927E-004 182.49000 20.00000 0.18880 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 SOUTH ZONE UNITARY Cooling Sensible 6177.52 0.43972 0.43972 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 05:00:00
2 SOUTH ZONE UNITARY Heating Sensible 8507.44 0.10843 0.10843 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00
3 EAST ZONE UNITARY Cooling Sensible 3617.41 0.30455 0.30455 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 05:00:00
4 EAST ZONE UNITARY Heating Sensible 3871.67 4.94255E-002 4.94255E-002 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00
5 WEST ZONE UNITARY Cooling Sensible 4404.79 0.35381 0.35381 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 05:00:00
6 WEST ZONE UNITARY Heating Sensible 3871.67 4.94255E-002 4.94255E-002 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00
7 CORE UNITARY Cooling Sensible 8453.53 0.57918 0.57918 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 05:00:00
8 CORE UNITARY Heating Sensible 15192.13 0.18880 0.18880 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 01:00:00
9 NORTH ZONE UNITARY Cooling Sensible 6044.14 0.42766 0.42766 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 05:00:00
10 NORTH ZONE UNITARY Heating Sensible 8439.81 0.10638 0.10638 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat SOUTH PERIMETER CV Design Size Maximum Air Flow Rate [m3/s] 0.43972
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat EAST PERIMETER CV Design Size Maximum Air Flow Rate [m3/s] 0.30455
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat NORTH PERIMETER CV Design Size Maximum Air Flow Rate [m3/s] 0.42766
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat WEST PERIMETER CV Design Size Maximum Air Flow Rate [m3/s] 0.35381
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE CV Design Size Maximum Air Flow Rate [m3/s] 0.57918
6 AirLoopHVAC SOUTH ZONE UNITARY Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.43972
7 AirLoopHVAC SOUTH ZONE UNITARY Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.43972
8 AirLoopHVAC SOUTH ZONE UNITARY Sum of Air Terminal Maximum Flow Rates [m3/s] 0.43972
9 AirLoopHVAC SOUTH ZONE UNITARY Adjusted Heating Design Air Flow Rate [m3/s] 0.43972
10 AirLoopHVAC SOUTH ZONE UNITARY Adjusted Cooling Design Air Flow Rate [m3/s] 0.43972
11 AirLoopHVAC SOUTH ZONE UNITARY Adjusted Main Design Air Flow Rate [m3/s] 0.43972
12 AirLoopHVAC SOUTH ZONE UNITARY User Heating Air Flow Ratio [] 1.00000
13 AirLoopHVAC SOUTH ZONE UNITARY Calculated Heating Air Flow Ratio [] 1.00000
14 AirLoopHVAC EAST ZONE UNITARY Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.30455
15 AirLoopHVAC EAST ZONE UNITARY Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.30455
16 AirLoopHVAC EAST ZONE UNITARY Sum of Air Terminal Maximum Flow Rates [m3/s] 0.30455
17 AirLoopHVAC EAST ZONE UNITARY Adjusted Heating Design Air Flow Rate [m3/s] 0.30455
18 AirLoopHVAC EAST ZONE UNITARY Adjusted Cooling Design Air Flow Rate [m3/s] 0.30455
19 AirLoopHVAC EAST ZONE UNITARY Adjusted Main Design Air Flow Rate [m3/s] 0.30455
20 AirLoopHVAC EAST ZONE UNITARY User Heating Air Flow Ratio [] 1.00000
21 AirLoopHVAC EAST ZONE UNITARY Calculated Heating Air Flow Ratio [] 1.00000
22 AirLoopHVAC WEST ZONE UNITARY Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.35381
23 AirLoopHVAC WEST ZONE UNITARY Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.35381
24 AirLoopHVAC WEST ZONE UNITARY Sum of Air Terminal Maximum Flow Rates [m3/s] 0.35381
25 AirLoopHVAC WEST ZONE UNITARY Adjusted Heating Design Air Flow Rate [m3/s] 0.35381
26 AirLoopHVAC WEST ZONE UNITARY Adjusted Cooling Design Air Flow Rate [m3/s] 0.35381
27 AirLoopHVAC WEST ZONE UNITARY Adjusted Main Design Air Flow Rate [m3/s] 0.35381
28 AirLoopHVAC WEST ZONE UNITARY User Heating Air Flow Ratio [] 1.00000
29 AirLoopHVAC WEST ZONE UNITARY Calculated Heating Air Flow Ratio [] 1.00000
30 AirLoopHVAC CORE UNITARY Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.57918
31 AirLoopHVAC CORE UNITARY Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.57918
32 AirLoopHVAC CORE UNITARY Sum of Air Terminal Maximum Flow Rates [m3/s] 0.57918
33 AirLoopHVAC CORE UNITARY Adjusted Heating Design Air Flow Rate [m3/s] 0.57918
34 AirLoopHVAC CORE UNITARY Adjusted Cooling Design Air Flow Rate [m3/s] 0.57918
35 AirLoopHVAC CORE UNITARY Adjusted Main Design Air Flow Rate [m3/s] 0.57918
36 AirLoopHVAC CORE UNITARY User Heating Air Flow Ratio [] 1.00000
37 AirLoopHVAC CORE UNITARY Calculated Heating Air Flow Ratio [] 1.00000
38 AirLoopHVAC NORTH ZONE UNITARY Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.42766
39 AirLoopHVAC NORTH ZONE UNITARY Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.42766
40 AirLoopHVAC NORTH ZONE UNITARY Sum of Air Terminal Maximum Flow Rates [m3/s] 0.42766
41 AirLoopHVAC NORTH ZONE UNITARY Adjusted Heating Design Air Flow Rate [m3/s] 0.42766
42 AirLoopHVAC NORTH ZONE UNITARY Adjusted Cooling Design Air Flow Rate [m3/s] 0.42766
43 AirLoopHVAC NORTH ZONE UNITARY Adjusted Main Design Air Flow Rate [m3/s] 0.42766
44 AirLoopHVAC NORTH ZONE UNITARY User Heating Air Flow Ratio [] 1.00000
45 AirLoopHVAC NORTH ZONE UNITARY Calculated Heating Air Flow Ratio [] 1.00000
46 AirLoopHVAC SOUTH ZONE UNITARY Design Supply Air Flow Rate [m3/s] 0.43972
47 AirLoopHVAC EAST ZONE UNITARY Design Supply Air Flow Rate [m3/s] 0.30455
48 AirLoopHVAC WEST ZONE UNITARY Design Supply Air Flow Rate [m3/s] 0.35381
49 AirLoopHVAC CORE UNITARY Design Supply Air Flow Rate [m3/s] 0.57918
50 AirLoopHVAC NORTH ZONE UNITARY Design Supply Air Flow Rate [m3/s] 0.42766
51 Controller:OutdoorAir SOUTH ZONE UNITARY OA CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.43972
52 Controller:OutdoorAir SOUTH ZONE UNITARY OA CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.10384
53 Coil:Cooling:DX:SingleSpeed SOUTH ZONE UNITARY COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.43972
54 Coil:Cooling:DX:SingleSpeed SOUTH ZONE UNITARY COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 9027.20867
55 Coil:Cooling:DX:SingleSpeed SOUTH ZONE UNITARY COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.76646
56 AirLoopHVAC:Unitary:Furnace:HeatCool SOUTH ZONE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate [m3/s] 0.43972
57 AirLoopHVAC:Unitary:Furnace:HeatCool SOUTH ZONE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate During Heating Operation [m3/s] 0.43972
58 AirLoopHVAC:Unitary:Furnace:HeatCool SOUTH ZONE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate During Cooling Operation [m3/s] 0.43972
59 AirLoopHVAC:Unitary:Furnace:HeatCool SOUTH ZONE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.43972
60 AirLoopHVAC:Unitary:Furnace:HeatCool SOUTH ZONE UNITARY FURNACE WITH DX COOLING Nominal Heating Capacity [W] 8507.44010
61 AirLoopHVAC:Unitary:Furnace:HeatCool SOUTH ZONE UNITARY FURNACE WITH DX COOLING Nominal Cooling Capacity [W] 9027.20867
62 AirLoopHVAC:Unitary:Furnace:HeatCool SOUTH ZONE UNITARY FURNACE WITH DX COOLING Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
63 Fan:OnOff SOUTH ZONE UNITARY SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.43972
64 Coil:Heating:Fuel SOUTH ZONE UNITARY HEATING COIL Design Size Nominal Capacity [W] 8507.44010
65 Controller:OutdoorAir EAST ZONE UNITARY OA CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.30455
66 Controller:OutdoorAir EAST ZONE UNITARY OA CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.72000E-002
67 Coil:Cooling:DX:SingleSpeed EAST ZONE UNITARY COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.30455
68 Coil:Cooling:DX:SingleSpeed EAST ZONE UNITARY COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5041.33701
69 Coil:Cooling:DX:SingleSpeed EAST ZONE UNITARY COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
70 AirLoopHVAC:Unitary:Furnace:HeatCool EAST ZONE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate [m3/s] 0.30455
71 AirLoopHVAC:Unitary:Furnace:HeatCool EAST ZONE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate During Heating Operation [m3/s] 0.30455
72 AirLoopHVAC:Unitary:Furnace:HeatCool EAST ZONE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate During Cooling Operation [m3/s] 0.30455
73 AirLoopHVAC:Unitary:Furnace:HeatCool EAST ZONE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.30455
74 AirLoopHVAC:Unitary:Furnace:HeatCool EAST ZONE UNITARY FURNACE WITH DX COOLING Nominal Heating Capacity [W] 3871.67023
75 AirLoopHVAC:Unitary:Furnace:HeatCool EAST ZONE UNITARY FURNACE WITH DX COOLING Nominal Cooling Capacity [W] 5041.33701
76 AirLoopHVAC:Unitary:Furnace:HeatCool EAST ZONE UNITARY FURNACE WITH DX COOLING Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
77 Fan:OnOff EAST ZONE UNITARY SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.30455
78 Coil:Heating:Fuel EAST ZONE UNITARY HEATING COIL Design Size Nominal Capacity [W] 3871.67023
79 Controller:OutdoorAir WEST ZONE UNITARY OA CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.35381
80 Controller:OutdoorAir WEST ZONE UNITARY OA CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.72000E-002
81 Coil:Cooling:DX:SingleSpeed WEST ZONE UNITARY COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.35381
82 Coil:Cooling:DX:SingleSpeed WEST ZONE UNITARY COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6035.42069
83 Coil:Cooling:DX:SingleSpeed WEST ZONE UNITARY COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80077
84 AirLoopHVAC:Unitary:Furnace:HeatCool WEST ZONE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate [m3/s] 0.35381
85 AirLoopHVAC:Unitary:Furnace:HeatCool WEST ZONE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate During Heating Operation [m3/s] 0.35381
86 AirLoopHVAC:Unitary:Furnace:HeatCool WEST ZONE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate During Cooling Operation [m3/s] 0.35381
87 AirLoopHVAC:Unitary:Furnace:HeatCool WEST ZONE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.35381
88 AirLoopHVAC:Unitary:Furnace:HeatCool WEST ZONE UNITARY FURNACE WITH DX COOLING Nominal Heating Capacity [W] 3871.67023
89 AirLoopHVAC:Unitary:Furnace:HeatCool WEST ZONE UNITARY FURNACE WITH DX COOLING Nominal Cooling Capacity [W] 6035.42069
90 AirLoopHVAC:Unitary:Furnace:HeatCool WEST ZONE UNITARY FURNACE WITH DX COOLING Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
91 Fan:OnOff WEST ZONE UNITARY SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.35381
92 Coil:Heating:Fuel WEST ZONE UNITARY HEATING COIL Design Size Nominal Capacity [W] 3871.67023
93 Controller:OutdoorAir CORE UNITARY OA CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.57918
94 Controller:OutdoorAir CORE UNITARY OA CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.18880
95 Coil:Cooling:DX:SingleSpeed CORE UNITARY COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.57918
96 Coil:Cooling:DX:SingleSpeed CORE UNITARY COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 12792.33802
97 Coil:Cooling:DX:SingleSpeed CORE UNITARY COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.73955
98 AirLoopHVAC:Unitary:Furnace:HeatCool CORE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate [m3/s] 0.57918
99 AirLoopHVAC:Unitary:Furnace:HeatCool CORE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate During Heating Operation [m3/s] 0.57918
100 AirLoopHVAC:Unitary:Furnace:HeatCool CORE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate During Cooling Operation [m3/s] 0.57918
101 AirLoopHVAC:Unitary:Furnace:HeatCool CORE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.57918
102 AirLoopHVAC:Unitary:Furnace:HeatCool CORE UNITARY FURNACE WITH DX COOLING Nominal Heating Capacity [W] 15192.13400
103 AirLoopHVAC:Unitary:Furnace:HeatCool CORE UNITARY FURNACE WITH DX COOLING Nominal Cooling Capacity [W] 12792.33802
104 AirLoopHVAC:Unitary:Furnace:HeatCool CORE UNITARY FURNACE WITH DX COOLING Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
105 Fan:OnOff CORE UNITARY SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.57918
106 Coil:Heating:Fuel CORE UNITARY HEATING COIL Design Size Nominal Capacity [W] 15192.13400
107 Controller:OutdoorAir NORTH ZONE UNITARY OA CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.42766
108 Controller:OutdoorAir NORTH ZONE UNITARY OA CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.10384
109 Coil:Cooling:DX:SingleSpeed NORTH ZONE UNITARY COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.42766
110 Coil:Cooling:DX:SingleSpeed NORTH ZONE UNITARY COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 8856.03485
111 Coil:Cooling:DX:SingleSpeed NORTH ZONE UNITARY COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.76289
112 AirLoopHVAC:Unitary:Furnace:HeatCool NORTH ZONE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate [m3/s] 0.42766
113 AirLoopHVAC:Unitary:Furnace:HeatCool NORTH ZONE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate During Heating Operation [m3/s] 0.42766
114 AirLoopHVAC:Unitary:Furnace:HeatCool NORTH ZONE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate During Cooling Operation [m3/s] 0.42766
115 AirLoopHVAC:Unitary:Furnace:HeatCool NORTH ZONE UNITARY FURNACE WITH DX COOLING Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.42766
116 AirLoopHVAC:Unitary:Furnace:HeatCool NORTH ZONE UNITARY FURNACE WITH DX COOLING Nominal Heating Capacity [W] 8439.81490
117 AirLoopHVAC:Unitary:Furnace:HeatCool NORTH ZONE UNITARY FURNACE WITH DX COOLING Nominal Cooling Capacity [W] 8856.03485
118 AirLoopHVAC:Unitary:Furnace:HeatCool NORTH ZONE UNITARY FURNACE WITH DX COOLING Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
119 Fan:OnOff NORTH ZONE UNITARY SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.42766
120 Coil:Heating:Fuel NORTH ZONE UNITARY HEATING COIL Design Size Nominal Capacity [W] 8439.81490


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed SOUTH ZONE UNITARY COOLING COIL 8685.7 2.59 8.85 9.39 8.89 9.16
2 Coil:Cooling:DX:SingleSpeed EAST ZONE UNITARY COOLING COIL 4805.0 2.51 8.56 9.08 8.59 8.70
3 Coil:Cooling:DX:SingleSpeed WEST ZONE UNITARY COOLING COIL 5760.9 2.52 8.60 9.13 8.63 8.77
4 Coil:Cooling:DX:SingleSpeed CORE UNITARY COOLING COIL 12342.4 2.62 8.94 9.49 8.98 9.30
5 Coil:Cooling:DX:SingleSpeed NORTH ZONE UNITARY COOLING COIL 8523.9 2.60 8.86 9.41 8.90 9.18


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUN PERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day Yes Yes No Yes Yes Clark and Allen


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 No      


Environment:WarmupDays

NumberofWarmupDays
1 6


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 PLENUM RunPeriod: RUN PERIOD 1 0.1192151384 8.3338245972E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 SOUTH PERIMETER RunPeriod: RUN PERIOD 1 2.0724163126E-015 2.2740759639E-015 Pass Pass 0.4826393075 1.2217383659 Pass Pass
3 EAST PERIMETER RunPeriod: RUN PERIOD 1 3.4046839422E-015 1.9129657833E-015 Pass Pass 0.3702194183 1.2838749548 Pass Pass
4 NORTH PERIMETER RunPeriod: RUN PERIOD 1 1.9243865760E-015 1.7701781882E-015 Pass Pass 4.7655192735E-002 4.1076680702E-002 Pass Pass
5 WEST PERIMETER RunPeriod: RUN PERIOD 1 2.6645352591E-015 2.3498992184E-015 Pass Pass 7.1589292970E-002 5.5379766778E-002 Pass Pass
6 CORE RunPeriod: RUN PERIOD 1 4.1448326253E-015 3.1886581122E-015 Pass Pass 5.5173091842E-002 4.2487626246E-002 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 2018.12 15.31 0.00 81.26 269.09 2383.75



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
CHICAGO_IL_USA HEATING 99% CONDITIONS -18.10 0.00 -18.10 Wetbulb [C] 4.60 270.00
CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 31.30 10.90 22.80 Wetbulb [C] 5.40 230.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
WALL-1PF WALL-1 0.22 0.384 0.408 18.30 18.30 180.00 90.00 S
WALL-1PR WALL-1 0.22 0.384 0.408 9.12 9.12 90.00 90.00 E
WALL-1PB WALL-1 0.22 0.384 0.408 18.30 18.30 0.00 90.00 N
WALL-1PL WALL-1 0.22 0.384 0.408 9.12 9.12 270.00 90.00 W
TOP-1 ROOF-1 0.35 0.271 0.282 463.60 463.60 180.00 0.00  
FRONT-1 WALL-1 0.22 0.384 0.408 73.20 50.64 180.00 90.00 S
F1-1 FLOOR-SLAB-1 0.35 4.174 12.894 99.16 99.16 0.00 180.00  
RIGHT-1 WALL-1 0.22 0.384 0.408 36.48 27.36 90.00 90.00 E
F2-1 FLOOR-SLAB-1 0.35 4.174 12.894 42.73 42.73 270.00 180.00  
BACK-1 WALL-1 0.22 0.384 0.408 73.20 52.35 0.00 90.00 N
F3-1 FLOOR-SLAB-1 0.35 4.174 12.894 96.48 96.48 44.22 180.00  
LEFT-1 WALL-1 0.22 0.384 0.408 36.48 27.36 270.00 90.00 W
F4-1 FLOOR-SLAB-1 0.35 4.174 12.894 42.74 42.74 90.00 180.00  
F5-1 FLOOR-SLAB-1 0.35 4.174 12.894 182.49 182.49 0.00 180.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
C1-1P CLNG-1 0.35 1.085 1.533 99.16 99.16 0.00 180.00  
C2-1P CLNG-1 0.35 1.085 1.533 42.73 42.73 270.00 180.00  
C3-1P CLNG-1 0.35 1.085 1.533 96.48 96.48 44.22 180.00  
C4-1P CLNG-1 0.35 1.085 1.533 42.74 42.74 90.00 180.00  
C5-1P CLNG-1 0.35 1.085 1.533 182.49 182.49 0.00 180.00  
SB12 INT-WALL-1 0.25 1.680 2.811 12.56 12.56 45.00 90.00 E
SB14 INT-WALL-1 0.25 1.680 2.811 12.56 12.56 315.00 90.00 N
SB15 INT-WALL-1 0.25 1.680 2.811 55.44 55.44 0.00 90.00 N
C1-1 CLNG-1 0.35 1.085 1.533 99.16 99.16 180.00 0.00  
SB21 INT-WALL-1 0.25 1.680 2.811 12.56 12.56 225.00 90.00 W
SB23 INT-WALL-1 0.25 1.680 2.811 12.39 12.39 315.78 90.00 N
SB25 INT-WALL-1 0.25 1.680 2.811 18.96 18.96 270.00 90.00 W
C2-1 CLNG-1 0.35 1.085 1.533 42.73 42.73 90.00 0.00  
SB32 INT-WALL-1 0.25 1.680 2.811 12.39 12.39 135.78 90.00 S
SB34 INT-WALL-1 0.25 1.680 2.811 12.39 12.39 224.22 90.00 S
SB35 INT-WALL-1 0.25 1.680 2.811 55.44 55.44 180.00 90.00 S
C3-1 CLNG-1 0.35 1.085 1.533 96.48 96.48 224.22 0.00  
SB41 INT-WALL-1 0.25 1.680 2.811 12.56 12.56 135.00 90.00 S
SB43 INT-WALL-1 0.25 1.680 2.811 12.39 12.39 44.22 90.00 N
SB45 INT-WALL-1 0.25 1.680 2.811 18.96 18.96 90.00 90.00 E
C4-1 CLNG-1 0.35 1.085 1.533 42.73 42.73 270.00 0.00  
SB51 INT-WALL-1 0.25 1.680 2.811 55.44 55.44 180.00 90.00 S
SB52 INT-WALL-1 0.25 1.680 2.811 18.96 18.96 90.00 90.00 E
SB53 INT-WALL-1 0.25 1.680 2.811 55.44 55.44 0.00 90.00 N
SB54 INT-WALL-1 0.25 1.680 2.811 18.96 18.96 270.00 90.00 W
C5-1 CLNG-1 0.35 1.085 1.533 182.49 182.49 180.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WF-1 DOUBLE LOE CLEAR ARGON 16.56 0.00 0.00 16.56 16.56 1.493 0.568 0.745     No FRONT-1 180.00 90.00 S
DF-1 DOUBLE LOE CLEAR ARGON 6.00 0.00 0.00 6.00 6.00 1.493 0.568 0.745     No FRONT-1 180.00 90.00 S
WR-1 DOUBLE LOE CLEAR ARGON 9.12 0.00 0.00 9.12 9.12 1.493 0.568 0.745     No RIGHT-1 90.00 90.00 E
WB-1 DOUBLE LOE CLEAR ARGON 16.44 0.00 0.00 16.44 16.44 1.493 0.568 0.745     No BACK-1 0.00 90.00 N
DB-1 DOUBLE LOE CLEAR ARGON 4.41 0.00 0.00 4.41 4.41 1.493 0.568 0.745     No BACK-1 0.00 90.00 N
WL-1 DOUBLE LOE CLEAR ARGON 9.12 0.00 0.00 9.12 9.12 1.493 0.568 0.745     No LEFT-1 270.00 90.00 W
Total or Average           61.65 1.493 0.568 0.745              
North Total or Average           20.85 1.493 0.568 0.745              
Non-North Total or Average           40.80 1.493 0.568 0.745              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
None                  


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
SOUTH PERIMETER LIGHTS 1 SOUTH PERIMETER 15.9742 99.16 1584.00 GeneralLights OFFICE LIGHTING 2 56.37 167.98 56.37 0.2000 Y 16.76
EAST PERIMETER LIGHTS 1 EAST PERIMETER 16.0056 42.73 684.00 GeneralLights OFFICE LIGHTING 2 56.37 167.98 56.37 0.2000 Y 7.24
NORTH PERIMETER LIGHTS 1 NORTH PERIMETER 16.4179 96.48 1584.00 GeneralLights OFFICE LIGHTING 2 56.37 167.98 56.37 0.2000 Y 16.76
WEST PERIMETER LIGHTS 1 WEST PERIMETER 16.0056 42.74 684.00 GeneralLights OFFICE LIGHTING 2 56.37 167.98 56.37 0.2000 Y 7.24
CORE LIGHTS 1 CORE 16.2420 182.49 2964.00 GeneralLights OFFICE LIGHTING 2 56.37 167.98 56.37 0.2000 Y 31.36
Interior Lighting Total   16.1777 463.60 7500.00               79.36


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
Exterior Lighting Total 0.00           0.00



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
SOUTH ZONE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed   9027.21 6918.95 2108.26 0.77 3.00    
EAST ZONE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed   5041.34 4036.37 1004.96 0.80 3.00    
WEST ZONE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed   6035.42 4833.01 1202.41 0.80 3.00    
CORE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed   12792.34 9460.53 3331.81 0.74 3.00    
NORTH ZONE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed   8856.03 6756.21 2099.82 0.76 3.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
SOUTH ZONE UNITARY COOLING COIL   8685.7 2.59 8.85 9.39 8.89 9.16
EAST ZONE UNITARY COOLING COIL   4805.0 2.51 8.56 9.08 8.59 8.70
WEST ZONE UNITARY COOLING COIL   5760.9 2.52 8.60 9.13 8.63 8.77
CORE UNITARY COOLING COIL   12342.4 2.62 8.94 9.49 8.98 9.30
NORTH ZONE UNITARY COOLING COIL   8523.9 2.60 8.86 9.41 8.90 9.18
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
SOUTH ZONE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed                
EAST ZONE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed                
WEST ZONE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed                
CORE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed                
NORTH ZONE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
SOUTH ZONE UNITARY HEATING COIL Coil:Heating:Fuel   8507.44 0.80
EAST ZONE UNITARY HEATING COIL Coil:Heating:Fuel   3871.67 0.80
WEST ZONE UNITARY HEATING COIL Coil:Heating:Fuel   3871.67 0.80
CORE UNITARY HEATING COIL Coil:Heating:Fuel   15192.13 0.80
NORTH ZONE UNITARY HEATING COIL Coil:Heating:Fuel   8439.81 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
SOUTH ZONE UNITARY SUPPLY FAN Fan:OnOff 0.70 600.00 0.44 376.91 857.14 1.00 2.12 General CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00
EAST ZONE UNITARY SUPPLY FAN Fan:OnOff 0.70 600.00 0.30 261.04 857.14 1.00 2.40 General CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00
WEST ZONE UNITARY SUPPLY FAN Fan:OnOff 0.70 600.00 0.35 303.27 857.14 1.00 2.27 General CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00
CORE UNITARY SUPPLY FAN Fan:OnOff 0.70 600.00 0.58 496.44 857.14 1.00 1.96 General CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 01:00:00
NORTH ZONE UNITARY SUPPLY FAN Fan:OnOff 0.70 600.00 0.43 366.56 857.14 1.00 2.14 General CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
None                


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
None            



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
SOUTH PERIMETER 4041.23 4849.47 48.91 0.366 0.440 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 15:00:00 22.00 22.00 0.00851 31.30 0.01439 0.104 0.00
EAST PERIMETER 2799.11 3358.94 78.60 0.254 0.305 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 09:00:00 22.00 22.00 0.00823 25.30 0.01438 0.047 0.00
NORTH PERIMETER 3930.33 4716.40 48.88 0.356 0.428 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 15:00:00 22.00 22.00 0.00852 31.30 0.01439 0.104 0.00
WEST PERIMETER 3251.50 3901.80 91.30 0.295 0.354 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 17:00:00 22.00 22.00 0.00831 29.77 0.01439 0.047 0.00
CORE 5322.39 6386.87 35.00 0.483 0.579 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 17:00:00 22.00 22.00 0.00871 29.77 0.01439 0.189 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
SOUTH PERIMETER 3033.93 3640.72 36.72 0.090 0.108 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 22.00 22.00 0.00733 -18.10 0.00078 0.104 0.00
EAST PERIMETER 1382.98 1659.58 38.83 0.041 0.049 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 22.00 22.00 0.00737 -18.10 0.00078 0.047 0.00
NORTH PERIMETER 2976.75 3572.10 37.02 0.089 0.106 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 22.00 22.00 0.00732 -18.10 0.00078 0.104 0.00
WEST PERIMETER 1382.98 1659.58 38.83 0.041 0.049 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 22.00 22.00 0.00737 -18.10 0.00078 0.047 0.00
CORE 2986.41 3583.70 19.64 0.089 0.189 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 22.00 22.00 0.00688 -18.10 0.00078 0.189 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
SOUTH ZONE UNITARY 0.44 0.44 0.11 0.11 0.4397 0.4397 0.4397 1.0000 1.0000
EAST ZONE UNITARY 0.30 0.30 0.05 0.05 0.3045 0.3045 0.3045 1.0000 1.0000
WEST ZONE UNITARY 0.35 0.35 0.05 0.05 0.3538 0.3538 0.3538 1.0000 1.0000
CORE UNITARY 0.58 0.58 0.19 0.19 0.5792 0.5792 0.5792 1.0000 1.0000
NORTH ZONE UNITARY 0.43 0.43 0.11 0.11 0.4277 0.4277 0.4277 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
SOUTH ZONE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC SOUTH ZONE UNITARY 9027.209 6918.952 0.439725 -999.0 -999.000 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 15:00:00 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 15:00:00 9187.13 6988.25 0.439725 25.40 17.78 0.00989641 12.80 11.39 0.00800000 31.30 0.01439335 22.81 23.6148 22.00 0.00850617 50.4756 4041.23 0.00 8951.58 6916.76
SOUTH ZONE UNITARY HEATING COIL Coil:Heating:Fuel AirLoopHVAC SOUTH ZONE UNITARY 8507.440 8507.440 -999.0 -999.0 -999.000 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 8507.44 8507.44 0.439725 12.53 8.92 0.00578366 50.00 23.69 0.00800000 -18.10 0.00077793 -18.10 23.6148 22.00 0.00733120 43.5868 3033.93 0.00 -999.00 -999.00
EAST ZONE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC EAST ZONE UNITARY 5041.337 4036.373 0.304547 -999.0 -999.000 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 10:00:00 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 09:00:00 4999.14 4086.16 0.304547 23.57 16.57 0.00918404 12.80 11.39 0.00800000 25.30 0.01438252 21.11 15.4984 22.00 0.00833542 49.4753 2765.23 0.00 4999.10 4036.00
EAST ZONE UNITARY HEATING COIL Coil:Heating:Fuel AirLoopHVAC EAST ZONE UNITARY 3871.670 3871.670 -999.0 -999.0 -999.000 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 3871.67 3871.67 0.304547 15.78 10.95 0.00634639 50.00 23.69 0.00800000 -18.10 0.00077793 -18.10 15.4984 22.00 0.00736770 43.8006 1382.98 0.00 -999.00 -999.00
WEST ZONE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC WEST ZONE UNITARY 6035.421 4833.012 0.353810 -999.0 -999.000 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 17:00:00 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 17:00:00 6265.38 5204.34 0.353810 24.05 16.69 0.00911954 12.80 11.39 0.00800000 29.77 0.01439058 22.39 13.3405 22.00 0.00830811 49.3171 3251.50 0.00 5984.85 4833.22
WEST ZONE UNITARY HEATING COIL Coil:Heating:Fuel AirLoopHVAC WEST ZONE UNITARY 3871.670 3871.670 -999.0 -999.0 -999.000 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 3871.67 3871.67 0.353810 16.65 11.46 0.00648859 50.00 23.69 0.00800000 -18.10 0.00077793 -18.10 13.3405 22.00 0.00736770 43.8006 1382.98 0.00 -999.00 -999.00
CORE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC CORE UNITARY 12792.338 9460.528 0.579179 -999.0 -999.000 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 15:00:00 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 17:00:00 12514.47 8862.65 0.579179 25.86 18.46 0.01055874 12.80 11.39 0.00800000 29.77 0.01439058 22.39 32.5979 22.00 0.00869400 51.5759 5226.36 0.00 12685.16 9454.79
CORE UNITARY HEATING COIL Coil:Heating:Fuel AirLoopHVAC CORE UNITARY 15192.134 15192.134 -999.0 -999.0 -999.000 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 01:00:00 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 01:00:00 15192.13 15192.13 0.579179 8.93 6.18 0.00489043 50.00 23.69 0.00800000 -18.10 0.00077793 -18.10 32.5979 22.00 0.00687937 40.9309 2986.40 0.00 -999.00 -999.00
NORTH ZONE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC NORTH ZONE UNITARY 8856.035 6756.212 0.427659 -999.0 -999.000 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 15:00:00 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 15:00:00 8993.54 6806.59 0.427659 25.47 17.85 0.00994555 12.80 11.39 0.00800000 31.30 0.01439335 22.81 24.2810 22.00 0.00851925 50.5523 3930.33 0.00 8781.84 6754.63
NORTH ZONE UNITARY HEATING COIL Coil:Heating:Fuel AirLoopHVAC NORTH ZONE UNITARY 8439.815 8439.815 -999.0 -999.0 -999.000 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 8439.81 8439.81 0.427659 12.26 8.74 0.00573118 50.00 23.69 0.00800000 -18.10 0.00077793 -18.10 24.2810 22.00 0.00731956 43.5185 2976.75 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
SOUTH ZONE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC SOUTH ZONE UNITARY SOUTH PERIMETER Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 9027.209 6918.952 0.439725 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.2369 1004.8586 1.1759 SOUTH ZONE UNITARY SUPPLY FAN Fan:OnOff 0.439725 0.51706547   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 15:00:00 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 15:00:00 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 15:00:00 Sensible 9187.13 6988.25 0.9826 0.51706547 0.439725 25.40 17.78 0.00989641 50742.5 12.80 11.39 0.00800000 33059.8 -999.0 -999.00 -999.00 -999.00 376.907 8810.22 31.30 0.01439335 22.81 0.10384000 23.6148 22.65 0.00850617 22.00 0.00850617 50.4756 4041.23 0.00 8951.58 6916.76 0.49664530 26.67 19.44 0.01118466 55322.4 13.05 13.05 0.00957828 37298.3
SOUTH ZONE UNITARY HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC SOUTH ZONE UNITARY SOUTH PERIMETER Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 8507.440 8507.440 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1759 SOUTH ZONE UNITARY SUPPLY FAN Fan:OnOff 0.439725 0.51706547   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 unknown unknown CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 Sensible 8507.44 8507.44 1.0000 0.51706547 0.439725 12.53 8.92 0.00578366 27187.9 50.00 23.69 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 8507.44 -18.10 0.00077793 -18.10 0.10384000 23.6148 22.00 0.00733120 22.00 0.00733120 43.5868 3033.93 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
EAST ZONE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC EAST ZONE UNITARY EAST PERIMETER Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5041.337 4036.373 0.304547 -999.0 -999.000 -999.0000 1.03832 1.00000 1021.9127 1004.8586 1.1759 EAST ZONE UNITARY SUPPLY FAN Fan:OnOff 0.304547 0.35811235   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 10:00:00 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 10:00:00 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 09:00:00 Sensible 4999.14 4086.16 1.0084 0.35811235 0.304547 23.57 16.57 0.00918404 47050.9 12.80 11.39 0.00800000 33059.8 -999.0 -999.00 -999.00 -999.00 261.040 4738.10 25.30 0.01438252 21.11 0.04720000 15.4984 22.40 0.00823059 22.00 0.00833542 49.4753 2765.23 0.00 4999.10 4036.00 0.34396962 26.67 19.44 0.01118466 55322.4 15.20 14.57 0.01008687 40788.8
EAST ZONE UNITARY HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC EAST ZONE UNITARY EAST PERIMETER Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3871.670 3871.670 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1759 EAST ZONE UNITARY SUPPLY FAN Fan:OnOff 0.304547 0.35811235   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 unknown unknown CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 Sensible 3871.67 3871.67 1.0000 0.35811235 0.304547 15.78 10.95 0.00634639 31917.1 50.00 23.69 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 3871.67 -18.10 0.00077793 -18.10 0.04720000 15.4984 22.00 0.00736770 22.00 0.00736770 43.8006 1382.98 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
WEST ZONE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC WEST ZONE UNITARY WEST PERIMETER Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6035.421 4833.012 0.353810 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.7928 1004.8586 1.1759 WEST ZONE UNITARY SUPPLY FAN Fan:OnOff 0.353810 0.41603921   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 17:00:00 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 17:00:00 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 17:00:00 Sensible 6265.38 5204.34 0.9633 0.41603921 0.353810 24.05 16.69 0.00911954 47381.2 12.80 11.39 0.00800000 33059.8 -999.0 -999.00 -999.00 -999.00 303.265 5962.12 29.77 0.01439058 22.39 0.04720000 13.3405 22.35 0.00830811 22.00 0.00830811 49.3171 3251.50 0.00 5984.85 4833.22 0.39960880 26.67 19.44 0.01118466 55322.4 14.85 14.40 0.01005474 40345.6
WEST ZONE UNITARY HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC WEST ZONE UNITARY WEST PERIMETER Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3871.670 3871.670 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1759 WEST ZONE UNITARY SUPPLY FAN Fan:OnOff 0.353810 0.41603921   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 unknown unknown CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 Sensible 3871.67 3871.67 1.0000 0.41603921 0.353810 16.65 11.46 0.00648859 33156.8 50.00 23.69 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 3871.67 -18.10 0.00077793 -18.10 0.04720000 13.3405 22.00 0.00736770 22.00 0.00736770 43.8006 1382.98 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
CORE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CORE UNITARY CORE Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 12792.338 9460.528 0.579179 -999.0 -999.000 -999.0000 1.00000 1.00000 1024.4682 1004.8586 1.1759 CORE UNITARY SUPPLY FAN Fan:OnOff 0.579179 0.68104758   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 15:00:00 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 15:00:00 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 17:00:00 Sensible 12514.47 8862.65 1.0222 0.68104758 0.579179 25.86 18.46 0.01055874 52903.7 12.80 11.39 0.00800000 33059.8 -999.0 -999.00 -999.00 -999.00 496.439 12018.03 29.77 0.01439058 22.39 0.18880000 32.5979 22.92 0.00870553 22.00 0.00869400 51.5759 5226.36 0.00 12685.16 9454.79 0.65415135 26.67 19.44 0.01118466 55322.4 12.52 12.52 0.00924848 35930.6
CORE UNITARY HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC CORE UNITARY CORE Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 15192.134 15192.134 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1759 CORE UNITARY SUPPLY FAN Fan:OnOff 0.579179 0.68104758   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 01:00:00 unknown unknown CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 01:00:00 Sensible 15192.13 15192.13 1.0000 0.68104758 0.579179 8.93 6.18 0.00489043 21280.8 50.00 23.69 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 15192.13 -18.10 0.00077793 -18.10 0.18880000 32.5979 22.00 0.00687938 22.00 0.00687937 40.9309 2986.40 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
NORTH ZONE UNITARY COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC NORTH ZONE UNITARY NORTH PERIMETER Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 8856.035 6756.212 0.427659 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.3283 1004.8586 1.1759 NORTH ZONE UNITARY SUPPLY FAN Fan:OnOff 0.427659 0.50287738   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 15:00:00 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 15:00:00 CHICAGO_IL_USA COOLING 1% CONDITIONS DB=>MWB 7/21 15:00:00 Sensible 8993.54 6806.59 0.9847 0.50287738 0.427659 25.47 17.85 0.00994555 50940.8 12.80 11.39 0.00800000 33059.8 -999.0 -999.00 -999.00 -999.00 366.565 8626.98 31.30 0.01439335 22.81 0.10384000 24.2810 22.66 0.00851925 22.00 0.00851925 50.5523 3930.33 0.00 8781.84 6754.63 0.48301752 26.67 19.44 0.01118466 55322.4 12.99 12.99 0.00953913 37141.2
NORTH ZONE UNITARY HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC NORTH ZONE UNITARY NORTH PERIMETER Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 8439.815 8439.815 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1759 NORTH ZONE UNITARY SUPPLY FAN Fan:OnOff 0.427659 0.50287738   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 unknown unknown CHICAGO_IL_USA HEATING 99% CONDITIONS 1/21 24:00:00 Sensible 8439.81 8439.81 1.0000 0.50287738 0.427659 12.26 8.74 0.00573118 26784.1 50.00 23.69 0.00800000 70993.1 -999.0 -999.00 -999.00 -999.00 0.000 8439.81 -18.10 0.00077793 -18.10 0.10384000 24.2810 22.00 0.00731956 22.00 0.00731956 43.5185 2976.75 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
SOUTH PERIMETER 156.00 4472.00 156.00
EAST PERIMETER 164.00 4357.00 156.00
NORTH PERIMETER 213.00 4469.00 213.00
WEST PERIMETER 237.00 4214.00 164.00
CORE 74.00 4472.00 74.00
PLENUM 0.00 0.00 0.00
Facility 319.00 4472.00 238.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
SOUTH PERIMETER 2.00 1.00 2.00 0.00
EAST PERIMETER 7.00 5.00 7.00 0.00
NORTH PERIMETER 1.00 2.00 1.00 1.00
WEST PERIMETER 13.00 19.00 13.00 0.00
CORE 4.00 3.00 4.00 2.00
PLENUM 0.00 0.00 0.00 0.00
Facility 25.00 26.00 25.00 2.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
SOUTH PERIMETER 6.01 11.00 239.25 1.583 0.136 0.000 0.000
EAST PERIMETER 2.73 5.00 103.31 1.666 0.135 0.000 0.000
NORTH PERIMETER 6.01 11.00 239.25 1.583 0.136 0.000 0.000
WEST PERIMETER 2.73 5.00 103.31 1.666 0.135 0.000 0.000
CORE 10.92 20.00 447.68 1.538 0.129 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
SOUTH PERIMETER 6.01 11.00 239.25 1.535 0.000 0.000 0.000
EAST PERIMETER 2.73 5.00 103.31 1.616 0.000 0.000 0.000
NORTH PERIMETER 6.01 11.00 239.25 1.535 0.000 0.000 0.000
WEST PERIMETER 2.73 5.00 103.31 1.616 0.000 0.000 0.000
CORE 10.92 20.00 447.68 1.491 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
SOUTH PERIMETER SOUTH ZONE UNITARY 6.01 11.00 239.25 99.16 0.1038 0.000
EAST PERIMETER EAST ZONE UNITARY 2.73 5.00 103.31 42.73 0.0472 0.000
NORTH PERIMETER NORTH ZONE UNITARY 6.01 11.00 239.25 96.48 0.1038 0.000
WEST PERIMETER WEST ZONE UNITARY 2.73 5.00 103.31 42.74 0.0472 0.000
CORE CORE UNITARY 10.92 20.00 447.68 182.49 0.1888 0.000
Total Facility   28.39 52.00 1132.80 463.60 0.4909 0.000


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
SOUTH PERIMETER 1671740.93 0.00 1671740.93 257834.53 1929575.46 910710.03 0.00 0.00 4472.00 0.00
EAST PERIMETER 759882.24 0.00 759882.24 110500.51 870382.75 413959.10 0.00 0.00 4472.00 0.00
NORTH PERIMETER 1671740.93 0.00 1671740.93 257834.53 1929575.46 910710.03 0.00 0.00 4472.00 0.00
WEST PERIMETER 759882.24 0.00 759882.24 110500.51 870382.75 413959.10 0.00 0.00 4472.00 0.00
CORE 3039528.96 0.00 3039528.96 456735.46 3496264.42 1655836.42 0.00 0.00 4472.00 0.00
Total Facility 7902775.30 0.00 7902775.30 1193405.55 9096180.85 4305174.68 0.00 0.00 4472.00 0.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
SOUTH PERIMETER 0.1038 0.0000 0.1038 0.0089 0.1128 0.0566 0.00 0.00 4472.00
EAST PERIMETER 0.0472 0.0000 0.0472 0.0038 0.0510 0.0257 0.00 0.00 4472.00
NORTH PERIMETER 0.1038 0.0000 0.1038 0.0089 0.1128 0.0566 0.00 0.00 4472.00
WEST PERIMETER 0.0472 0.0000 0.0472 0.0038 0.0510 0.0257 0.00 0.00 4472.00
CORE 0.1888 0.0000 0.1888 0.0158 0.2046 0.1029 0.00 0.00 4472.00
Total Facility 0.4909 0.0000 0.4909 0.0414 0.5322 0.2674 0.00 0.00 4472.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
SOUTH ZONE UNITARY 2311524.16 0.00 2311524.16 910710.03 0.00 0.00 4472.00 0.00
EAST ZONE UNITARY 1050692.80 0.00 1050692.80 413959.10 0.00 0.00 4472.00 0.00
WEST ZONE UNITARY 1050692.80 0.00 1050692.80 413959.10 0.00 0.00 4472.00 0.00
CORE UNITARY 4202771.21 0.00 4202771.21 1655836.42 0.00 0.00 4472.00 0.00
NORTH ZONE UNITARY 2311524.16 0.00 2311524.16 910710.03 0.00 0.00 4472.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
SOUTH ZONE UNITARY 0.1436 0.0000 0.1436 0.0566 0.00 0.00 4472.00
EAST ZONE UNITARY 0.0653 0.0000 0.0653 0.0257 0.00 0.00 4472.00
WEST ZONE UNITARY 0.0653 0.0000 0.0653 0.0257 0.00 0.00 4472.00
CORE UNITARY 0.2611 0.0000 0.2611 0.1029 0.00 0.00 4472.00
NORTH ZONE UNITARY 0.1436 0.0000 0.1436 0.0566 0.00 0.00 4472.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
SOUTH ZONE UNITARY 0.00 4472.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
EAST ZONE UNITARY 0.00 4472.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WEST ZONE UNITARY 0.00 4472.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE UNITARY 0.00 4472.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
NORTH ZONE UNITARY 0.00 4472.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
SOUTH ZONE UNITARY 0.0000 0.1436 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
EAST ZONE UNITARY 0.0000 0.0653 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
WEST ZONE UNITARY 0.0000 0.0653 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CORE UNITARY 0.0000 0.2611 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
NORTH ZONE UNITARY 0.0000 0.1436 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Surfaces by Class

Total Outdoors
Wall 24 8
Floor 10 5
Roof 6 1
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 6 6
Door 0 0
Glass Door 0 0
Shading 4 4
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 5
Conditioned Zones 5
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 353
Defaulted Fields 294
Fields with Defaults 1114
Autosized Fields 85
Autosizable Fields 105
Autocalculated Fields 11
Autocalculatable Fields 117



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 240.49 2429.22 04-DEC-24:00 26666.90 19-JUL-15:00
Electricity:Building 132.26 625.00 01-JAN-01:00 11250.00 02-JAN-09:00
Electricity:Zone:SOUTH PERIMETER 27.93 132.00 01-JAN-01:00 2376.00 02-JAN-09:00
InteriorLights:Electricity 79.36 375.00 01-JAN-01:00 6750.00 02-JAN-09:00
InteriorLights:Electricity:Zone:SOUTH PERIMETER 16.76 79.20 01-JAN-01:00 1425.60 02-JAN-09:00
GeneralLights:InteriorLights:Electricity 79.36 375.00 01-JAN-01:00 6750.00 02-JAN-09:00
Electricity:Zone:EAST PERIMETER 12.06 57.00 01-JAN-01:00 1026.00 02-JAN-09:00
InteriorLights:Electricity:Zone:EAST PERIMETER 7.24 34.20 01-JAN-01:00 615.60 02-JAN-09:00
Electricity:Zone:NORTH PERIMETER 27.93 132.00 01-JAN-01:00 2376.00 02-JAN-09:00
InteriorLights:Electricity:Zone:NORTH PERIMETER 16.76 79.20 01-JAN-01:00 1425.60 02-JAN-09:00
Electricity:Zone:WEST PERIMETER 12.06 57.00 01-JAN-01:00 1026.00 02-JAN-09:00
InteriorLights:Electricity:Zone:WEST PERIMETER 7.24 34.20 01-JAN-01:00 615.60 02-JAN-09:00
Electricity:Zone:CORE 52.27 247.00 01-JAN-01:00 4446.00 02-JAN-09:00
InteriorLights:Electricity:Zone:CORE 31.36 148.20 01-JAN-01:00 2667.60 02-JAN-09:00
InteriorEquipment:Electricity 52.91 250.00 01-JAN-01:00 4500.00 02-JAN-09:00
InteriorEquipment:Electricity:Zone:SOUTH PERIMETER 11.17 52.80 01-JAN-01:00 950.40 02-JAN-09:00
General:InteriorEquipment:Electricity 52.91 250.00 01-JAN-01:00 4500.00 02-JAN-09:00
InteriorEquipment:Electricity:Zone:EAST PERIMETER 4.82 22.80 01-JAN-01:00 410.40 02-JAN-09:00
InteriorEquipment:Electricity:Zone:NORTH PERIMETER 11.17 52.80 01-JAN-01:00 950.40 02-JAN-09:00
InteriorEquipment:Electricity:Zone:WEST PERIMETER 4.82 22.80 01-JAN-01:00 410.40 02-JAN-09:00
InteriorEquipment:Electricity:Zone:CORE 20.91 98.80 01-JAN-01:00 1778.40 02-JAN-09:00
ElectricityPurchased:Facility 240.49 2429.22 01-JAN-01:00 26666.90 19-JUL-15:00
ElectricityPurchased:Plant 240.49 2429.22 01-JAN-01:00 26666.90 19-JUL-15:00
Cogeneration:ElectricityPurchased 240.49 2429.22 01-JAN-01:00 26666.90 19-JUL-15:00
General:Cogeneration:ElectricityPurchased 240.49 2429.22 01-JAN-01:00 26666.90 19-JUL-15:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-01:00 0.00 01-JAN-01:00
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-01:00 0.00 01-JAN-01:00
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-01:00 0.00 01-JAN-01:00
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-01:00 0.00 01-JAN-01:00
ElectricityNet:Facility 240.49 2429.22 01-JAN-01:00 26666.90 19-JUL-15:00
ElectricityNet:Plant 240.49 2429.22 01-JAN-01:00 26666.90 19-JUL-15:00
Cogeneration:ElectricityNet 240.49 2429.22 01-JAN-01:00 26666.90 19-JUL-15:00
General:Cogeneration:ElectricityNet 240.49 2429.22 01-JAN-01:00 26666.90 19-JUL-15:00
Electricity:HVAC 108.23 1804.22 29-MAR-19:00 15416.90 19-JUL-15:00
Fans:Electricity 56.90 1804.22 29-MAR-19:00 1804.22 05-JAN-11:00
General:Fans:Electricity 56.90 1804.22 29-MAR-19:00 1804.22 05-JAN-11:00
Heating:Electricity 0.00 0.00 01-JAN-01:00 0.00 01-JAN-01:00
General:Heating:Electricity 0.00 0.00 01-JAN-01:00 0.00 01-JAN-01:00
Cooling:Electricity 51.33 0.00 01-JAN-01:00 13612.69 19-JUL-15:00
General:Cooling:Electricity 51.33 0.00 01-JAN-01:00 13612.69 19-JUL-15:00


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 149.68 0.00 16-JAN-14:00 42811.36 27-JAN-08:00
NaturalGas:HVAC 149.68 0.00 16-JAN-14:00 42811.36 27-JAN-08:00
Heating:NaturalGas 149.68 0.00 16-JAN-14:00 42811.36 27-JAN-08:00
General:Heating:NaturalGas 149.68 0.00 16-JAN-14:00 42811.36 27-JAN-08:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-01:00 0.000 01-JAN-01:00
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-01:00 0.000 01-JAN-01:00


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 453.17 762.24 11-APR-22:00 61076.05 19-JUL-17:00
EnergyTransfer:Building 180.20 94.76 30-MAY-06:00 19298.49 17-JUL-16:00
EnergyTransfer:Zone:PLENUM 0.00 0.00 01-JAN-01:00 0.00 01-JAN-01:00
Heating:EnergyTransfer 61.60 0.00 02-JAN-09:00 13507.35 27-JAN-01:00
Heating:EnergyTransfer:Zone:PLENUM 0.00 0.00 01-JAN-01:00 0.00 01-JAN-01:00
General:Heating:EnergyTransfer 61.60 0.00 02-JAN-09:00 13507.35 27-JAN-01:00
Cooling:EnergyTransfer 118.59 0.00 01-JAN-01:00 19298.49 17-JUL-16:00
Cooling:EnergyTransfer:Zone:PLENUM 0.00 0.00 01-JAN-01:00 0.00 01-JAN-01:00
General:Cooling:EnergyTransfer 118.59 0.00 01-JAN-01:00 19298.49 17-JUL-16:00
EnergyTransfer:Zone:SOUTH PERIMETER 42.48 5.24 26-OCT-20:00 4397.77 17-JUL-15:00
Heating:EnergyTransfer:Zone:SOUTH PERIMETER 15.71 0.00 01-JAN-11:00 3432.11 27-JAN-01:00
Cooling:EnergyTransfer:Zone:SOUTH PERIMETER 26.77 0.00 01-JAN-01:00 4397.77 17-JUL-15:00
EnergyTransfer:Zone:EAST PERIMETER 21.88 1.53 11-MAR-14:00 2854.91 06-JUL-09:00
Heating:EnergyTransfer:Zone:EAST PERIMETER 7.19 0.00 02-JAN-09:00 1549.40 27-JAN-01:00
Cooling:EnergyTransfer:Zone:EAST PERIMETER 14.69 0.00 01-JAN-01:00 2854.91 06-JUL-09:00
EnergyTransfer:Zone:NORTH PERIMETER 41.15 5.16 21-OCT-08:00 4409.33 17-JUL-16:00
Heating:EnergyTransfer:Zone:NORTH PERIMETER 16.21 0.00 02-JAN-09:00 3373.31 27-JAN-01:00
Cooling:EnergyTransfer:Zone:NORTH PERIMETER 24.93 0.00 01-JAN-01:00 4409.33 17-JUL-16:00
EnergyTransfer:Zone:WEST PERIMETER 21.82 1.32 10-JUN-24:00 3223.14 18-AUG-17:00
Heating:EnergyTransfer:Zone:WEST PERIMETER 7.28 0.00 02-JAN-09:00 1549.29 27-JAN-01:00
Cooling:EnergyTransfer:Zone:WEST PERIMETER 14.54 0.00 01-JAN-01:00 3223.14 18-AUG-17:00
EnergyTransfer:Zone:CORE 52.87 4.42 29-OCT-17:00 5623.75 17-JUL-16:00
Heating:EnergyTransfer:Zone:CORE 15.22 0.00 02-JAN-09:00 3603.25 27-JAN-01:00
Cooling:EnergyTransfer:Zone:CORE 37.65 0.00 01-JAN-01:00 5623.75 17-JUL-16:00
EnergyTransfer:HVAC 272.97 277.44 18-APR-04:00 43333.37 19-JUL-17:00
HeatingCoils:EnergyTransfer 102.44 0.00 16-JAN-14:00 33113.23 27-JAN-08:00
CoolingCoils:EnergyTransfer 170.53 0.00 01-JAN-01:00 43333.37 19-JUL-17:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
SOUTH PERIMETER 0.000 0.000 15.707 -26.776 0.000 0.000 7.530 16.760 11.174 16.639 0.000 0.236 0.000 0.000 -8.271 0.000 -4.049 -28.950
EAST PERIMETER 0.000 0.000 7.185 -14.695 0.000 0.000 3.423 7.237 4.825 12.129 0.000 0.101 0.000 0.000 -3.382 0.000 -1.735 -15.087
NORTH PERIMETER 0.000 0.000 16.213 -24.934 0.000 0.000 7.530 16.760 11.174 12.071 0.000 0.236 0.000 0.000 -8.067 0.000 -4.049 -26.935
WEST PERIMETER 0.000 0.000 7.279 -14.541 0.000 0.000 3.423 7.237 4.825 11.791 0.000 0.101 0.000 0.000 -3.463 0.000 -1.735 -14.919
CORE 0.000 0.000 15.217 -37.656 0.000 0.000 13.690 31.362 20.908 0.000 0.000 0.418 0.000 0.000 0.000 0.000 -7.172 -36.768
PLENUM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -0.000
Total Facility 0.000 0.000 61.602 -118.602 0.000 0.000 35.595 79.358 52.906 52.631 0.000 1.092 0.000 0.000 -23.183 0.000 -18.740 -122.659


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
SOUTH PERIMETER 17-JUL-14:20 0.00 0.00 0.00 -4416.02 0.00 0.00 815.59 1425.60 950.40 1942.56 0.00 181.73 0.00 0.00 -0.00 0.00 0.00 -899.86
EAST PERIMETER 06-JUL-08:30 0.00 0.00 0.00 -2856.57 0.00 0.00 370.69 615.60 410.40 3638.43 0.00 42.03 0.00 0.00 -0.00 0.00 0.00 -2220.58
NORTH PERIMETER 17-JUL-16:00 0.00 0.00 0.00 -4411.44 0.00 0.00 808.93 1425.60 950.40 1805.70 0.00 197.37 0.00 0.00 -0.00 0.00 0.00 -776.56
WEST PERIMETER 18-AUG-16:30 0.00 0.00 0.00 -3222.94 0.00 0.00 370.69 615.60 410.40 3939.66 0.00 6.54 0.00 0.00 -0.00 0.00 0.00 -2119.94
CORE 17-JUL-16:00 0.00 0.00 0.00 -5625.36 0.00 0.00 1474.80 2667.60 1778.40 0.00 0.00 349.74 0.00 0.00 -0.00 0.00 0.00 -645.18
PLENUM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 17-JUL-16:00 0.00 0.00 0.00 -19301.69 0.00 0.00 3839.29 6750.00 4500.00 7122.95 0.00 913.91 0.00 0.00 0.00 0.00 0.00 -3824.46


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
SOUTH PERIMETER 27-JAN-01:00 0.00 0.00 3432.01 0.00 0.00 0.00 0.00 79.20 52.80 0.00 0.00 0.00 0.00 0.00 -1364.89 0.00 -1019.98 -1179.15
EAST PERIMETER 27-JAN-01:00 0.00 0.00 1549.36 0.00 0.00 0.00 0.00 34.20 22.80 0.00 0.00 0.00 0.00 0.00 -561.34 0.00 -437.13 -607.88
NORTH PERIMETER 27-JAN-01:00 0.00 0.00 3373.22 0.00 0.00 0.00 0.00 79.20 52.80 0.00 0.00 0.00 0.00 0.00 -1281.63 0.00 -1019.98 -1203.61
WEST PERIMETER 27-JAN-01:00 0.00 0.00 1549.24 0.00 0.00 0.00 0.00 34.20 22.80 0.00 0.00 0.00 0.00 0.00 -561.34 0.00 -437.13 -607.77
CORE 27-JAN-01:00 0.00 0.00 3603.16 0.00 0.00 0.00 0.00 148.20 98.80 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -1806.81 -2043.34
PLENUM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 27-JAN-01:00 0.00 0.00 13506.98 0.00 0.00 0.00 0.00 375.00 250.00 0.00 0.00 0.00 0.00 0.00 -3769.20 0.00 -4721.03 -5641.76



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
SOUTH ZONE UNITARY 0.4397 0.0000 11.0000 1.0000 0.1038 0.4397 0.2361 1.0000 0.1038 0.2361    
EAST ZONE UNITARY 0.3045 0.0000 5.0000 1.0000 0.0472 0.3045 0.1550 1.0000 0.0472 0.1550    
WEST ZONE UNITARY 0.3538 0.0000 5.0000 1.0000 0.0472 0.3538 0.1334 1.0000 0.0472 0.1334    
CORE UNITARY 0.5792 0.0000 20.0000 1.0000 0.1888 0.5792 0.3260 1.0000 0.1888 0.3260    
NORTH ZONE UNITARY 0.4277 0.0000 11.0000 1.0000 0.1038 0.4277 0.2428 1.0000 0.1038 0.2428    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
SOUTH ZONE UNITARY 0.4397 0.0000 11.0000 1.0000 0.1038 0.4397 1.0000 1.0000 0.1038 0.2361    
EAST ZONE UNITARY 0.3045 0.0000 5.0000 1.0000 0.0472 0.3045 1.0000 1.0000 0.0472 0.1550    
WEST ZONE UNITARY 0.3538 0.0000 5.0000 1.0000 0.0472 0.3538 1.0000 1.0000 0.0472 0.1334    
CORE UNITARY 0.5792 0.0000 20.0000 1.0000 0.1888 0.5792 1.0000 1.0000 0.1888 0.3260    
NORTH ZONE UNITARY 0.4277 0.0000 11.0000 1.0000 0.1038 0.4277 1.0000 1.0000 0.1038 0.2428    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
SOUTH PERIMETER SOUTH ZONE UNITARY 0.009440 11.0000 0.000000 99.16 0.1038 1.0000 0.1038 1.000 0.1038
EAST PERIMETER EAST ZONE UNITARY 0.009440 5.0000 0.000000 42.73 0.0472 1.0000 0.0472 1.000 0.0472
NORTH PERIMETER NORTH ZONE UNITARY 0.009440 11.0000 0.000000 96.48 0.1038 1.0000 0.1038 1.000 0.1038
WEST PERIMETER WEST ZONE UNITARY 0.009440 5.0000 0.000000 42.74 0.0472 1.0000 0.0472 1.000 0.0472
CORE CORE UNITARY 0.009440 20.0000 0.000000 182.49 0.1888 1.0000 0.1888 1.000 0.1888


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
SOUTH ZONE UNITARY 0.009440 11.00 0.000000 99.1600 0.1038 0.1038 0.1038
EAST ZONE UNITARY 0.009440 5.00 0.000000 42.7350 0.0472 0.0472 0.0472
WEST ZONE UNITARY 0.009440 5.00 0.000000 42.7350 0.0472 0.0472 0.0472
CORE UNITARY 0.009440 20.00 0.000000 182.4900 0.1888 0.1888 0.1888
NORTH ZONE UNITARY 0.009440 11.00 0.000000 96.4800 0.1038 0.1038 0.1038


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
SOUTH PERIMETER SOUTH ZONE UNITARY AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4397 0.4397 0.4397 0.1038 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
EAST PERIMETER EAST ZONE UNITARY AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3045 0.3045 0.3045 0.0472 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
NORTH PERIMETER NORTH ZONE UNITARY AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4277 0.4277 0.4277 0.1038 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
WEST PERIMETER WEST ZONE UNITARY AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3538 0.3538 0.3538 0.0472 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE CORE UNITARY AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5792 0.5792 0.5792 0.1888 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
SOUTH ZONE UNITARY 0.4397 0.4397 0.4397 0.4397 0.1038 1.0000
EAST ZONE UNITARY 0.3045 0.3045 0.3045 0.3045 0.0472 1.0000
WEST ZONE UNITARY 0.3538 0.3538 0.3538 0.3538 0.0472 1.0000
CORE UNITARY 0.5792 0.5792 0.5792 0.5792 0.1888 1.0000
NORTH ZONE UNITARY 0.4277 0.4277 0.4277 0.4277 0.1038 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
SOUTH PERIMETER SOUTH ZONE UNITARY AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4397 0.4397 0.4397 0.1038 0.9577 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
EAST PERIMETER EAST ZONE UNITARY AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3045 0.3045 0.3045 0.0472 0.9550 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
NORTH PERIMETER NORTH ZONE UNITARY AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4277 0.4277 0.4277 0.1038 0.9761 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
WEST PERIMETER WEST ZONE UNITARY AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3538 0.3538 0.3538 0.0472 0.9550 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE CORE UNITARY AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5792 0.5792 0.5792 0.1888 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
SOUTH ZONE UNITARY 0.4397 0.4397 0.4397 0.4397 0.1038 1.0000
EAST ZONE UNITARY 0.3045 0.3045 0.3045 0.3045 0.0472 1.0000
WEST ZONE UNITARY 0.3538 0.3538 0.3538 0.3538 0.0472 1.0000
CORE UNITARY 0.5792 0.5792 0.5792 0.5792 0.1888 1.0000
NORTH ZONE UNITARY 0.4277 0.4277 0.4277 0.4277 0.1038 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Sec1.1A-General Information

Data
Weather File RUN PERIOD 1 ** Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300
Total gross floor area [m2] 463.60
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
SOUTH PERIMETER 99.16 99.16 0.00 85.76
EAST PERIMETER 42.73 42.73 0.00 85.76
NORTH PERIMETER 96.48 96.48 0.00 85.76
WEST PERIMETER 42.74 42.74 0.00 85.76
CORE 182.49 182.49 0.00 85.76
PLENUM 463.60 0.00 463.60 0.00
Totals 463.60 463.60 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 25.00
Number of hours cooling loads not met 2.00
Number of hours not met 27.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 149.68 42811.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 51.33 13612.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- GeneralLights 79.36 6750.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- General 52.91 4500.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 56.90 1804.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 52.91 240.49
Natural Gas 0.00 149.68
Additional 0.00 0.00
Total 52.91 390.17


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 171.18
Space Heating 0.00
Space Cooling 110.72
Fans (All) 122.73
Service Water Heating 0.00
Receptacle Equipment 114.12
Miscellaneous (All) 518.75
Subtotal 518.75


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 322.86
Service Water Heating 0.00
Miscellaneous (All) 322.86
Subtotal 322.86


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 20.34
Space Heating 38.36
Space Cooling 13.16
Fans (All) 14.58
Service Water Heating 0.00
Receptacle Equipment 13.56
Miscellaneous 0.00


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
OFFICE LIGHTING 2 2939. 8760.
OFFICE OCCUPANCY 2 2436. 4472.
SHADETRANSSCH 0. 0.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
OFFICE HEATING SETPOINTS OFFICE THERMOSTAT DUAL SP CONTROL January 22.00 365 22.00 365
OFFICE COOLING SETPOINTS OFFICE THERMOSTAT DUAL SP CONTROL July 22.00 365 22.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
SOUTH PERIMETER 8760.00 0.00 0.00 0.00 0.00
EAST PERIMETER 8760.00 0.00 0.00 0.00 0.00
NORTH PERIMETER 8760.00 0.00 0.00 0.00 0.00
WEST PERIMETER 8760.00 0.00 0.00 0.00 0.00
CORE 8760.00 0.00 0.00 0.00 0.00
PLENUM 8638.00 122.00 0.00 0.00 0.00
Min 8638.00 0.00 0.00 0.00 0.00
Max 8760.00 122.00 0.00 0.00 0.00
Average 8739.67 20.33 0.00 0.00 0.00
Sum 52438.00 122.00 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
SOUTH PERIMETER 25376.00 0.00 0.00 0.00 0.00
EAST PERIMETER 9568.00 0.00 0.00 0.00 0.00
NORTH PERIMETER 25376.00 0.00 0.00 0.00 0.00
WEST PERIMETER 9568.00 0.00 0.00 0.00 0.00
CORE 48724.00 0.00 0.00 0.00 0.00
PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 48724.00 0.00 0.00 0.00 0.00
Average 19768.67 0.00 0.00 0.00 0.00
Sum 118612.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
SOUTH PERIMETER 8760.00 0.00 0.00 0.00 0.00
EAST PERIMETER 8760.00 0.00 0.00 0.00 0.00
NORTH PERIMETER 8760.00 0.00 0.00 0.00 0.00
WEST PERIMETER 8760.00 0.00 0.00 0.00 0.00
CORE 8760.00 0.00 0.00 0.00 0.00
PLENUM 8760.00 0.00 0.00 0.00 0.00
Min 8760.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 8760.00 0.00 0.00 0.00 0.00
Sum 52560.00 0.00 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
SOUTH PERIMETER 25376.00 0.00 0.00 0.00 0.00
EAST PERIMETER 9568.00 0.00 0.00 0.00 0.00
NORTH PERIMETER 25376.00 0.00 0.00 0.00 0.00
WEST PERIMETER 9568.00 0.00 0.00 0.00 0.00
CORE 48724.00 0.00 0.00 0.00 0.00
PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 48724.00 0.00 0.00 0.00 0.00
Average 19768.67 0.00 0.00 0.00 0.00
Sum 118612.00 0.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2022-03-23 15:31:30

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None